TABLE 1.2A : CODES & STANDARDS
TABLE 1.2A : CODES & STANDARDS | ||
Name | Description | Remarks |
SINGAPORE STANDARDS | ||
SS CP 52 | CoP for Automatic Fire Sprinkler System | |
SS 99 | Specifications for Welded Low Carbon Steel Cylinders for Storage and Transportation of Low-Pressure Liquefiable Gases | |
SS141 | Specification for Unplasticised PVC pipe for Cold Water Services and Industrial Uses | |
SS 213 | Unplasticised PVC Pipes and Fittings for Soil, Waste and Vent Application | |
SS 232 Pt 1 to 6 | Portable Fire Extinguishers | Replaced by SS EN 3 - 7 to 10 |
SS 233 | Specifications for Flexible Rubber Tubing, Rubber Hose and Rubber Hose Assemblies for Use in LPG Vapour Phase Installations | |
SS 254 | Electrical Apparatus for Explosive Gas Atmospheres | Replaced by IEC 60079 |
SS 263
Pt 2 | Luminaires - Particular Requirements for Luminaires for Emergency Lighting | Replaced by IEC 60598-2-22 |
SS 281 | Specifications for Pressure Regulators for LPG | |
SS 286 | Caution Labelling for Hazardous Substances | Replaced by SS 586 |
SS 294 | Specifications for Valves for Use with Domestic and Industrial LPG Cylinders | |
SS 299 | Fire Resistant Cables | |
SS 332 | Specification for Fire Door | |
SS 333 | Specification for Fire Dampers | |
SS 489 | Specification for Fire Shutters | |
SS 508 | Graphical Symbols - Safety Colours & Safety Signs | Formerly SS 217 & SS 364 |
Pt 1 | Design Principles for Safety Signs & Safety Markings | |
Pt 2 | Design Principles for Product Safety Labels | |
SS 512 | CoP for the design, construction and operation of pipeline service corridors | |
SS 532 | CoP for the Storage of Flammable Liquids | Formerly CP 40
|
SS 535 | CoP for Installation, Operation, Maintenance, Performance Constructional Requirements of Mains Failure Standby Generating Systems | Formerly CP 31 |
SS 546 | CoP for Emergency Voice Communication Systems in Buildings | Formerly CP 25 |
SS 550 | CoP for Installation, Operation and Maintenance of El Passenger and Goods Lifts | Formerly CP 2 |
SS 551 | CoP for Earthing | Formerly CP 16
|
SS 563 | CoP for the Design, Installation & Maintenance of Em Lighting and Power Supply Systems in Building | Formerly CP 19 |
Pt 1 | Emergency lighting | |
Pt 2 | Installation Requirements and Maintenance Procedures | |
SS 572 | CoP for the Use of Timber in Buildings | Formerly CP 1 |
SS 575 | CoP for Fire Hydrant, Rising Mains and Hose Reel System | Formerly CP 29 |
SS 578 | CoP for the Use and Maintenance of Portable Fire Extinguishers | Formerly CP 55 |
SS 586 | Specification for Hazard Communication for Hazardous Chemicals and Dangerous Goods | Replaces SS 286 |
SS 608 | CoP for Gas Installation | Formerly CP 51 |
SS 634 | CoP for Fire Safety for Open Plant Processing Facilities in Oil, Chemical and Process Industries | |
SS 638 | CoP for Electrical Installations | Formerly CP 5 |
SS 641 | CoP for Fire Safety for Laboratories Using Chemicals | |
SS 645 | CoP for the Installation and Servicing of Electrical Fire Alarm Systems | Formerly CP 10 |
SS EN 3-7 | Portable Fire Extinguishers - | Replaces SS 232 Pt 1 to 6 |
Part 7: Characteristics, performance requirements and test methods | ||
SS EN 3-8 | Portable Fire Extinguishers - | |
Part 8: Additional requirements to SS EN 3-7 for the construction, resistance to pressure and mechanical tests for extinguishers with a maximum allowable pressure equal to or lower than 30 bar | ||
SS EN 3-9 | Portable Fire Extinguishers - | |
Part 9: Additional requirements to SS EN 3-7 for pressure resistance if CO extinguishers | ||
SS EN 3-10 | Portable Fire Extinguishers - | |
Part 10: Provisions for evaluating the conformity of a portable fire extinguisher to SS EN 3-7 | ||
SS EN 1992 | Design of Concrete Structures | Formerly CP 65 |
Pt 1 | Planning and Performance Assessment of Electrical Energy Storage Systems – General Specification | |
Pt 2 | Safety Considerations for Grid- Integrated EES Systems – General Specifications | |
TR 77 | Electrical Energy Storage (EES) Systems | |
Pt 1 | Planning and Performance Assessment of Electrical Energy Storage Systems – General Specification | |
Pt 2 | Safety Considerations for Grid-integrated EES Systems – General Specification | |
AMERICAN STANDARDS | ||
ANSI | American National Standard Institute | |
A14.3 | American National Standards for Ladders - Fixed - Safety Requirements | |
