a. PG III to VIII occupancies
(1) Every building or part of a building, except that of PG I or II (residential floors), having a total floor area of more than that specified in column (3) of Table 6.3A having regard to the purpose group of the building or part of the building, shall be installed with a fire
alarm system, either of the automatic or manual type as indicated in column (4), which shall be an electrically supervised system complying with the requirements of the SS 645. The fire alarm system shall be connected to the SCDF’s Operations
Centre through an approved alarm monitoring company if required under Cl.6.3.8.
Effective Date: 10 May 2019
E
Explanations & Illustrations
Clause 6.3.1a.(1) : General
Figure 6.3.1a.(1) - 1
Based on the floor area of 1st storey, the above building is required to be provided with manual fire alarm system to 1st, 2nd and 3rd storey, which are for commercial usage. The bells of the alarm system shall be extended to the common areas (lobbies, corridors, staircases, etc.) of the residential floor at 4th storey.
Warehouse
Single storey warehouse not exceeding 2000m² is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the building is small, hence escape to the exterior via exit doors would be straight forward.
Warehouse building of 2 to 4 storeys and having a total floor area (per storey) of greater than 1000m² is required to provide manual type of fire alarm system. This manual fire alarm system (break glass type) is not required to be connected to an approved alarm monitoring company.
Warehouse building which is more than 4 storeys is required to be provided with automatic fire alarm system such as smoke or heat detection types, irrespective of the floor area per storey.
Factory
Single storey factory building not exceeding 400m² is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the building is small, hence escape to the exterior via exit doors would be straight forward.
Factory building of 2 to 4 storeys and having a total floor area (per storey) of greater than 200m² is required to be provided with manual type of fire alarm system. This manual fire alarm system (break glass type) is not required to be connected to an approved alarm monitoring company.
Factory building which is more than 4 storeys is required to be provided with automatic fire alarm system such as smoke or heat detection system, irrespective of the floor area per storey.
Figure 6.3.1a.(1) - 2
Even though the warehouse floor has less than 1000m², the whole building is required to be provided with manual fire alarm system as the factory floor (per storey) exceeds 200m².
Figure 6.3.1a.(1) - 3
Although the floor area of each factory floor is less than 200m², the building is required to be provided with manual fire alarm system as the warehouse located at 1st storey exceeds 1000m².
Figure 6.3.1a.(1) - 4
Factory or Warehouse
As the factory floor area per storey is less than 200m² and the warehouse floor area is less than 1000m² there is no need to provide fire alarm system unless requested by the SCDF. It should be noted that if in the event that warehouse floor is granted change of use to factory, a manual fire alarm system will be required to be provided to the whole building. The main reasons for the difference in floor area between factory and warehouse are:
a. occupants load of factory is higher than warehouse;
b. occupants would be working for long hours in factory as compared to warehouse where workers would only be involved when there is movement of goods in/out of the building.
Owners of factory or warehouse installed with manual fire system could opt for connection to the approved alarm monitoring station. Approved alarm monitoring stations are private monitoring companies. Owing to excessive false alarm signals being received by fire stations in the past, such monitoring was introduced to screen and verify the activation of automatic fire alarm signals.
Office/Shop
Single storey shop or office building not exceeding 400m2 is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the buildings are small, hence escape to the exterior via exit doors would be straight forward.
Building of 2 to 4 storeys and having a total floor area (per storey) of greater than 200m2 is required to be provided with manual type of fire alarm system. This manual fire alarm system (break glass type) is not required to be connected to an approved alarm monitoring company.
Building which is more than 4 storeys is required to be provided with both automatic fire alarm system such as smoke or heat detection system and manual fire alarm system, regardless of the floor area per storey.
Place of Public Resort
1. With stay-in facilities:
Single storey building used as a place of public resort with stay-in facilities shall be provided with manual type of fire alarm system, regardless of the floor area.
Building of 2 or more storeys shall be provided with both automatic fire alarm system such as smoke or heat detector system and manual fire alarm system, regardless of the floor area per storey.
The main reason for having more stringent requirement in respect of the provision of fire alarm system is the presence of sleeping risk involving guests.
2. Without stay-in facilities:
Single storey building used as a place of public resort without stay-in facilities and having a floor area not greater than 400m2 is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the building is small, hence escape to the exterior via exit doors would be straight-forward.
Building of 2 to 4 storeys and having a total floor area (per storey) of greater than 200m2 shall be provided with manual fire alarm system. This alarm system is not required to be connected to an approved alarm monitoring station. Building which is more than 4 storeys is required to be provided with both automatic fire alarm system such as smoke or heat detection system and manual fire alarm system, regardless of the floor area per storey. This is in compliance with column (4) of Table 6.3A. The complementary manual fire alarm system would allow occupants to activate the system before the automatic smoke or heat detection system is set-off by the smoke or heat from the fire.
Mixed Occupancy
When there are two or more purpose groups in a building, the strictest requirement for any one of the purpose groups shall be applicable to the whole building.
Figure 6.3.1a.(1) - 5 : Example of office/shop/public resort usage
Even though the whole building is not more than 4 storey, it is required to be provided with both automatic and manual fire alarm systems, owing to the sleeping risk in the 2nd & 3rd storeys.
