Search Fire Code
Include in Search
Clear All

Please enter a keyword to search

TABLE 1.2A : CODES & STANDARDS

TABLE 1.2A : CODES & STANDARDS
NameDescriptionRemarks
SINGAPORE STANDARDS

SS CP 52

CoP for Automatic Fire Sprinkler System

 

SS 99

Specifications for Welded Low Carbon Steel Cylinders for Storage and Transportation of Low-Pressure Liquefiable Gases 
SS141Specification for Unplasticised PVC pipe for Cold Water Services and Industrial Uses 
SS 213Unplasticised PVC Pipes and Fittings for Soil, Waste and Vent Application 

SS 232 Pt 1 to 6

Portable Fire ExtinguishersReplaced by SS EN 3 - 7 to 10

SS 233

Specifications for Flexible Rubber Tubing, Rubber Hose and Rubber Hose Assemblies for Use in LPG Vapour Phase Installations 

SS 254

Electrical Apparatus for Explosive Gas AtmospheresReplaced by IEC 60079

SS 263

 

Pt 2

Luminaires -

Particular Requirements for Luminaires for Emergency Lighting

Replaced by IEC 60598-2-22

SS 281

Specifications for Pressure Regulators for LPG 

SS 286

Caution Labelling for Hazardous SubstancesReplaced by SS 586

SS 294

Specifications for Valves for Use with Domestic and Industrial LPG Cylinders 

SS 299

Fire Resistant Cables 

SS 332

Specification for Fire Door 

SS 333

Specification for Fire Dampers 

SS 489

Specification for Fire Shutters 

SS 508

Graphical Symbols - Safety Colours & Safety SignsFormerly SS 217 & SS 364
   Pt 1

Design Principles for Safety Signs & Safety Markings

 
   Pt 2

Design Principles for Product Safety Labels

 
SS 512CoP for the design, construction and operation of pipeline service corridors 

SS 532

CoP for the Storage of Flammable Liquids

Formerly CP 40

 

SS 535

CoP for Installation, Operation, Maintenance, Performance Constructional Requirements of Mains Failure Standby Generating SystemsFormerly CP 31

SS 546

CoP for Emergency Voice Communication Systems in BuildingsFormerly CP 25

SS 550

CoP for Installation, Operation and Maintenance of El Passenger and Goods LiftsFormerly CP 2

SS 551

CoP for Earthing

Formerly CP 16

 

SS 563

CoP for the Design, Installation & Maintenance of Em Lighting and Power Supply Systems in BuildingFormerly CP 19

   Pt 1

Emergency lighting

 

   Pt 2

Installation Requirements and Maintenance Procedures

 

SS 572

CoP for the Use of Timber in Buildings

Formerly CP 1

SS 575

CoP for Fire Hydrant, Rising Mains and Hose Reel System

Formerly CP 29

SS 578

CoP for the Use and Maintenance of Portable Fire Extinguishers

Formerly CP 55

SS 586

Specification for Hazard Communication for Hazardous Chemicals and Dangerous GoodsReplaces SS 286

SS 608

CoP for Gas InstallationFormerly CP 51
SS 634CoP for Fire Safety for Open Plant Processing Facilities in Oil, Chemical and Process Industries 
SS 638CoP for Electrical InstallationsFormerly CP 5
SS 641CoP for Fire Safety for Laboratories Using Chemicals 
SS 645CoP for the Installation and Servicing of Electrical Fire Alarm SystemsFormerly CP 10
SS EN 3-7

Portable Fire Extinguishers -

Replaces SS 232 Pt 1 to 6
 Part 7: Characteristics, performance requirements and test methods 
SS EN 3-8Portable Fire Extinguishers - 
 Part 8: Additional requirements to SS EN 3-7 for the construction, resistance to pressure and mechanical tests for extinguishers with a maximum allowable pressure equal to or lower than 30 bar 
SS EN 3-9Portable Fire Extinguishers - 
 Part 9: Additional requirements to SS EN 3-7 for pressure resistance if CO extinguishers 
SS EN 3-10Portable Fire Extinguishers - 
 Part 10: Provisions for evaluating the conformity of a portable fire extinguisher to SS EN 3-7 
SS EN 1992Design of Concrete StructuresFormerly CP 65
Pt 1Planning and Performance Assessment of Electrical Energy Storage Systems – General Specification 
Pt 2Safety Considerations for Grid- Integrated EES Systems – General Specifications 
TR 77Electrical Energy Storage (EES) Systems 
Pt 1Planning and Performance Assessment of Electrical Energy Storage Systems – General Specification 
Pt 2Safety Considerations for Grid-integrated EES Systems – General Specification 
AMERICAN STANDARDS
ANSIAmerican National Standard Institute 
     A14.3American National Standards for Ladders - Fixed - Safety Requirements 