ASTM D635 | Standard Test Method for Rate of Burning and/ or Extent & Time of Burning of Plastics in a Horizontal Position | |
ASTM E108 | Standard Test Methods for Fire Tests of Roof Coverings | |
ASTM E119 | Standard Test Methods for Fire Tests of Building Construction & Materials | |
ASTM E 662 | Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials | |
ASTM E814 | Standard Test Method for Fire Tests of Penetration Firestop Systems | |
ASTM E2307 | Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate – Scale, Multi-story Test Apparatus | |
NFPA 16 | Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems | Formerly NFPA 16A |
NFPA 30 | Flammable & Combustible Liquids Code | |
NFPA 33 | Standard for Spray Application Using Flammable or Combustible Materials | |
NFPA 45 | Standard on Fire Protection for Laboratories Using Chemicals | |
NFPA 54 | National Fuel Gas Code | |
NFPA 55 | Compressed Gases and Cryogenic Fluids Code | |
NFPA 58 | Liquefied Petroleum Gas Code | |
NFPA 251 | Standard Methods of Tests of Fire Resistance of Building Construction & Materials | |
NFPA 253 | Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant heat Energy Source | |
NFPA 258 | Recommended Practice for Determining Smoke Generation of Solid Material | |
NFPA 262 | Standard Methods of Tests for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces | |
NFPA 285 | Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components | |
NFPA 400 | Hazardous Materials Code | |
NFPA 430 | Code for the Storage of Liquids & Solid Oxidizers | Replaced by NFPA 400 |
NFPA 432 | Code for the Storage of Organic Peroxide Formulations | |
NFPA 495 | Explosive Materials Code | |
NFPA 502 | Standard for Road Tunnels, Bridges and other Limited Access Highways | |
NFPA 750 | Standard on Water Mist Fire Protection Systems | |
NFPA 2001 | Standard on Clean Agent Fire Protection Systems | |
UL 132 | Standard for Safety Relief Valves for Anhydrous Ammonia and LP-Gas | |
UL 144 | Standard for LP-Gas Regulators | |
UL 217 | Standard for Smoke Alarms | |
UL 300 | Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment | |
UL 448 | Standard for Safety Centrifugal Stationary Pumps for Fire Protection Service | |
UL 555 | Fire Dampers | |
UL 924 | Standard for Emergency Lighting and Power Equipment | |
AUSTRALIAN STANDARDS | ||
AS 1530 | Methods for Fire Tests on Building Materials, Components & Structures | |
Pt 4 | Fire-resistance Test of Elements of Construction | |
AS 2208 | Safety Glazing Materials in Buildings | |
AS/NZS 2293 | Emergency Lighting and Exit Signs for Buildings | |
Pt 1 | System Design, Installation and Operation | |
AS 2714 | The Storage & Handling of Organic Peroxides | |
AS 2941 | Fixed Fire Protection Installations - Pumpset Systems | |
AS 3786 | Smoke Alarms Using Scattered Light, Transmitted Light or Ionization | |
AS 4391 | Smoke Management Systems - Hot Smoke Test | |
AS 4326 | The Storage & Handling of Oxidizng Agents | |
AS 4587 | Water Mist Fire Protection Systems - System Design, Installation and Commissioning | |
BRITISH STANDARDS | ||
BR 186 | Design Principles for Smoke Ventilation in Enclosed Shopping Centres | Published by Fire Research Station, Building Research Establishment, Borehamwood, Herts WD62BL |
BR 258 | Design Approaches for Smoke Control in Atrium Buildings | |
BR 368 | Design Methodologies for Smoke and Heat Exhaust Ventilation | Published by Construction Research Communications Ltd by permission of Building Re- search Establishment Ltd |
BS 476 | Fire Tests on Building Materials and Structures | |
Pt 3 | Classification and Method of Test for External Fire Exposure to Roofs | |
Pt 4
| Non-Combustibility Test for Materials | |
Pt 5 | Method of Test for Ignitability | |
Pt 6 | Method of Test for Fire Propagation for Products | |
Pt 7 | Method of Test to Determine the Classification of the Surface Spread of Flame of Products | |
Pt 11 | Method for Assessing the Heat Emission from Building Materials | |
Pt 20 | Method for Determination of the Fire Resistance of Elements of Construction (General Principles) | |
Pt 21 | Methods for Determination of the Fire Resistance of Load- Bearing Elements of Construction | |
Pt 22 | Method for Determination of the Fire Resistance of Non-Load- Bearing Elements of Construction | |
Pt 23 | Methods for Determination of the Contribution of Components to the Fire Resistance of a Structure | |