Figure 6.3.1a.(1) - 6
Although the floor area of each floor is less than 200m2, the building is required to be provided with both automatic and manual fire alarm systems because of public resort with stay-in facilities.
Figure 6.3.1a.(1) - 7
As the area per storey is less than 200m² and the public resort does not have stay-in facilities, there is no need to provide fire alarm system unless otherwise required by the SCDF.
School
1. Single storey school building is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the building is single storey without sleeping accommodation, hence escape to the exterior via exit doors would be straight forward.
2. Building of 2 to 4 storeys without sleeping accommodation and having a total floor area (per storey) of greater than 400m2 is required to be provided with automatic type of fire alarm system. This automatic fire alarm system is not required to be connected to an approved alarm monitoring station. If the total floor area per storey exceeds 4000m², then both automatic and manual fire alarm system are required to be provided under Cl.6.3.1a.(2).
3. Building of 2 to 4 storeys with sleeping accommodation shall be provided with both automatic and manual fire alarm system.
4. Building which is more than 4 storeys but less than 24m in habitable height without sleeping accommodation shall be provided with automatic type fire alarm system. If the total floor area per storey exceeds 4000m², then both automatic and manual fire alarm system shall be provided under Cl.6.3.1a.(2).
5. Building which is more than 4 storeys but less than 24m in habitable height with sleeping accommodation shall be provided with both automatic and manual fire alarm system.
Healthcare occupancy
1. With stay-in facilities:
Single storey building used as healthcare occupancy e.g. hospital, old folk home etc., with stay-in facilities shall be provided with manual fire alarm system, regardless of the floor area.
Building of 2 or more storeys shall be provided with both automatic fire alarm system such as smoke or heat detector system and manual fire alarm system, regardless of the floor area per storey.
The main reason for having more stringent requirement in respect of the provision of fire alarm system for such premises is to address the concerns of sleeping risk.
2. Without stay-in facilities:
Single storey building used as healthcare occupancy without stay-in facilities and regardless of the floor area is not required to be provided with fire alarm system unless otherwise specified by the SCDF. The main reason is that the building is single storey without sleeping accommodation, hence escape to the exterior via exit doors would be straight forward.
Building of 2 to 4 storeys and having a total floor area (per storey) of greater than 200m2 shall be provided with manual fire alarm system. This alarm system is not required to be connected to an approved alarm monitoring company. The total floor area per storey of a 2 to 4 storeys building shall not exceed 4000m² unless automatic and manual fire alarm system are provided. See Cl.6.3.1a.(2).
Building of more than 4 storeys is required to be provided with both automatic fire alarm system such as smoke or heat detection system and manual fire alarm system, regardless of the floor area per storey. This is in compliance with column (4) of Table 6.3A. The complementary manual fire alarm system would allow occupants to activate the system before the automatic smoke or heat detection system is set-off by the smoke or heat from the fire.
3. Dormitories/Hostels:
Building of single storey used as dormitory/hostel shall be provided with manual fire alarm regardless of the floor area subject to Cl.6.3.1a.(2), which stipulates that the total floor area per storey of a 2 to 4 storeys buildings shall not exceed 4000m² unless both automatic and manual fire alarm system are provided.
Building of more than 1 storey used as dormitory/hostel shall be provided with both automatic and manual fire alarm system.
Figure 6.3.1a.(1) - 8 : School building of 2 to 4 storeys with
floor area per storey more than 400m2
School buildings exceeding 4 storeys but not exceeding 24m in habitable height shall be provided with automatic fire alarm system. If the above 4 storey building is provided with sleeping accommodation, then both automatic and manual fire alarm system shall be provided, regardless of the floor area per storey.
Figure 6.3.1a.(1) - 9
School buildings exceeding 4 storeys but not exceeding 24m in habitable height shall be provided with both automatic and manual types of fire alarm system.
Figure 6.3.1a.(1) - 10 : Mixed occupancy
Owing to the sleeping risk in the homes, the building is required to be provided with both automatic fire alarm system and manual fire alarm system.
Figure 6.3.1a.(1) - 11
Although the floor area of each floor is less than 200m², the building is required to be provided with both automatic fire alarm system and manual fire alarm system because of clinic with stay-in facilities and old folk homes.
Figure 6.3.1a.(1) - 12
As the area per storey is less than 200m2 and the clinic and health care occupancies do not have stay-in facilities, there is no need to provide automatic fire alarm system unless otherwise required by the SCDF.
Amendment History
6.3.1a(1) |
10 May 2019 |
10 May 2019 |
Clarification |
Every building or part of a building, except that of PG I or II (residential floors), having a total floor area of more than that specified in column (3) of Table 6.3A having regard to the purpose group of the building or part of the building, shall be installed with a fire alarm system, either of the automatic or manual type as indicated in column (4), which shall be an electrically supervised system complying with the requirements of the SS CP 10. The fire alarm system shall be connected to the SCDF’s Operations Centre through an approved alarm monitoring company if required under Cl.6.3.7. |
10 May 2019 |
Download
|
(2) Notwithstanding Cl.6.3.1a.(1) above, if the total floor area per storey of a 2 to 4 storey building of any of the PG III to VIII exceeds
the sizes as stipulated in column (2) of Table 3.2A, the building
shall be provided with an automatic fire alarm system.