ASTM D635

Standard Test Method for Rate of Burning and/ or Extent & Time of Burning of Plastics in a Horizontal Position 

ASTM E108

Standard Test Methods for Fire Tests of Roof Coverings 
ASTM E119Standard Test Methods for Fire Tests of Building Construction & Materials 
ASTM E 662 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials 
ASTM E814Standard Test Method for Fire Tests of Penetration Firestop Systems 
ASTM E2307Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate – Scale, Multi-story Test Apparatus 
NFPA 16Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems

Formerly NFPA 16A

NFPA 30

Flammable & Combustible Liquids Code

 
NFPA 33Standard for Spray Application Using Flammable or Combustible Materials 
NFPA 45Standard on Fire Protection for Laboratories Using Chemicals 
NFPA 54National Fuel Gas Code 
NFPA 55Compressed Gases and Cryogenic Fluids Code 
NFPA 58Liquefied Petroleum Gas Code 
NFPA 251Standard Methods of Tests of Fire Resistance of Building Construction & Materials 
NFPA 253Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant heat Energy Source 
NFPA 258Recommended Practice for Determining Smoke Generation of Solid Material 
NFPA 262Standard Methods of Tests for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces 
NFPA 285Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components 
NFPA 400Hazardous Materials Code 
NFPA 430Code for the Storage of Liquids & Solid Oxidizers

Replaced by NFPA 400

NFPA 432Code for the Storage of Organic Peroxide Formulations
NFPA 495Explosive Materials Code 
NFPA 502Standard for Road Tunnels, Bridges and other Limited Access Highways 
NFPA 750Standard on Water Mist Fire Protection Systems 
NFPA 2001Standard on Clean Agent Fire  Protection Systems 

UL 132

Standard for Safety Relief Valves for Anhydrous Ammonia and LP-Gas

 

UL 144

Standard for LP-Gas Regulators 
UL 217Standard for Smoke Alarms 
UL 300Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment 
UL 448Standard for Safety Centrifugal Stationary Pumps for Fire Protection Service 
UL 555Fire Dampers 
UL 924Standard for Emergency Lighting and Power Equipment 
AUSTRALIAN STANDARDS
AS 1530

Methods for Fire Tests on Building Materials, Components & Structures

 

     Pt 4

Fire-resistance Test of Elements of Construction

 
AS 2208

Safety Glazing Materials in Buildings

 
AS/NZS 2293Emergency Lighting and Exit Signs for Buildings 
Pt 1System Design, Installation and Operation 
AS 2714

The Storage & Handling of Organic Peroxides

 
AS 2941

Fixed Fire Protection Installations - Pumpset Systems

 
AS 3786Smoke Alarms Using Scattered Light, Transmitted Light or Ionization 
AS 4391

Smoke Management Systems - Hot Smoke Test

 
AS 4326

The Storage & Handling of Oxidizng Agents

 
AS 4587

Water Mist Fire Protection Systems - System Design, Installation and Commissioning

 
BRITISH STANDARDS
BR 186

Design Principles for Smoke Ventilation in Enclosed Shopping Centres

Published by Fire Research Station, Building Research Establishment, Borehamwood, Herts WD62BL
BR 258

Design Approaches for Smoke Control in Atrium Buildings

BR 368

Design Methodologies for Smoke and Heat Exhaust Ventilation

Published by Construction Research Communications Ltd by permission of Building Re- search Establishment Ltd
BS 476

Fire Tests on Building Materials and Structures

 
  Pt 3Classification and Method of Test for External Fire Exposure to Roofs  
  Pt 4

 

Non-Combustibility Test for Materials

 
  Pt 5

Method of Test for Ignitability

 
  Pt 6

Method of Test for Fire Propagation for Products

 
  Pt 7

Method of Test to Determine the Classification of the Surface Spread of Flame of Products