Pt 24 | Method for Determination of the Fire Resistance of Ventilation Ducts | |
BS 1230
Pt 1 | Specification for Plasterboard Excluding Materials Submitted to Secondary Operations | Replaced by BS EN 520 |
BS 2594 | Specification for Carbon Steel Welded Horizontal Cylindrical Storage Tanks | Withdrawn |
BS 3016 | Specifications for Pressure Regulators for LPG | Replaced by BS EN 16219 |
BS 4514 | Specification for Unplasticized PVC Soil and Ventilating Pipes of 82.4mm Minimum Mean Outside Diameter, and Fittings and Accessories of 82.4mm and of Other Sizes | |
BS 5041 | Fire Hydrant Systems Equipment | |
Pt 1 | Specification for Landing Valves for Wet Risers | |
Pt 3 | Specification for Inlet Breechings for Dry Riser Inlets | |
BS 5234 | Partitions (including matching linings) | |
Pt 2 | Specification for Performance Requirements for Strength and Robustness including Methods of Test | |
BS 5345 | Selection, Installation and Maintenance of Electrical Apparatus for Use in Potentially Explosive Atmosphere (Other than Mining Applications or Explosive Processing and Manufacturing) | Replaced by BS EN 60079-14 |
Pt 1 | General Recommendations | |
Pt 3 | Installation and Maintenance Requirements for Electrical Apparatus with Type of Protection ‘d’. Flameproof Enclosure | |
BS 5499 | Fire Safety Signs, Notices and Graphic Symbols | |
Pt 2 | Specification for Self-Luminous Fire Safety Signs | Withdrawn |
BS 5588 | Fire Precautions in the Design, Construction and Use of Buildings | |
Pt 5 | CoP for Firefighting Stairways and Lifts | Withdrawn |
BS 5852 | Methods of Test for Assessment of the Ignitability of Upholstered Seating by Smouldering and Flaming Ignition Source | |
BS 6206 | Specification for Impact Performance Requirements for Flat Safety Glass and Safety Plastics for Use in Buildings | Replaced by EN 12600 |
BS 6387 | Test Method for Resistance to Fire of Cables Required to Maintain Circuit Integrity under Fire Conditions | |
BS 6391 | Specification for Non-Percolating Layflat Delivery Hoses and Hose Assemblies for Fire Fighting Purposes | |
BS 7346 | Components for Smoke and Heat Control Systems | |
Pt 2 | Specification for Powered Smoke and Heat Exhaust Ventilators | Withdrawn |
Pt 3 | Specification for Smoke Curtains | Withdrawn |
BS 7346 | Components for Smoke and Heat Control Systems | |
Pt 7 | CoP on Functional Recommendations and Calculation Methods for Smoke and Heat Control Systems for Covered Car Parks | |
BS 7846 | Electric Cables. Thermosetting Insulated, Armoured, Fire-resistant Cables of Rated Voltage 600/1000V for Fixed Installations, Having Low Emission of Smoke and Corrosive Gases when Affected by Fire. Specification | |
BS 8202 | Coatings for Fire Protection of Building Elements | |
Pt 2 | CoP for the Use of Intumescent Coating Systems to Metallic Substrates for Providing Fire Resistance | |
EN 54 | Fire Detection and Alarm Systems | |
Pt 2 | Control and Indicating Equipment | |
Pt 4 | Power Supply Equipment | |
BS EN 520 | Gypsum Plasterboards. Definitions, Requirements and Test Methods | Replaces BS 1230 Pt 1 |
BS EN 12101-1 | Smoke & Heat Control Systems – Specification for Smoke Barriers | Replaces BS 7346 Pt 3 |
BS EN 12101-3 | Smoke & Heat Control Systems – Specification for Powered Smoke & Heat Control Ventilators (Fans) | Replaces BS 7346 Pt 2 |
BS EN 13501-1 | Fire Test to Building Materials - Classification | |
BS EN 50054 | Electrical Apparatus for the Detection and Measurement of Combustible Gases. - General Requirements and Test Methods | |
BS EN 50057 | Electrical Apparatus for the Detection and Measurement of Combustible Gases. - Performance Requirements for Group II Apparatus Indicating up to 100% Lower Explosive Limit | |
BS EN 50272-2 | Safety Requirements for Secondary Batteries and Battery Installations. Stationary Batteries | Withdrawn |
BS EN 50272-3 | Safety Requirements for Secondary Batteries and Battery Installations. - Traction Batteries | Withdrawn |
BS EN 60079-14 | Explosive Atmosphere. Electrical Installations Design, Selection and Erection | Replaces BS 5345 Pt 1 & 3 |
BS EN IEC 62485-2 | Safety Requirements for Secondary Batteries and Battery Installations - Stationary Batteries | Replaces BS EN 50272-2 |
BS EN IEC 62485-3 | Safety Requirements for Secondary Batteries and Battery Installations - Traction Batteries | Replaces BS EN 50272-3 |