E
Explanations & Illustrations
Clause 6.3.1a.(2) : General
Figure 6.3.1a.(2)
The above figure shows a typical floor area exceeding 5000m², accordingly it requires sprinkler protection for such excessive floor area. By compartmentalising the floor area with each compartment not exceeding 4000m², sprinkler installation will be waived. In its place, automatic fire alarm system is required to be provided. Therefore, notwithstanding the provision of compartmentation, if the total floor area per storey of a 2 to 4 storey building exceeds 4000m², the building shall be provided with automatic fire alarm system. This requirement will not apply to a single storey building. The automatic fire alarm system serves to provide early detection to the occupants. Hence, it allows more time for occupants to evacuate.
b. PG II mixed occupancy
For PG II mixed occupancy buildings where an automatic sprinkler system and/ or electrical fire alarm system is provided to the non-residential part of the building:
Effective Date: 1 June 2020
Amendment History
6.3.1b |
|
1 Nov 2016 |
Revised, extracted from SCDF's circular. Formerly Cl.6.3.1(b)(i) & (ii) |
|
11 Aug 2016 |
-
|
6.3.1b(3) |
10 May 2019 |
Immediate |
Clarification |
Connection of the fire alarm system to an approved alarm monitoring company stipulated under Cl.6.3.7 is not required if the number of non-residential floors is not more than one storey. |
10 May 2019 |
Download
|
6.3.1b. ( dated 2 Dec 2019) |
2 Dec 2019 |
1 June 2020 |
Revised |
b. PG II mixed occupancy For PG II mixed occupancy buildings where an automatic sprinkler system and/or electrical fire alarm system is provided to the non-residential part of the building: (1) Alarm sounders shall be installed within the non-residential units, at the common areas of the non-residential floors and extended to the immediate two residential floors above the non-residential floor. (2) The alarm sounders shall be able to produce a minimum sound level of 65dBA, or 5dBA above the ambient noise level in all parts of such areas. (3) Connection of the fire alarm system to an approved alarm monitoring company stipulated under Cl.6.3.8 is not required if the number of non-residential floors is not more than one storey. |
2 Dec 2019 |
Download
|
(1) Alarm sounders shall be able to produce a minimum sound level of 65dBA, or 5dBA above the ambient noise level, whichever is greater but not more than 120dBA, at all parts of the following areas:
(a) the non-residential units;
(b) the common areas of the non-residential floors; and
(c) the common areas of the immediate two residential floors above the non-residential floor.
R
Rationale - Clause 6.3.1b.(1)
During a fire emergency in non-residential spaces, the building occupants closer to these spaces should be notified via fire alarm sounding. As each residential unit is a fire compartment by itself, total evacuation of the building occupants is not necessary. However, those units closer to the fire source could be affected by smoke and fire and hence need to be alerted to be prepared for evacuation. For units located further away from the fire floor, it is safer for the occupants to remain within their units. These occupants will have sufficient time to evacuate if the fire cannot be controlled/contained. Phased evacuation could reduce the risk of stampede and injury as compared to total evacuation.
(2) Connection of the fire alarm system to an approved alarm monitoring company stipulated under Cl.6.3.8 is not required if the number of
non-residential floors is not more than one storey.
c. Dormitories
For dormitories, including workers' dormitories, an electrical fire alarm system shall be provided as follows:
(1) For single storey dormitory buildings, manual fire alarm system is to be provided to comply with SS 645.
(2) For dormitories exceeding one storey, both automatic and manual fire alarm systems shall be provided to comply with SS 645.
d. The following are not required to be provided with electrical fire alarm system:
(1) Roof level of single storey buildings with roof height not more than 12m or inaccessible pitched roof up to 24m from grade level used solely for roof-mounted PV installations in accordance with Cl.10.2.1b.(1).
(2) Roof level of an external/ open-sided overhead bridge/ shed/ linkway/ walkway with clear width less than 6m, roof height not more than 12m and used solely for roof-mounted PV installations in accordance with Cl.10.2.1b.(1).
a. An electrical fire alarm system of the automatic or manual type shall be provided with a fire alarm panel to indicate the location of the alarm which has been actuated or operated. Such an alarm panel shall be accurate to the
maximum allowed alarm group area limitations specified in SS 645.
E
Explanations & Illustrations
Clause 6.3.2a. : Fire alarm panel
( No illustration )
1. Fire fighters responding to a fire call would first, on arrival at the scene, need to check the fire alarm panel to confirm the location of the alarm, which has been actuated or operated before proceeding to the fire site.