 
  Pt 11

Method for Assessing the Heat Emission from Building Materials

 
  Pt 20

Method for Determination of the Fire Resistance of Elements of Construction (General Principles)

 
  Pt 21

Methods for Determination of the Fire Resistance of Load- Bearing Elements of Construction

 
 Pt 22

Method for Determination of the Fire Resistance of Non-Load- Bearing Elements of Construction

 
  Pt 23

Methods for Determination of the Contribution of Components to the Fire Resistance of a Structure

 
  Pt 24

Method for Determination of the Fire Resistance of Ventilation Ducts

 

BS 1230

 

Pt 1

Specification for Plasterboard Excluding Materials Submitted to Secondary Operations

Replaced by BS EN 520
BS 2594

Specification for Carbon Steel Welded Horizontal Cylindrical Storage Tanks

Withdrawn
BS 3016

Specifications for Pressure Regulators for LPG

Replaced by BS EN 16219
BS 4514

Specification for Unplasticized PVC Soil and Ventilating Pipes of 82.4mm Minimum Mean Outside Diameter, and Fittings and Accessories of 82.4mm and of Other Sizes

 
BS 5041

Fire Hydrant Systems Equipment

 
  Pt 1

Specification for Landing Valves for Wet Risers

 
  Pt 3

Specification for Inlet Breechings for Dry Riser Inlets

 
BS 5234

Partitions (including matching linings)

 
  Pt 2

Specification for Performance Requirements for Strength and Robustness including Methods of Test

 
BS 5345

Selection, Installation and Maintenance of Electrical Apparatus for Use in Potentially Explosive Atmosphere (Other than Mining Applications or Explosive Processing and Manufacturing)

Replaced by BS EN 60079-14
   Pt 1

General Recommendations

   Pt 3

Installation and Maintenance Requirements for Electrical Apparatus with Type of Protection ‘d’. Flameproof Enclosure

BS 5499

Fire Safety Signs, Notices and Graphic Symbols

 
   Pt 2

Specification for Self-Luminous Fire Safety Signs

Withdrawn
BS 5588

Fire Precautions in the Design, Construction and Use of Buildings

 
   Pt 5

CoP for Firefighting Stairways and Lifts

Withdrawn
BS 5852

Methods of Test for Assessment of the Ignitability of Upholstered Seating by Smouldering and Flaming Ignition Source

 
BS 6206

Specification for Impact Performance Requirements for Flat Safety Glass and Safety Plastics for Use in Buildings

Replaced by EN 12600
BS 6387Test Method for Resistance to Fire of Cables Required to Maintain Circuit Integrity under Fire Conditions 
BS 6391

Specification for Non-Percolating Layflat Delivery Hoses and Hose Assemblies for Fire Fighting Purposes

 
BS 7346

Components for Smoke and Heat Control Systems

 
  Pt 2

Specification for Powered Smoke and Heat Exhaust Ventilators

Withdrawn
  Pt 3

Specification for Smoke Curtains

Withdrawn
BS 7346

Components for Smoke and Heat Control Systems

 
  Pt 7

CoP on Functional Recommendations and Calculation Methods for Smoke and Heat Control Systems for Covered Car Parks

 
BS 7846Electric Cables. Thermosetting Insulated, Armoured, Fire-resistant Cables of Rated Voltage 600/1000V for Fixed Installations, Having Low Emission of Smoke and Corrosive Gases when Affected by Fire. Specification 
BS 8202

Coatings for Fire Protection of Building Elements

 
  Pt 2

CoP for the Use of Intumescent Coating Systems to Metallic Substrates for Providing Fire Resistance

 
EN 54

Fire Detection and Alarm Systems

 
  Pt 2

Control and Indicating Equipment

 
  Pt 4

Power Supply Equipment

 
BS EN 520

Gypsum Plasterboards. Definitions, Requirements and Test Methods

Replaces BS 1230 Pt 1
BS EN 12101-1

Smoke & Heat Control Systems – Specification for Smoke Barriers

Replaces BS 7346 Pt 3

BS EN 12101-3

Smoke & Heat Control Systems – Specification for Powered Smoke & Heat Control Ventilators (Fans)

Replaces BS 7346 Pt 2

BS EN 13501-1

Fire Test to Building Materials - Classification

 
BS EN 50054

Electrical Apparatus for the Detection and Measurement of Combustible Gases. - General Requirements and Test Methods