EUROPEAN STANDARDS | ||
EN ISO 1182 | Reaction to Fire Tests for Products – Non-Combustibility Test | |
EN ISO 1716 | Reaction to Fire Tests for Building Products - Determination of the Gross Heat of Combustion (Calorific Value) | |
EN ISO 11925 – 2 | Reaction to Fire Tests – Ignitability of Products subjected to Direct Impingement of Flame - Part: Single Flame Source Test | |
EN ISO 5659 | Plastics – Smoke Generation | |
Pt 2 | Determination of Optical Density by a Single-chamber Test | |
EN 3 | Portable Fire Extinguishers | |
Pt 8 | Additional Requirements to EN 3 – 7 for the Construction, Resistance to Pressure and Mechanical Tests for extinguishers with a Maximum Allowable Pressure Equal to or Lower than 30 Bar | |
Pt 9 | Additional Requirements to EN 3 – 7 for Pressure Resistance of C02 Extinguishers | |
EN 54 - 2 | Fire Detection and Alarm Systems - Control and Indicating Equipment | |
EN 54 - 4 | Fire Detection and Alarm Systems - Power Supply Equipment | |
EN 81 - 58 | Safety Rules for the Construction and Installation of Lifts. Examination and Tests | |
Pt 58 | Landing Doors Fire Resistance Test | |
EN 179 | Building Hardware – Emergency Exit Devices Operated by a Lever Handle or Push Pad | |
EN 520 | Gypsum Plasterboards – Definitions, Requirements and Test Methods | |
EN 671 - 1 | Fixed Firefighting Systems. Hose Systems. Hose Reels with Semi-Rigid Hose | |
EN 1125 | Building Hardware – Panic Exit Devices Operated by a Horizontal Bar | |
EN 1154 | Building Hardware – Controlled Door Closing Devices | |
EN 1155 | Electrically Powered Hold Open Devices for Swing Doors | |
EN 1158 | Building Hardware – Door Coordinator Devices – Requirements and Test Standards | |
EN 1303 | Building Hardware – Cylinders for Locks | |
EN 1363 | Fire Resistance Tests. General Requirements | |
EN 1364 | Fire Resistance Test for Non-loadbearing Elements | |
Pt 1 | Walls | |
EN 1365 | Fire Resistance Test for Loadbearing Elements. Floors and Roofs | |
EN 1366 | Fire Resistance Test for Service Installations | |
Pt 1 | Ventilation Ducts | |
Pt 3 | Penetration Seals | |
Pt 4 | Linear Joint Seals | |
Pt 8 | Smoke Extraction Ducts | |
Pt 9 | Single Compartment Smoke Extraction Ducts | |
EN 1634-1 | Fire Resistance and Smoke Control Tests for Door and Shutter Assemblies, Openable Windows and Elements of Building Hardware | |
Pt 1 | Fire Resistance Test for Door and Shutter Assemblies and Openable Window | |
EN 1751 | Ventilation for Buildings – Air Terminal Devices – Aerodynamic Testing of Damper and Valves | |
EN 1906 | Building Hardware. Lever Handles and Knob Furniture. Requirements and Test Method | |
EN 1935 | Building Hardware. Single-axis Hinges. Requirements and Test Methods | |
EN 12051 | Building Hardware. Door and Window Bolts. Requirements and Test Methods | |
EN 12101 | Smoke and Heat Control Systems | |
Pt 1 | Specification for Smoke Barriers | |
EN 12209 | Building Hardware. Mechanically Operated Locks and Locking plates. Requirements and Test Methods | |
EN 12600 | Glass in Building. Pendulum Test. Impact Test Method and Classification for Flat Glass | |
EN 13501 | Fire Classification of Construction Products and Building Elements | |
Pt 5 | Classification Using Data from External Fire Exposure to Roofs Tests | |
EN 13823 | Reaction to Fire Tests for Building Products - Building Products excluding Floorings exposed to the Thermal Attack by a Single Burning Item | |
EN 14041 | Resilient, Textile and Laminate Floor Coverings. Essential Characteristics | |
EN 14064 - 1 | Thermal Insulation Products for Buildings. IN-situ Formed Loose-fill Mineral Wool (MW) Products. Specifications for the Loose-fill Products Before Insulation | |
EN 14064 | Smoke Alarm Devices | |
EN 14846 | Building Hardware. Locks and Latches. Electromechanically Operated Locks and Striking Plates. Requirements and Test Methods | |
EN 15684 | Building Hardware – Mechatronic Cylinders – Requirements and Test Methods | |
EN 16623 | Paints and Varnishes. Reactive Coatings for Fire Protection of Metallic Substrates. Definitions, Requirements, Characteristics and Marking | |
EN 45545 | Railway Applications – Fire protection on Railway Vehicles | |
Pt 2 | Determination of Optical Density by a Single-chamber Test | |
IEC STANDARDS | ||
IEC 60079 | Explosive Atmospheres | |
IEC 60331 | Tests for Electric Cables Under Fire Conditions – Circuit Integrity | |