2. The Fire alarm panel monitors the actuation of detectors, call-points and sprinkler flow switch.
3. A permanent fire zone chart or minic panel shall be displayed at the Fire alarm panel location to provide information on originality of the alarm. The fire zone chart or minic panel shall be installed in accordance with the floor or building orientation. All the alarm zones and Fire alarm panel zones if provided should be clearly depicted on the fire zone chart/minic panel. Additional information such as, fire engine accessway, location of breeching inlets, fire hydrant, sprinkler control valve, hosereel and fire extinguisher should be provided on the fire zone chart/minic panel where applicable. This would help the fire fighters to identify the location of fire engine accessway, breeching inlets etc., when they arrived at the fire site.
4. Where addressable fire alarm system is used, fire alarm panel shall be provided additional to the programmable message on display.
b. The associated control and supervisory equipment, indicating equipment, wiring and arrangement of power supplies for the fire alarm panel shall comply with the requirements in SS 645.
c. All automatic systems which are activated via the general building alarm shall be connected directly to the fire alarm panel.
d. The fire alarm panel shall be located near the main entrance of the building, in the Fire Command Centre (FCC), in the guardhouse or in the fire lift lobby.
E
Explanations & Illustrations
Clause 6.3.2d. : Fire alarm panel
( No illustration )
Where FCC is not provided, the fire alarm panel is usually near the main entrance of the building or in the guardhouse.
Where sub-fire alarm panels are provided, they shall be located at the fire lift lobby, smoke-stop lobby, protected staircase in that order of priority or at the main point of entry into the area covered by the alarm zone.
e. Sub fire alarm panel, where provided, shall comply with the requirements in SS 645 be located at the fire lift lobby, smoke-free lobby, or protected staircase, in that order of priority, or at the main point of entry into the area covered by the alarm zone.
6.3.3 Manual alarm call points
E
Explanations & Illustrations
Clause 6.3.3 : General
Figure 6.3.3
1. Manual call points shall be located:
(a) along exit routes leading to exit staircase;
(b) adjacent to hose reels;
(c) at floor landing of exit staircases; and
(d) at exits to the street.
2. Manual call points shall be so located such that no occupant needs to run more than 30m, measured from any position within the building to a manual call point.
a. In a manual alarm system, except as otherwise exempted in Cl.6.3.1, the manual call points shall be provided on every storey of the building
or part of the building and shall be so located that no person need travel more than 30m from any position within the building to activate the alarm.
b. Manual call points shall be located on exit routes preferably next to hose reels and in particular on the floor landings of exit staircases and at exits to the street. In the case where an automatic fire alarm system is provided, grouping for indication
of location of the manual call points shall comply with the requirements in SS 645.
c. Manual call points shall be located between 800mm and 1.2m above the finished floor level and shall be located at easily accessible and conspicuous positions free from obstructions. The installation of the sounding device shall be in accordance with SS 645.
d. Exemption
Manual call points can be omitted for the following:
(1) car parks, regardless whether the parking facility is standalone type or forms part of a building;
Effective Date: 01 Mar 2019
Amendment History
6.3.3d.(2) |
|
01 Mar 2019 |
New |
|
--- |
-
|
(2) open-to-sky roof gardens/terraces, provided an alarm sounder is extended to this level and positioned near the exit staircase except for developments where fire alarm system is not required; and
(3) mezzanine floor of factory unit, subject to compliance with Cl.9.6.1a.(2) and provided no person
on the mezzanine floor need to travel more than 30m to activate the nearest manual call point located on the main floor.
e. Manual call point shall be provided for buildings protected with an automatic fire sprinkler system or automatic fire alarm system.
Effective Date: 01 Mar 2019
Amendment History
6.3.3e |
|
01 Mar 2019 |
New |
|
--- |
-
|
6.3.4 Automatic fire alarm
E
Explanations & Illustrations
Clause 6.3.4 : Automatic fire alarm
( No illustration )
Automatic alarm system would not normally be provided to solely PG II buildings. However, there is an advantage of providing smoke detectors, as the detectors could detect the generation of smoke from even incipient fires, hence providing occupants early warning and adequate lead-time in evacuation. Automatic fire alarm system is required in buildings of more than 4 storeys having commercial cum residential mix, for example, shops with apartment/maisonette units above.
SS CP 10 gives general guidance for selection of detectors. Whenselecting the type of detectors, the likely fire behaviour of the contents of each part of the building, the processes taking place and the design of the building should be considered. The effective coverage of each type of detectors differs from each other. The location of placing the detectors and the spacing between detectors shall apply with the requirements in SS CP 10. Detectors shall be zoned into alarm group and be properly wired to achieve electrical supervision of the alarm circuit.
Where an automatic fire alarm system is required by this Code, the type, location, spacing and installation of the detectors shall comply with the requirements in SS 645.
6.3.5 Alarm device
E
Explanations & Illustrations
Clause 6.3.5 : Alarm device
( No illustration )
It is important that the sounding from the electrical fire alarm system, for example, installed in the office/shop/places of public resort, should be audible and readily distinguishable to all occupants.
All fire alarm sounders must generate the continuous ringing tone of the bell. In special environment where the use of bell tone is impractical or in area of high background noise level, other tone may be used, in which case SCDF’s permission must be sought.
The number of fire alarm sounders used should be sufficient to produce a minimum sound level of either 65 dBA, or 5 dBA above any other noise likely to persist for a period longer than 30 seconds, whichever is greater, in all parts of the buildings which are normally occupied.
