sg-crest
Hotlines
  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

  • Fire Hazard Reporting

    1800 280 0000

  • General Enquiries

    1800 286 5555

  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

Legend: Explanations & Illustrations Rationale Note Figures & Tables Revision history

9.4 PURPOSE GROUP IV OCCUPANCY

9.4.1 General

a. Means of escape

(1) Aboveground office floors 

One exit staircase is permitted to serve an aboveground office floor
provided:

(a) the habitable height of the floor does not exceed 15m; 

(b) the floor does not be located above 4th storey; and 

E

(c) the AFA of the floor does not exceed 200m².

Effective Date: 01 Mar 2019

(2) Underground office floors

One exit staircase is permitted to serve an office basement provided:

(a) the building is of non-combustible construction;

(b) the depth of basement storey does not exceed 9m below the average ground level;

(c) compartment below ground does not comprise more than one storey; and

(d) the AFA of each basement storey, including service ducts, lift shafts, toilets, staircase, etc., does not exceed 200m2.

Effective Date: 01 Mar 2019

b. Structural fire precautions

(Not in use)

Updated 1 Mar 2024