Pt 25 | Procedures and Requirements – Optical Fibre Cables | |
IEC 60332 | Tests on Electric and Optical Fibre Cables Under Fire Conditions – All Parts | |
Pt 1 | Test for Vertical Flame Propagation for a Single Insulated Wire or Cable - Apparatus | |
Pt 3 | Test for Vertical Flame Spread of Vertically-Mounted Bunched Wires or Cable - Apparatus | |
IEC 60598-2-22 | Luminaries – Part 2-22: Particular Requirements - Luminaries for Emergency Lighting | |
IEC 60754 | Test on gases Evolved during Combustion of Materials From Cables | |
Pt 1 | Determination of the Halogen Acid Gas Content | |
IEC 61034 | Measurement of Smoke Density of Cables Burning Under Defined Conditions | |
IEC 61730 | Photovoltaic (PV) Module for Safety Qualification | |
Pt 2 | Requirements for Testing | |
ISO STANDARDS | ||
ISO 834 | Fire resistance Tests - Elements of Building Construction | |
Pt 1 | General Requirements | |
Pt 5 | Specific Requirements for Loadbearing Horizontal Separating Elements | |
Pt 7 | Specific Requirements for Columns | |
Pt 8 | Specific Requirements for Non-loadbearing Vertical Separating Elements | |
Pt 9 | Specific Requirements for Non-loadbearing Ceiling Elements | |
ISO 1896 | Thermal Insulating Asbestos Boards | |
ISO 3864 | Graphical Symbols – Safety Colours and Safety Signs | |
Pt 1 | Design Principles for Safety Signs and Safety Markings | |
Pt 2 | Design Principles for Product Safety Labels | |
Pt 3 | Design Principles for Graphical Symbols for Use in Safety Signs | |
ISO 5149 | Refrigerating Systems and Heat Pumps - Safety and Environment Requirements | |
ISO 5167 | Measurement of Fluid Flow by Means of Differential Pressure Devices | |
ISO 7010 | Graphical Symbols – Safety Colours and Safety Signs – Registered Safety Signs | |
ISO 7244 | Air Distribution and Air Diffusion – Aerodynamic Testing of Dampers and Valves | |
ISO 30061 | Emergency Lighting | |
FACTORY MUTUAL RESEARCH COPORATION | ||
FM 1311 | Centrifugal Fire Pumps Spilt-close Type (Axial or Radial) | |
FM 1319 | Centrifugal Fire Pumps (Horizontal, END Suction Type) | |
Note: - The Standards stated above are non-exhaustive, - SCDF shall not be held responsible for the accuracy of the standard titles shown in Table. |
TABLE 1.3A : ABBREVIATIONS
TABLE 1.3A : ABBREVIATIONS | |
Abbreviation | Definition |
ACMV | Air-Conditioning & Mechanical Ventilation |
AFA | Accessible Floor Area |
AHJ | Authority Having Jurisdiction |
ANSI | American National Standards Institute |
AS | Australian Standard |
ASHRAE | American Society of Heating, Refrigerating & Air-conditioning Engineers |
ASTM | American Society for Testing and Materials |
BRE | Building Research Establishment |
BS | British Standard |
BSL | Bio-Safety Level |
CD | Civil Defence |
CoC | Certificate of Conformity |
CoP | Code of Practice |
Cl. | Clause |
CERT | Company Emergency Response Team |
DIN | German Institute for Standardization |
DoC | Declaration of Compliance |
EC | Exit Capacity |
EN | European Standard |
FAMCP | Fully Automated Mechanised Car Park |
FCC | Fire Command Centre |
FM | Factory Mutual |
FMRC | Factory Mutual Research Corporation |
FSC | Fire Safety Certificate |
FSE | Fire Safety Engineer |
HFAD | Home Fire Alarm Device |
HR | Hour |
IEC | International Electrotechnical Commission |
ISO | International Organisation for Standardisation |
LPG | Liquid Petroleum Gas |
MAQ | Maximum Allowable Quantity |
MCST | Management Corporation Strata Title |
MRA | Mutual Recognition Arrangement |
MSDS | Material Safety Data Sheet |
MV | Mechanical Ventilation |
NFPA | National Fire Protection Association |
NoA | Notice of Approval |
NZS | New Zealand Standard |
ODA | Outdoor Display Area |
OL | Occupant Load |
ORA | Outdoor Refreshment Area |
PE | Professional Engineer |
PG | Purpose Group |
PLS | Product Listing Scheme |
Pt | Part |
PWDs | Persons With Disabilities |
QP | Qualified Person |
RI | Registered Inspector |
SAC | Singapore Accreditation Council |
SCDF | Singapore Civil Defence Force |
SS | Singapore Standard |
SS EN | Singapore Standard implementation of a European Standard |
TFP | Temporary Fire Permit |
UL | Underwriters Laboratories |
VIFDS | Video Image Fire Detection System |
WHO | World Health Organisation |
TABLE 1.4A : DESIGNATION OF PURPOSE GROUPS
TABLE 1.4A : DESIGNATION OF PURPOSE GROUPS | |||