In areas where a normal type of sounder may be ineffective, e.g. where the background noise is excessive, where the occupants are deaf or where hearing protection is likely to be worn, visual signals shall be provided. In general, visual signals shall not be used in place of audible alarms. The intensity of the light shall be sufficient to draw the attention of people in the vicinity.
In discos, nightclub and other places of entertainment, it is recommended that the sound system be electrically interlocked with the fire alarm system to enable the sound system to be automatically cut-off in the event that the fire alarm is activated.
a. General
(1) The alarm device, which should normally issue an audible or visible signal, unless specifically allowed or required otherwise by the SCDF, shall be actuated if the electrical fire alarm system is activated or operated. The type, number and location of the alarm device shall comply with the requirements in SS 645.
(2) All sounders and visual alarm signals in the building shall be actuated simultaneously in the event of an activation. However, in cases permitted or required by the SCDF where the operation of alarm sounders are grouped or activated in stages, the arrangement shall comply with the requirements in SS 645.
b. Audio alarm
The fire alarm sounder shall have a sound that is readily distinguishable from any other alarm systems. In places of entertainment or areas where sound and/or special effects lighting systems are installed, including KTV kiosks/booths placed within building premises, the sound systems shall be electronically interlocked with the fire alarm system to enable these systems to be automatically cut-off when the fire alarm system is activated.
Effective Date: 15 Mar 2021
Amendment History
6.3.5b |
10 May 2019 |
Immediate |
Change in requirements |
The fire alarm sounder shall have a sound that is readily distinguishable from any other alarm system. |
10 May 2019 |
Download
|
6.3.5b. (dated 15 Sep 2020) |
15 Mar 2021 |
15 Mar 2021 |
Revised |
b. Audio alarm
The fire alarm sounder shall have a sound that is readily distinguishable from any other alarm systems. In places of entertainment or areas where sound and/or special effects lighting systems are installed, the sound systems shall be electronically interlocked with the fire alarm system to enable these systems to be automatically cut-off when the fire alarm system is activated. |
15 Sep 2020 |
Download
|
c. Visual alarms
(1) Visual alarms shall be provided in addition to the audible alarms for buildings protected by fire alarm systems and separate visual alarm(s) shall be provided in the following:
(a) Where persons with hearing impairment can be isolated, especially when they are not in their identified locations, visual alarm(s) shall also be provided:
(i) in toilets and inside full-height partitioned cubicles;
(ii) car park floors;
(iii) lift lobbies; and
(iv) in places of entertainment, e.g., dance halls, gaming outlets, internet games cafes, arcades where users use headgear that affect hearing or areas where sound and/ or special effects lighting systems are installed.
(2) Visual alarms shall not be used in place of audible alarms.
Effective Date: 25 Aug 2023
Amendment History
6.3.5c(1)(c) |
1 March 2019 |
1 March 2019 |
Relocated and Revised |
In dance clubs, gaming centres, places of entertainment or areas where sound and/or special effects lighting systems are installed, they shall be electronically synchronised with the fire alarm system to enable these systems to be automatically cut-off when the fire alarm system is activated. |
|
-
|
6.3.5c. |
10 May 2019 |
Immediate |
Change in requirements |
(1) Provision
(a) Visual alarms shall be provided for buildings protected by fire alarm systems, and shall not be used in place of audible alarms.
(b) Visual alarms shall also be provided in places where persons can be isolated. This is to account for persons with severe hearing impairment, especially when they are not in their identified locations. Such isolated spaces includes full-height enclosed washroom spaces, car park floors, lift lobbies, etc..
(c) In dance clubs, gaming centres, places of entertainment or areas where sound and/or special effects lighting systems are installed, they shall be electronically synchronised with the fire alarm system to enable these systems to be automatically cut-off when the fire alarm system is activated.
(2) Siting of visual alarms
Visual alarms shall be located together with manual alarm call points. Where they are not readily visible from all accessible locations, additional visual alarms shall be provided. the height of the visual alarms shall be between 2m to 2.5m above finished floor level. |
10 May 2019 |
Download
|
6.3.5c. (dated 25 Aug 2023) |
25 Aug 2023 |
25 Aug 2023 |
Revised/Clarifications |
6.3.5c. Visual alarms
(1) Visual alarms shall not be used in place of audible alarms and shall be provided:
(a) for buildings protected by fire alarm systems
(b) in places, such as full-height enclosed washroom spaces, car park floors, lift lobbies, etc. where persons with hearing impairment can be isolated, especially when they are not in their identified locations; and
(c) in places of entertainment e.g. dance halls, gaming outlets, internet games cafes, arcades where users use headgear that affect hearing or areas where sound and/ or special effects lighting systems are installed.
(2) Siting of visual alarms
Visual alarms shall be located ……. |
25 Aug 2023 |
Download
|
6.3.5c.(1)(b) |
|
Immediate |
Relocated from Appendix 20 (Cl.7.2) of Fire Code 2013 |
|
--- |
-
|
6.3.5c.(2) and (3) |
|
Immediate |
Relocated from Appendix 20 (Cl.7.2) of Fire Code 2013 |
|
--- |
-
|
(3) Siting of visual alarms
Visual alarms shall be located together with fire alarm sounder. Where they are not readily visible from areas accessible to persons with hearing impairment who may be in isolation, additional visual alarms shall be provided. The height of the visual alarms shall be between 2m to 3m above finished floor level.