 
BS EN 50057

Electrical Apparatus for the Detection and Measurement of Combustible Gases. - Performance Requirements for Group II Apparatus Indicating up to 100% Lower Explosive Limit

 
BS EN 50272-2

Safety Requirements for Secondary Batteries and Battery Installations. Stationary Batteries

Withdrawn

BS EN 50272-3

Safety Requirements for Secondary Batteries and Battery Installations. - Traction Batteries

Withdrawn

BS EN 60079-14

Explosive Atmosphere. Electrical Installations Design, Selection and Erection

Replaces BS 5345 Pt 1 & 3

BS EN IEC 62485-2

Safety Requirements for Secondary Batteries and Battery Installations - Stationary Batteries

Replaces BS EN 50272-2

BS EN IEC 62485-3

Safety Requirements for Secondary Batteries and Battery Installations - Traction Batteries

Replaces BS EN 50272-3

EUROPEAN STANDARDS
EN ISO 1182Reaction to Fire Tests for Products – Non-Combustibility Test
 
EN ISO 1716Reaction to Fire Tests for Building Products - Determination of the Gross Heat of Combustion (Calorific Value) 
EN ISO 11925 – 2Reaction to Fire Tests – Ignitability of Products subjected to Direct Impingement of Flame - Part: Single Flame Source Test 
EN ISO 5659Plastics – Smoke Generation 
Pt 2Determination of Optical Density by a Single-chamber Test 
EN 3Portable Fire Extinguishers 
Pt 8Additional Requirements to EN 3 – 7 for the Construction, Resistance to Pressure and Mechanical Tests for extinguishers with a Maximum Allowable Pressure Equal to or Lower than 30 Bar  
Pt 9Additional Requirements to EN 3 – 7 for Pressure Resistance of C02 Extinguishers  
EN 54 - 2Fire Detection and Alarm Systems - Control and Indicating Equipment 
EN 54 - 4Fire Detection and Alarm Systems - Power Supply Equipment 
EN 81 - 58

Safety Rules for the Construction and Installation of Lifts. Examination and Tests 

 
Pt 58Landing Doors Fire Resistance Test 
EN 179Building Hardware – Emergency Exit Devices Operated by a Lever Handle or Push Pad 
EN 520Gypsum Plasterboards – Definitions, Requirements and Test Methods 

EN 671 - 1

Fixed Firefighting Systems. Hose Systems. Hose Reels with Semi-Rigid Hose

 
EN 1125Building Hardware – Panic Exit Devices Operated by a Horizontal Bar 
EN 1154Building Hardware – Controlled Door Closing Devices 
EN 1155Electrically Powered Hold Open Devices for Swing Doors 
EN 1158Building Hardware – Door Coordinator Devices – Requirements and Test Standards 
EN 1303Building Hardware – Cylinders for Locks 
EN 1363Fire Resistance Tests. General Requirements 
EN 1364Fire Resistance Test for Non-loadbearing Elements 
Pt 1Walls 
EN 1365Fire Resistance Test for Loadbearing Elements. Floors and Roofs 
EN 1366Fire Resistance Test for Service Installations  
Pt 1Ventilation Ducts 
Pt 3Penetration Seals 
Pt 4Linear Joint Seals 
Pt 8Smoke Extraction Ducts 
Pt 9Single Compartment Smoke Extraction Ducts 
EN 1634-1Fire Resistance and Smoke Control Tests for Door and Shutter Assemblies, Openable Windows and Elements of Building Hardware  
Pt 1Fire Resistance Test for Door and Shutter Assemblies and Openable Window 
EN 1751Ventilation for Buildings – Air Terminal Devices – Aerodynamic Testing of Damper and Valves 
EN 1906Building Hardware. Lever Handles and Knob Furniture. Requirements and Test Method 
EN 1935Building Hardware. Single-axis Hinges. Requirements and Test Methods 
EN 12051Building Hardware. Door and Window Bolts. Requirements and Test Methods 
EN 12101Smoke and Heat Control Systems 
Pt 1Specification for Smoke Barriers  
EN 12209Building Hardware. Mechanically Operated Locks and Locking plates. Requirements and Test Methods 
EN 12600Glass in Building. Pendulum Test. Impact Test Method and Classification for Flat Glass 
EN 13501
Fire Classification of Construction Products and Building Elements 
Pt 5Classification Using Data from External Fire Exposure to Roofs Tests  
EN 13823