Purpose Group (PG) | Descriptive Title | Purpose for which building or part of the building is used or intended to be used | |
I | Small residential | Residential dwelling house, such as: | |
• bungalow • detached house | • semi-detached house • terrace house | ||
II | Other residential | Accommodation for residential purposes other than any premises comprised in PG I, such as: | |
• apartment • cluster housing • condominium | • flat • maisonette • town house | ||
III | Institutional | Establishments used for treatment, care or maintenance of persons suffering from disabilities, such as: | |
• community hospital • convalescent home • home for intellectually disabled • home for the aged | • home for the spastic • hospice • hospital • psychiatric hospital • nursing home | ||
Establishments used for care or maintenance of young/ dependent persons, such as: | |||
• children's home • correction centre • daycare centre • detention centre • dialysis centre | • infant-care centre • rehabilitation centre • school for the spastic • senior activity centre • orphanage | ||
Establishments used for educational/ training purposes, such as: | |||
• college • commerical/ private • school • enrichment centre • kindergarten/nursery • military camp | • polytechnic • public school • tuition centre • university • vocational institution | ||
Establishments used for worker lodging purposes, such as: | |||
• workers' dormitory | |||
IV | Office | Premises/ areas/ spaces/ floors used for the purposes of administration and clerical work, or as premises occupied with an office for the purposes of the activities therein carried on, such as: | |
• banking • insurance • publisher | • stock broker • telephone/ telegraph operating | ||
V | Shop | Premises/ areas/ spaces/ floors used for the following purposes (and/or any other similar trades or businesses): | |
• beauty salon • book store • boutique • confectionary outlet • departmental store • drugstore • gift shop • hairdressing salon • jewellery shop • laundry • outpatient clinic • pawnshop | • pet shop/ clinic • polyclinic • provisional shop • shopping arcade • shopping centre • show flat • showrooms for sale of goods • supermarket • take-away F&B • outlet/ kiosk • ticketing agency • travel agency | ||
VI | Factory | Premises/ areas/ spaces/ floors with manufacturing, processing, servicing or testing activities, such as: | |
• aircraft hangar • chemicals • consumable products • data/ server centre • electrical switching/ transmitting • fireworks • food products • glassware • highly combustible substances • highly flammable products • incineration • metalwork | • oil refinery • pharmaceutical • power generation • recycling • rubber • ship building • telecommunication exchange • vehicle repair/ servicing • wafer • waste treatment/ pumping • woodwork | ||
VII | Place of public resort | Premises/ areas/ spaces/ floors used for accommodation purpose, such as: | |
• backpacker hotel • boarding house • hotel • staff quarters | • holiday resort • serviced apartment • student hostel | ||
Premises/ areas/ spaces/ floors used for educational purpose, such as: | |||
• auditorium • convention centre • exhibition centre | • museum • public art gallery • public library | ||
Premises used for social purpose such as: | |||
• community centre | • private club | ||
VII | Place of public resort | Premises/ areas/ spaces/ floors used for entertainment purpose, such as: | |
• casino • cinema • concert hall • discotheque | • internet gaming centre • karaoke lounge • night club • theatre | ||
Premises/ areas/ spaces/ floors used for religious purpose, such as: | |||
• church • mosque | • temple | ||
Premises/ areas/ spaces/ floors used for body treatment purpose, such as: | |||
• body massage • foot reflexology | • gymnasium • Spa | ||
Premises/ areas/ spaces/ floors used for recreational purpose, such as: | |||
• amusement centre • billiard/ snooker centre • bowling centre • roof garden/ terrace • sky garden/ terrace | • public sport complex • public swimming complex • stadium | ||
Premises/ areas/ spaces/ floors used for F&B purpose, such as: | |||
• cafeteria • canteen • coffee shop • eating house • fast food outlet | • food court • hawker centre • Pub/ bar • restaurant | ||
Premises/ areas/ spaces/ floors used for transportation purpose, such as: | |||
• airport terminal • bus terminal | • ferry terminal • train station | ||