(4) Technical specifications
Visual alarms shall comply with all of the following requirements:
(a) They shall take the form of a flashing beacon or strobe light for use in conjunction with the conventional fire alarm system.
(b) They shall be clearly distinguishable from any other visual indicator used in the premises.
(c) They shall be labelled with the word “Fire” of at least 15mm in height and lettering colour shall contrast with the background.
(d) The flashing rate shall be within 30 to 130 flashes per minute.
(e) The visual alarm signal shall be in white or red.
(f) The flashing of all visual alarm signals within a same space/ room shall be synchronised.
(g) The intensity of the light signal shall be sufficient to draw the attention of people in the vicinity.
6.3.6 Home Fire Alarm Device (HFAD)
Effective Date: 2 Mar 2020
R
Rationale - Clause 6.3.6
Home Fire Alarm Devices (HFAD) provide occupants with early warning of fire and enable occupants to extinguish the fire before it escalates. At the same times, enable occupants to evacuate safely.
!
Note to QPs on Clause 6.3.6
There is no need for building owners to engage a QP for submitting plans to the SCDF solely for the voluntary installation of HFAD. However, if QPs are submitting plans to the SCDF or other government agencies for other fire safety works carried out for residential homes, then QPs shall indicate the locations of the fire alarm device(s) on the submitted plans.
Amendment History
6.3.6 |
|
1 Jun 2018 |
Extracted from SCDF's circular |
|
16 Nov 2017 |
-
|
6.3.6 (dated 2 Mar 2020) |
2 Mar 2020 |
2 Mar 2020 |
Clarification |
Home Fire Alarm Device (HFAD)
For individual residential units under PG I or II, HFAD shall be installed in accordance with all of the following requirements:
a. HFAD shall possess the following features and comply with all the requirements stated below:
(1) operate on smoke detection technology alone, or have a multi-sensor detector (a detector with multiple sensors built into the device) with smoke detection capability;
(2) indicator lights to inform users on the status/condition of the device(s);
(3) temporary silence/reset feature to address false alarms;
(4) alarm sounder with sound level compliant with any standard listed in item (7);
(5) test button to allow the device(s) to be tested/checked periodically;
(6) to be powered by long-life built-in battery (i.e. battery that lasts at least 10 years) with low battery alert capability, or to be wired to household electrical supply;
(7) detector design to comply with any of the following standards (EN 14604, AS 3786, UL 217);
(8) where two or more HFADs are installed, all devices shall be interconnected (either wired or wirelessly) such that when one of the HFADs is triggered, all connected HFADs shall sound an alarm if they are installed on 2 or more storeys (see Diagram 6.3.6a.(8)); and |
2 Mar 2020 |
Download
|
For individual residential units under PG I or II, HFAD shall be installed in accordance with all of the following requirements:
a. HFAD shall possess the following features and comply with all the requirements stated below:
(1) operate on smoke detection technology alone, or have a multi-sensor detector (a detector with multiple sensors built into the device) with smoke detection capability;
(2) indicator lights to inform users on the status/ condition of the device(s);
(3) temporary silence/ reset feature to address false alarms;
(4) alarm sounder with sound level compliant with any standard listed in item (7);
(5) test button to allow the device(s) to be tested/checked periodically;
(6) to be powered by long-life built-in battery (i.e., battery that lasts at least 10 years) with low battery alert capability, or to be wired to household electrical supply;
(7) detector design to comply with any of the following standards (EN 14604, AS 3786, UL 217);
Amendment History
6.3.6 |
|
1 Jun 2018 |
Extracted from SCDF's circular |
|
16 Nov 2017 |
-
|
6.3.6 (dated 2 Mar 2020) |
2 Mar 2020 |
2 Mar 2020 |
Clarification |
Home Fire Alarm Device (HFAD)
For individual residential units under PG I or II, HFAD shall be installed in accordance with all of the following requirements:
a. HFAD shall possess the following features and comply with all the requirements stated below:
(1) operate on smoke detection technology alone, or have a multi-sensor detector (a detector with multiple sensors built into the device) with smoke detection capability;
(2) indicator lights to inform users on the status/condition of the device(s);
(3) temporary silence/reset feature to address false alarms;
(4) alarm sounder with sound level compliant with any standard listed in item (7);
(5) test button to allow the device(s) to be tested/checked periodically;
(6) to be powered by long-life built-in battery (i.e. battery that lasts at least 10 years) with low battery alert capability, or to be wired to household electrical supply;
(7) detector design to comply with any of the following standards (EN 14604, AS 3786, UL 217);
(8) where two or more HFADs are installed, all devices shall be interconnected (either wired or wirelessly) such that when one of the HFADs is triggered, all connected HFADs shall sound an alarm if they are installed on 2 or more storeys (see Diagram 6.3.6a.(8)); and |
2 Mar 2020 |
Download
|
(8) where two or more HFADs are installed, all devices shall be interconnected (either wired or wirelessly) such that when one of the HFADs is triggered, all connected HFADs shall sound an alarm simultaneously (see Diagram 6.3.6a.(8)); and
E
Explanations & Illustrations
Clause 6.3.6a.(8) : Home Fire Alarm Device (HFAD)
( No illustration )
Such wireless connectivity shall comply with IMDA’s Technical Specification for Short Range Devices. It is also preferred that the devices adhere to requirements in the TR40 Technical Reference for Sensor Network for Smart Nation (Homes).