Reaction to Fire Tests for Building Products - Building Products excluding Floorings exposed to the Thermal Attack by a Single Burning Item

 
EN 14041Resilient, Textile and Laminate Floor Coverings. Essential Characteristics 
EN 14064 - 1Thermal Insulation Products for Buildings. IN-situ Formed Loose-fill Mineral Wool (MW) Products. Specifications for the Loose-fill Products Before Insulation  
EN 14064Smoke Alarm Devices 
EN 14846Building Hardware. Locks and Latches. Electromechanically Operated Locks and Striking Plates. Requirements and Test Methods 
EN 15684Building Hardware – Mechatronic Cylinders – Requirements and Test Methods 
EN 16623Paints and Varnishes. Reactive Coatings for Fire Protection of Metallic Substrates. Definitions, Requirements, Characteristics and Marking 
EN 45545Railway Applications – Fire protection on Railway Vehicles   
Pt 2Determination of Optical Density by a Single-chamber Test 
IEC STANDARDS
IEC 60079Explosive Atmospheres 
IEC 60331Tests for Electric Cables Under Fire Conditions – Circuit Integrity 
Pt 25Procedures and Requirements – Optical Fibre Cables 
IEC 60332Tests on Electric and Optical Fibre Cables Under Fire Conditions – All Parts 
Pt 1Test for Vertical Flame Propagation for a Single Insulated Wire or Cable - Apparatus 
Pt 3Test for Vertical Flame Spread of Vertically-Mounted Bunched Wires or Cable - Apparatus 
IEC 60598-2-22Luminaries – Part 2-22: Particular Requirements - Luminaries for Emergency Lighting 
 IEC 60754Test on gases Evolved during Combustion of Materials From Cables 
Pt 1Determination of the Halogen Acid Gas Content 
IEC 61034Measurement of Smoke Density of Cables Burning Under Defined Conditions 
 IEC 61730Photovoltaic (PV) Module for Safety Qualification 
Pt 2Requirements for Testing 
ISO STANDARDS
ISO 834

Fire resistance Tests - Elements of Building Construction

 
Pt 1General Requirements 
Pt 5Specific Requirements for Loadbearing Horizontal Separating Elements 
Pt 7Specific Requirements for Columns 
Pt 8Specific Requirements for Non-loadbearing Vertical Separating Elements 
Pt 9Specific Requirements for Non-loadbearing Ceiling Elements 
ISO 1896Thermal Insulating Asbestos Boards 
ISO 3864Graphical Symbols – Safety Colours and Safety Signs  
Pt 1Design Principles for Safety Signs and Safety Markings 
Pt 2Design Principles for Product Safety Labels 
Pt 3Design Principles for Graphical Symbols for Use in Safety Signs 
ISO 5149

Refrigerating Systems and Heat Pumps - Safety and Environment Requirements

 
ISO 5167Measurement of Fluid Flow by Means of Differential Pressure Devices 
ISO 7010Graphical Symbols – Safety Colours and Safety Signs – Registered Safety Signs 
ISO 7244Air Distribution and Air Diffusion – Aerodynamic Testing of Dampers and Valves 
ISO 30061Emergency Lighting  
FACTORY MUTUAL RESEARCH COPORATION
FM 1311Centrifugal Fire Pumps Spilt-close Type (Axial or Radial) 
FM 1319Centrifugal Fire Pumps (Horizontal, END Suction Type) 

Note:

- The Standards stated above are non-exhaustive,

- SCDF shall not be held responsible for the accuracy of the standard titles shown in Table.

 