VIII | Storage | Premises/ areas/ spaces/ floors used for the purposes of storing, depositing or parking of goods, materials and/ or vehicles, such as: | |
• coldroom • godown • store | • vehicle park • warehouse | ||
Note: Requirements for buildings not listed in this Table, including but not limited to buildings used for the manufacture and/ or storage of highly combustible substances and/ or flammable liquids, etc., shall be consulted with the SCDF |
TABLE 1.4B : OCCUPANT LOAD FACTORS
TABLE 1.4B : OCCUPANT LOAD FACTORS | ||||
FUNCTIONAL SPACES | FACTOR (m 2/person) | REMARKS | ||
Amusement park | 1 | excluding machine areas | ||
Apartment, residential | 15 | |||
Area of refuge | ||||
ambulatory care facility | 1.4 | |||
custodian care facility | 1.4 | |||
hospital | 2.8 | |||
hospital | 0.56 | for area of refuge without patient accommodation | ||
nursing care facility | 2.8 | |||
nursing care facility | 0.56 | for area of refuge without patient accommodation | ||
supervisory care facility | 0.56 | |||
Archive room | ||||
reading area | 5 | |||
stack area | 10 | |||
Atrium floor | 3 | |||
Audio visual area | 3 | |||
Auditorium/ theatre | ||||
With individual fixed seating | 1.5 | occupant load can be based on number of fixed seating | ||
With fixed bench seating | --- | occupant load based on 450mm of length of the benches per person | ||
Audio visual control room for theatres/ cinemas/ concert halls | 5 | |||
Backpacker hotel | 3 | Max. 20 persons per room (including living area, toilet, etc.) | ||
Ball room | 1.5 | |||
Banking hall | 3 | |||
Bar/ pub | 1 | |||
Bath room | --- | non-simultaneous | ||
Bazaar | 5 | |||
Billiards room | 5 | |||
Book/ general storage | 30 | |||
Bowling alley | 1 | excluding bowling lanes | ||
Business centre/ office | 10 | |||
Cafeteria | 1.5 | |||
Canteen | 1.5 | including staff canteen | ||
Car parking area | 30 | |||
Changing room | --- | non-simultaneous | ||
Children playground | 5 | including playground equipment | ||
Classroom | ||||
Computer classroom | 1.5 | |||
Nursery classroom for children under 7 years of age | 1.5 | or higher OL factor as required by the authority having jurisdiction | ||
Others | 1.5 | |||
Club room | 1.5 | |||
Concourse | 3 | |||
Conference room | 1.5 | |||
Consultant room | 5 | |||
Common room | 1.5 | |||
Computer room | 5 | |||
Corridor | --- | non-simultaneous | ||
Crematoria | 1.5 | |||
Dance studio | 5 | |||
Department store | 5 | |||
Deposit/strong room | 30 | |||
Design studio | 5 | |||
Detention room | 3 | |||
Dining area | ||||
Hawker centre | 1.5 | |||
Fast food outlet | 1 | |||
others | 1.5 | |||
Discotheque | 1 | including dine & dance area | ||
Dormitory | 4.2 | bedroom area only, excluding living area, toilet, etc. | ||
Examination room | 5 | |||
Exposition/ Trade fair area | 1.5 | |||
Fast food outlet | 1 | |||
Filing room/ store | 10 | |||
Foyer Bus/ Airport/ Ferry terminal or station | 1.5 | |||
Fitness club/ centre | 5 | |||
Function room | 1.5 | |||
Gallery | ||||
exhibits | 2.5 | |||
choir | 1.5 | |||
prayer | 1.5 | |||
seating | 1.5 | occupant load can be based on number of fixed seating | ||
trading | 1.5 | |||
viewing | 1.5 | |||
surgical viewing | 3 | |||
General storage | 30 | |||
Goods storage | 30 | |||
Grandstand/ seating area | 1.5 | |||
Guestroom/ accommodation unit | 15 | min. 2 persons per room or 15m2/person, whichever is higher | ||
Gymnasium | 3.5 | |||
Health club/ centre | 5 | |||
Hobby room | 1.5 | |||
Housekeeping | 10 | |||
Indoor games room | 1.5 | |||
Indoor sport hall | ||||
school with multi-purpose hall | 3 | |||
school without multi-purpose hall | 1 | |||
others | 3 | |||
Karaoke lounge | 1.5 | including dine & dance areas | ||
Kitchen/ service area | 10 | |||
Laboratory | ||||
healthcare occupancy | 20 | |||
schools/ colleges/ tertiary institutions | 5 | |||
others | 5 | |||
Laundry | ||||
with machine operation | 15 | |||
others | 10 | |||
Lecture room | 1.5 | |||
Library room | ||||
stack area | 10 | |||
reading area | 5 | |||
Lighting control room | ||||
theatres/ cinemas/ concert halls | 5 | |||
others | 5 | |||
Loading/ unloading area | 4 per bay | |||
Lobby | --- | non-simultaneous | ||
Locker room | --- | non-simultaneous | ||
Lounge | 2.5 | |||
Machine/ printing room | 10 | |||
Maisonettes, residential | 15 | |||
Mechanical plant room | 30 | |||
Meeting room | 1.5 | |||