(9) the HFAD shall be either:
(a) listed by any accredited certification body accepted by the SCDF, or
(b) listed by Underwriters Laboratories (UL), or
(c) listed under the ActivFire Scheme, or
!
Note to QPs on Clause 6.3.6a.(9)(c)
For HFAD listed under ActiveFive Scheme, visit website https://activfire.csiro.au/outline.asp
(d) CE marked with certification from approved 3rd party Notified Bodies, or
(e) listed under BSI Product Directory.
!
Note to QPs on Clause 6.3.6a.(9)(e)
For HFAD listed under BSI Product Directory, visit website https://www.bsigroup.com/en-GB/Product-Directory/
b. Additional independent functions to enhance the operation of the HFAD may be included as optional features (Such as connection to smart home systems, remote controls, visual alarms, vibrating pads, etc.) of the HFAD, given that the requirements indicated
in Cl.6.3.6a. are met.
c. Table 6.3.6 states the minimum number of HFAD required for different home types, as well as the locations in which the detectors shall be installed.
TABLE 6.3.6 MINIMUM NUMBER OF HFAD TO BE INSTALLED FOR DIFFERENT HOME TYPES
|
Home type
|
Number and location of detectors (Also refer to Diagram 6.3.6 c. - 1 & 2)
|
Single storey homes:
(1) HDB flats
(2) Apartments/Condominium
(3) Single storey landed dwellings
|
(1) Minimum 1 smoke detector
(2) Installed along circulation area / escape route, e.g. living room, corridor
(3) Optional: Additional detectors can be installed in other spaces for enhanced protection.
|
Multi-storey homes:
(1) Landed/Non-landed dwellings
(2) HDB flats
(3) Apartments/ Condominiums
|
(1) Minimum 1 smoke detector per storey
(2) For storeys with circulation area > 70m2, at least 2 smoke detectors need to be installed on that storey.
(3) Installed along circulation area / escape route e.g. living room, corridor, and/or staircase landing
(4) Optional: Additional detectors can be installed in other spaces for enhanced protection.
|
6.3.7 Alarm system for cinema
A theatre or cinema shall be provided with an electrical fire alarm system of the manual type complying with all of the following:
a. The manual alarm system shall be installed in the lobbies and other areas adjoining the hall and shall be connected to the SCDF Operations Centre through an approved alarm monitoring company.
E
Explanations & Illustrations
Clause 6.3.7a. : Alarm system for cinema
( No illustration )
Manual alarm call points are required to be provided in the lobbies and other areas adjoining the cinema hall. Occupants escaping from a fire in the hall could break the glass of the call point to activate the alarm.
Manual alarm call points and sounding devices are not allowed to be installed in the hall owing to the nature of the occupancy, the lighting level and seating arrangement. The sounding of any alarm bells in the cinema hall when a show is in progress would cause confusion and panic to the occupants.
b. Visual indicators and audible sounders shall be installed in the projection room and in another room where a designated staff member can alert the audience in case of a fire.
E
Explanations & Illustrations
Clause 6.3.7b. : Alarm system for cinema
( No illustration )
In place of general sounding alarm, visual alarm indicator such as beacon lights and audible alarm indicator, instead of alarm bells are required to be installed in the projection room and cinema manager office to alert both the projectionists and the manager immediately, so that occupants in the cinema hall would be advised through the projection screen and or public address system to evacuate the hall in an orderly and calm manner.
c. The provision of the fire protection system in cinema which forms part of a building shall be similar to that of the building.
E
Explanations & Illustrations
Clause 6.3.7c. : Alarm system for cinema
( No illustration )
In situations where the cinema hall or halls are located within a commercial building, the fire protection system of the commercial building such as sprinkler system, would be required to be extended to cover the cinema hall, lobbies, projection room and other ancillary areas.
6.3.8 Connection to the SCDF Operations Centre
The electrical fire alarm system required to be installed in a building or premises under this clause shall be connected to the SCDF Operations Centre through an approved alarm monitoring company when the building or premises is:
a. a health care occupancy, hotel or other similar occupancies, or
b. an oil refinery, oil depot, general warehouse, chemical plant or other high hazard factory or premises, or
c. a theatre, cinema or concert hall as specified in Cl.6.3.7, or
d. a building required under the provisions of this Code to be protected by an automatic fire alarm (except those exempted under Cl.6.3.1b.) or fire extinguishing system.