TABLE 1.3A : ABBREVIATIONS

TABLE 1.3A : ABBREVIATIONS
AbbreviationDefinition
ACMVAir-Conditioning & Mechanical Ventilation
AFAAccessible Floor Area
AHJAuthority Having Jurisdiction
ANSIAmerican National Standards Institute
ASAustralian Standard
ASHRAEAmerican Society of Heating, Refrigerating & Air-conditioning Engineers
ASTMAmerican Society for Testing and Materials
BREBuilding Research Establishment
BSBritish Standard
BSLBio-Safety Level
CDCivil Defence
CoCCertificate of Conformity
CoPCode of Practice
Cl.Clause
CERTCompany Emergency Response Team
DINGerman Institute for Standardization
DoCDeclaration of Compliance
ECExit Capacity
ENEuropean Standard
FAMCPFully Automated Mechanised Car Park
FCCFire Command Centre
FMFactory Mutual
FMRCFactory Mutual Research Corporation
FSCFire Safety Certificate
FSEFire Safety Engineer
HFADHome Fire Alarm Device
HRHour
IECInternational Electrotechnical Commission
ISOInternational Organisation for Standardisation
LPGLiquid Petroleum Gas
MAQMaximum Allowable Quantity
MCSTManagement Corporation Strata Title
MRAMutual Recognition Arrangement
MSDSMaterial Safety Data Sheet
MVMechanical Ventilation
NFPANational Fire Protection Association
NoANotice of Approval
NZSNew Zealand Standard
ODAOutdoor Display Area
OLOccupant Load
ORAOutdoor Refreshment Area
PEProfessional Engineer
PGPurpose Group
PLSProduct Listing Scheme
PtPart
PWDsPersons With Disabilities
QPQualified Person
RIRegistered Inspector
SACSingapore Accreditation Council
SCDFSingapore Civil Defence Force
SSSingapore Standard
SS ENSingapore Standard implementation of a European Standard
TFPTemporary Fire Permit
ULUnderwriters Laboratories
VIFDSVideo Image Fire Detection System
WHOWorld Health Organisation

 

TABLE 1.4A : DESIGNATION OF PURPOSE GROUPS

TABLE 1.4A : DESIGNATION OF PURPOSE GROUPS
Purpose Group (PG)Descriptive TitlePurpose for which building or part of the building is used or intended to be used
ISmall residentialResidential dwelling house, such as:
• bungalow
• detached house
• semi-detached house
• terrace house
IIOther residentialAccommodation for residential purposes other than any premises comprised in PG I, such as:
• apartment
• cluster housing
• condominium
• flat
• maisonette
• town house
IIIInstitutionalEstablishments used for treatment, care or maintenance of persons suffering from disabilities, such as:
• community hospital
• convalescent home
• home for intellectually disabled
• home for the aged
• home for the spastic
• hospice
• hospital
• psychiatric hospital
• nursing home
Establishments used for care or maintenance of young/ dependent persons, such as:
• children's home
• correction centre
• daycare centre
• detention centre
• dialysis centre
• infant-care centre
• rehabilitation centre
• school for the spastic
• senior activity centre
• orphanage
Establishments used for educational/ training purposes, such as:
• college
• commerical/ private • school
• enrichment centre
• kindergarten/nursery
• military camp
• polytechnic
• public school
• tuition centre
• university
• vocational institution
Establishments used for worker lodging purposes, such as:
• workers' dormitory
IVOfficePremises/ areas/ spaces/ floors used for the purposes of administration and clerical work, or as premises occupied with an office for the purposes of the activities therein carried on, such as:
• banking
• insurance
• publisher
• stock broker
• telephone/ telegraph operating
VShopPremises/ areas/ spaces/ floors used for the following purposes (and/or any other similar trades or businesses):
• beauty salon
• book store
• boutique
• confectionary outlet
• departmental store
• drugstore
• gift shop
• hairdressing salon
• jewellery shop
• laundry
• outpatient clinic
• pawnshop
• pet shop/ clinic
• polyclinic
• provisional shop
• shopping arcade
• shopping centre
• show flat
• showrooms for sale of goods
• supermarket
• take-away F&B • outlet/ kiosk
• ticketing agency
• travel agency
VIFactoryPremises/ areas/ spaces/ floors with manufacturing, processing, servicing or testing activities, such as:
• aircraft hangar
• chemicals
• consumable products
• data/ server centre
• electrical switching/ transmitting
• fireworks
• food products
• glassware
• highly combustible substances
• highly flammable products
• incineration
• metalwork
• oil refinery
• pharmaceutical
• power generation
• recycling
• rubber
• ship building
• telecommunication exchange
• vehicle repair/ servicing
• wafer
• waste treatment/ pumping
• woodwork
VIIPlace of public resortPremises/ areas/ spaces/ floors used for accommodation purpose, such as:
• backpacker hotel
• boarding house
• hotel
• staff quarters
• holiday resort
• serviced apartment
• student hostel
Premises/ areas/ spaces/ floors used for educational purpose, such as:
• auditorium
• convention centre
• exhibition centre
• museum
• public art gallery
• public library
Premises used for social purpose such as:
• community centre• private club
VIIPlace of public resortPremises/ areas/ spaces/ floors used for entertainment purpose, such as:
• casino
• cinema
• concert hall
• discotheque
• internet gaming centre
• karaoke lounge
• night club
• theatre
Premises/ areas/ spaces/ floors used for religious purpose, such as:
• church
• mosque
• temple
Premises/ areas/ spaces/ floors used for body treatment purpose, such as:
• body massage
• foot reflexology
• gymnasium
• Spa
Premises/ areas/ spaces/ floors used for recreational purpose, such as:
• amusement centre
• billiard/ snooker centre
• bowling centre
• roof garden/ terrace
• sky garden/ terrace
• public sport complex
• public swimming complex
• stadium
Premises/ areas/ spaces/ floors used for F&B purpose, such as:
• cafeteria
• canteen
• coffee shop
• eating house
• fast food outlet
• food court
• hawker centre
• Pub/ bar
• restaurant
Premises/ areas/ spaces/ floors used for transportation purpose, such as:
• airport terminal
• bus terminal
• ferry terminal
• train station
VIIIStoragePremises/ areas/ spaces/ floors used for the purposes of storing, depositing or parking of goods, materials and/ or vehicles, such as:
• coldroom
• godown
• store
• vehicle park
• warehouse
Note:
Requirements for buildings not listed in this Table, including but not limited to buildings used for the manufacture and/ or storage of highly combustible substances and/ or flammable liquids, etc., shall be consulted with the SCDF