Mortuary | 30 | |||
Multi-purpose hall/ room | ||||
school/ colleges | 1 | |||
others | 1.5 | |||
Multi-purpose sports hall | ||||
public sport complex | 3 | |||
public swimming complex | 3 | |||
stadium | 3 | |||
others | 3 | |||
Night club | 1.5 | including dine & dance area | ||
Nursing station | 10 | |||
Office | ||||
Admin/ general | 10 | |||
director/ manager room | 15 | |||
drafting room/ area | 5 | |||
Operation theatre | 7.5 | |||
Orchestral pit | 1.5 | |||
Out-patient waiting area | 1.5 | |||
Packing/ distribution area | 10 | |||
Pantry | --- | non-simultaneous | ||
Passenger arrival/ departure areas | ||||
Bus/ Airport/ Ferry terminal or station | 1.5 | |||
Patient accommodation | ||||
intensive care | 20 | |||
room | 10 | |||
ward | 10 | |||
Pedestrian linkways (aboveground or underground) | ||||
with commercial activities | 2 | |||
building to Rapid Transit Stations (e.g., Mass Rapid Transit (MRT)) without commercial activities | 3.5 | |||
building to building without commercial activities | 5 | |||
standalone type without commercial activities | --- | non-simultaneous | ||
Pharmacy | ||||
staff area | 10 | |||
public waiting area | 2 | |||
Prayer hall | 1.5 | |||
Pre-function room | --- | non-simultaneous | ||
Production area | 10 | automated or non-automated | ||
Projection room | ||||
theatres/ cinemas/ concert halls | 5 | |||
others | 5 | |||
Promotion area | 1.5 | |||
Pub | 1 | |||
Reading room | 5 | |||
Reception area | 3 | |||
Recreation room | 1.5 | |||
Refreshment area | 1.5 | |||
Restroom | --- | non-simultaneous | ||
Restaurant | 1.5 | |||
Roof | --- | access for maintenance only | ||
Roof garden/ roof terrace, private | --- | non-simultaneous part of individual residential unit | ||
Roof garden/ roof terrace, public | ||||
health/ exercise corner | 5 | with exercise equipment | ||
jogging track/ designated foot path<=3m in width | 3 | |||
planter box <300m high | 1.5 | |||
planter box =>300mm | --- | fully covered with trees/ shrubs | ||
planter box =>300mm & <= 500mm high | 1.5 | turf | ||
planter box >500mm high | --- | without step/ ramp access | ||
sunken/ elevated water feature <300mm in depth/height | 3 | permanent or fixed structure | ||
sunken/ elevated water feature =>300mm in depth/height | --- | permanent or fixed structure | ||
sunken planting area | --- | fully covered with trees/ shrubs | ||
sunken planting area | 1.5 | turf | ||
other areas | 1.5 | |||
Seminar room | 1.5 | |||
Server room | 30 | |||
Serviced apartment | 15 | per unit | ||
Service area | 10 | |||
Shop | 5 | |||
Showroom | 5 | |||
Sick room | --- | non-simultaneous | ||
Skating rink | ||||
rink area | 3 | |||
spectator area | 1.5 | |||
Snack bar | 1.5 | |||
Society room | 1.5 | |||
Spa | 5 | include areas for weight training, aerobics, massage, sauna/steam bath and whirlpools | ||
Squash court | 2 per court | |||
Staff office | 10 | |||
Storage area | 30 | |||
Staff canteen | 1.5 | |||
Staff lounge | 3 | |||
Staff quarters | 15 | min. 2 persons per room or 15m2/person, whichever is higher | ||
Stage, front/ back | ||||
schools/ colleges/ tertiary institutions | 3 | |||
theatres/ cinemas/ concert halls | --- | non-simultaneous | ||
Storage/ store room | 30 | |||
Swimming pool | ||||
condominium/ apartment | 5 | |||
hotel | --- | |||
private club | --- | |||
public sports complex | 2.5 | |||
public swimming complex | 2.5 | |||
serviced apartment | --- | |||
Swimming pool deck | ||||
condominium/apartment | 10 | |||
hotel | 10 | |||
private club | 10 | |||
public sports complex | 5 | |||
public swimming complex | 5 | |||
serviced apartment | 10 | |||
Student bedroom | 15 | min. 2 persons per room or 15m2/person, whichever is higher | ||
Supermarket | 5 | |||
Therapy centre | 10 | |||
Ticketing office | 10 | |||
Toilet | --- | non-simultaneous | ||
Trading floor | 2 | |||
Training area | ||||
public sports complex | 3 | |||
public swimming complex | 3 | |||
stadium | 3 | |||
Treatment room | 5 | |||
Visitors lounge | 3 | |||
Waiting area | 3 | |||
Workshop | ||||
institutional | 5 | |||
industrial | 10 | |||
Note: - All functional spaces shall be computed based on accessible floor area for the calculation of occupant load, unless specifically exempted under the “Remarks” column - The functional spaces stated above are non-exhaustive. Usage of other occupancy load factor is only allowed if permitted by SCDF |