6.3.9 Sprinkler-protected building
Effective Date: 1 Sep 2021
E
Explanations & Illustrations
Clause 6.3.9 : Sprinkler-protected building
( No illustration )
Where sprinkler system is provided in any building, there is no necessity to provide automatic fire alarm system (heat or smoke detection system). Exception is for electrical rooms, AHU room, lift motor room, battery room, MDF room, PABX room where sprinkler system is replaced by electrical fire alarm system. Smoke detectors are also required to be installed in sprinkler-protected buildings to operate the smoke control system in atria, smoke purging system or control system in basement occupancies.
Amendment History
6.3.9 |
1 Sep 2021 |
1 Sep 2021 |
Clarification |
Sprinkler-protected building
Where sprinkler system is required by this Code, provision of automatic thermal/smoke detectors in sprinkler-protected premises will be exempted except where such detectors are required to activate or operate the sprinkler or other systems. |
1 Sep 2021 |
Download
|
Where sprinkler system is required by this Code, provision of automatic thermal/ smoke detectors in sprinkler-protected premises is exempted except where such detectors are required to activate/ operate the sprinkler, engineered smoke control system or other systems.
Amendment History
6.3.9 |
1 Sep 2021 |
1 Sep 2021 |
Clarification |
Sprinkler-protected building
Where sprinkler system is required by this Code, provision of automatic thermal/smoke detectors in sprinkler-protected premises will be exempted except where such detectors are required to activate or operate the sprinkler or other systems. |
1 Sep 2021 |
Download
|
6.3.10 Exemption of automatic fire alarm protection
Effective Date: 1 Mar 2022
Amendment History
6.3.10 |
|
16 Jun 2016 |
Extracted from SCDF's circular |
|
15 Dec 2015 |
-
|
6.3.10 (dated 1 Sep 2021) |
1 Sep 2021 |
1 Mar 2022 |
Revised/ Clarification |
Exemption of automatic fire alarm protection
The following areas are exempted from automatic fire alarm protection in an automatic fire alarm building:
a. areas which are covered with trellises, louvres or perforated panels having 50% or more evenly distributed effective free openings; and
b. external open-sided linkways not exceeding 5m in width measured from eave to eave, provided these areas are not for commercial activities or storage. |
1 Sep 2021 |
Download
|
The following areas are exempted from automatic fire alarm protection in an automatic fire alarm building:
a. External open-sided linkways not exceeding 5m in width measured from eave to eave, provided these areas are not for commercial activities or storage.
b. Areas which are covered with trellises, louvres or perforated panels having 50% or more evenly distributed effective free openings. An alarm sounder and visual alarm shall be provided near the exit staircase in accordance with SS 645.
c. Open-to-sky roof gardens/ terraces located within PG II buildings or mixed-use residential buildings, provided there are no covered commercial activities/ spaces at the open-to-sky roof gardens/ terraces. When there is other non-residential occupancy other than the open-to-sky roof gardens/ terraces located within the same PG II building, the alarm sounder and visual alarm shall be extended to the open-to-sky roof gardens/ terraces and positioned near the exit staircase in accordance with SS 645.
Amendment History
6.3.10 |
|
16 Jun 2016 |
Extracted from SCDF's circular |
|
15 Dec 2015 |
-
|
6.3.10 (dated 1 Sep 2021) |
1 Sep 2021 |
1 Mar 2022 |
Revised/ Clarification |
Exemption of automatic fire alarm protection
The following areas are exempted from automatic fire alarm protection in an automatic fire alarm building:
a. areas which are covered with trellises, louvres or perforated panels having 50% or more evenly distributed effective free openings; and
b. external open-sided linkways not exceeding 5m in width measured from eave to eave, provided these areas are not for commercial activities or storage. |
1 Sep 2021 |
Download
|
6.3.11 Video Image Fire Detection System (VIFDS)
Effective Date: 01 Mar 2019
R
Rationale - Clause 6.3.11
This new clause allows VIFDS to be used to complement conventional smoke, heat and flame detectors in an electrical fire alarm system. It is best installed in premises with large open space and high roofs such as production areas, halls, warehouses etc.. VIFDS can cover gaps where smoke detectors are unable to detect particles due to high air flow and can help reduce false alarm. It is compulsory to install VIFDS in unmanned buildings as there are no security or operation personnel to check and confirm whether there is an actual fire when the fire alarm system is activated after office/operating hours.
Amendment History
6.3.11 |
|
01 Mar 2019 |
New |
|
--- |
-
|
a. VIFDS shall be installed in addition to the electrical fire alarm system for buildings which meet all of the following conditions:
(1) It is an unmanned buildings belonging to PG III to VIII.
(2) It has an internal open space of more than 2000m2 or a ceiling height of more than 12m.
(3) It requires the provision of automatic fire alarm system in accordance with Table 6.3A
.
b. VIFDS shall comply with SS 645 and can be used to complement smoke, heat and flame detectors in an electrical fire alarm system.
c. It shall be connected to the SCDF Operations Centre through an approved alarm monitoring company. Alarm signals and live video images of fire and/or smoke captured shall be transmitted to the approved alarm monitoring company upon activation of the
building fire alarm system.
Amendment History
6.3.11 |
|
01 Mar 2019 |
New |
|
--- |
-
|