 

TABLE 1.4B : OCCUPANT LOAD FACTORS

TABLE 1.4B : OCCUPANT LOAD FACTORS
FUNCTIONAL SPACESFACTOR (m 2/person)REMARKS
Amusement park1excluding machine areas
Apartment, residential15 
Area of refuge
  ambulatory care facility1.4 
  custodian care facility1.4 
  hospital2.8 
  hospital0.56for area of refuge without patient accommodation
  nursing care facility2.8 
  nursing care facility0.56for area of refuge without patient accommodation
  supervisory care facility0.56 
Archive room
    reading area5 
    stack area10 
Atrium floor3 
Audio visual area3 
Auditorium/ theatre
   With individual fixed seating1.5occupant load can be based on number of fixed seating
   With fixed bench seating---occupant load based on 450mm of length of the benches per person
Audio visual control room for theatres/ cinemas/ concert halls5 
Backpacker hotel3Max. 20 persons per room (including living area, toilet, etc.)
Ball room1.5 
Banking hall3 
Bar/ pub1 
Bath room---non-simultaneous
Bazaar5 
Billiards room5 
Book/ general storage30 
Bowling alley1excluding bowling lanes
Business centre/ office10 
Cafeteria1.5 
Canteen1.5including staff canteen
Car parking area30 
Changing room---non-simultaneous
Children playground5including playground equipment
Classroom
Computer classroom1.5 
Nursery classroom for children under 7 years of age1.5or higher OL factor as required by the authority having jurisdiction
Others1.5 
Club room1.5 
Concourse3 
Conference room1.5 
Consultant room5 
Common room1.5 
Computer room5 
Corridor---non-simultaneous
Crematoria1.5 
Dance studio5 
Department store5 
Deposit/strong room30 
Design studio5 
Detention room3 
Dining area
    Hawker centre1.5 
    Fast food outlet1 
    others1.5 
Discotheque1including dine & dance area
Dormitory4.2bedroom area only, excluding living area, toilet, etc.
Examination room5 
Exposition/ Trade fair area1.5 
Fast food outlet1 
Filing room/ store10 

Foyer

    Bus/ Airport/ Ferry terminal or station

1.5 
Fitness club/ centre5 
Function room1.5 
Gallery
    exhibits2.5 
    choir1.5 
    prayer1.5 
    seating1.5occupant load can be based on number of fixed seating
    trading1.5 
    viewing1.5 
    surgical viewing3 
General storage30 
Goods storage30 
Grandstand/ seating area1.5 
Guestroom/ accommodation unit15min. 2 persons per room or 15m2/person, whichever is higher
Gymnasium3.5 
Health club/ centre5 
Hobby room1.5 
Housekeeping10 
Indoor games room1.5 
Indoor sport hall
  school with multi-purpose hall3 
  school without multi-purpose hall1 
  others3 
Karaoke lounge1.5including dine & dance areas
Kitchen/ service area10 
Laboratory
  healthcare occupancy20 
  schools/ colleges/ tertiary institutions5 
  others5 
Laundry
   with machine operation15 
   others10 
Lecture room1.5 
Library room
stack area10 
reading area5 
Lighting control room
   theatres/ cinemas/ concert halls5 
   others5 
Loading/ unloading area4 per bay 
Lobby---non-simultaneous
Locker room---non-simultaneous
Lounge2.5 
Machine/ printing room10 
Maisonettes, residential15 
Mechanical plant room30 
Meeting room1.5 
Mortuary30 
Multi-purpose hall/ room
    school/ colleges1 
    others1.5 
Multi-purpose sports hall
   public sport complex3 
   public swimming complex3 
  stadium3 
  others3 
Night club1.5including dine & dance area
Nursing station10 
Office
  Admin/ general10 
  director/ manager room15 
  drafting room/ area5 
Operation theatre7.5 
Orchestral pit1.5 
Out-patient waiting area1.5 
Packing/ distribution area10 
Pantry---non-simultaneous
Passenger arrival/ departure areas
    Bus/ Airport/ Ferry terminal or station1.5 
Patient accommodation
    intensive care20 
    room10
    ward10 
Pedestrian linkways (aboveground or underground)
   with commercial activities2 
   building to Rapid Transit Stations (e.g., Mass Rapid Transit (MRT)) without commercial activities3.5
   building to building without commercial activities5 
   standalone type without commercial activities---non-simultaneous
Pharmacy
  staff area10 
  public waiting area2 
Prayer hall1.5 
Pre-function room---non-simultaneous
Production area10automated or non-automated
Projection room
   theatres/ cinemas/ concert halls5 
   others5 
Promotion area1.5 
Pub1 
Reading room5 
Reception area3 
Recreation room1.5 
Refreshment area1.5 
Restroom---non-simultaneous
Restaurant1.5 
Roof---access for maintenance only
Roof garden/ roof terrace, private---non-simultaneous part of individual residential unit
Roof garden/ roof terrace, public
  health/ exercise corner5with exercise equipment
  jogging track/ designated foot path<=3m in width3 
  planter box <300m high1.5 
  planter box =>300mm---fully covered with trees/ shrubs
  planter box =>300mm & <= 500mm high1.5turf
  planter box >500mm high---without step/ ramp access
  sunken/ elevated water feature <300mm in depth/height3permanent or fixed structure
  sunken/ elevated water feature =>300mm in depth/height---permanent or fixed structure
  sunken planting area---fully covered with trees/ shrubs
  sunken planting area1.5turf
  other areas1.5 
Seminar room1.5 
Server room30 
Serviced apartment15per unit
Service area10 
Shop5 
Showroom5 
Sick room---non-simultaneous
Skating rink
       rink area3 
       spectator area1.5 
Snack bar1.5 
Society room1.5 
Spa5include areas for weight training, aerobics, massage, sauna/steam bath and whirlpools
Squash court2 per court 
Staff office10 
Storage area30 
Staff canteen1.5 
Staff lounge3 
Staff quarters15min. 2 persons per room or 15m2/person, whichever is higher
Stage, front/ back
  schools/ colleges/ tertiary institutions3 
  theatres/ cinemas/ concert halls---non-simultaneous
Storage/ store room30 
Swimming pool
  condominium/ apartment5 
  hotel--- 
  private club--- 
  public sports complex2.5 
  public swimming complex2.5 
  serviced apartment--- 
Swimming pool deck
condominium/apartment10 
  hotel10 
  private club10 
  public sports complex5 
  public swimming complex5 
  serviced apartment10 
Student bedroom15min. 2 persons per room or 15m2/person, whichever is higher
Supermarket5 
Therapy centre10 
Ticketing office10 
Toilet---non-simultaneous
Trading floor2 
Training area
   public sports complex3 
  public swimming complex3 
  stadium3 
Treatment room5 
Visitors lounge3 
Waiting area3 
Workshop
    institutional5 
    industrial10 

Note:

-  All functional spaces shall be computed based on accessible floor area for the calculation of occupant load, unless specifically exempted under the “Remarks” column

-  The functional spaces stated above are non-exhaustive. Usage of other occupancy load factor is only allowed if permitted by SCDF

 


Updated 3 Sep 2025