9.3.2 Healthcare occupancy
a. General
Amendment History
9.3.2a. |
|
01 Mar 2019 |
New |
|
--- |
-
|
Sprinkler shall be provided for healthcare occupancy with patient accommodation if:
(1) it comprises more than one storey, or
(2) it is located on an upper storey other than first storey, or
(3) its largest non-compartmented AFA exceeds 750m².
b. Hospital
They shall comply with the following additional requirements:
(1) Basement
Patient accommodation area containing beds shall not be located in basement storeys.
(2) Width of exit
The minimum clear width of an exit door opening shall be not less than 1.2m.
(3) Number of exits per ward
For patient accommodation wards where the occupant load exceeds 50 persons, each ward shall be provided with at least two exits, which shall be remotely located from each other.
(4) Provision of area of refuge
Every upper storey used for the accommodation of patients shall be provided with at least one area of refuge. The size of the area of refuge shall be computed based on Table 1.4B.
For hospital and nursing home, the area of refuge shall be sized adequately to accommodate the number of beds of minimum dimension 2.55m (length) by 1.1m (width) and computed based on occupant load factor of 2.8m2/person for the ward served
by the area of refuge.
(a) For area of refuge not adjacent to the patient ward, the routes leading to the area of refuge shall be through:
(i) an external corridor complying with Cl 2.3.10, or
Effective Date: 10 May 2019
Amendment History
9.3.2b.(4) |
10 May 2019 |
10 May 2019 |
Clarification |
Every upper storey used for the accommodation of patients shall be provided
with at least one area of refuge. The size of the area of refuge shall be computed
based on Table 1.4B. For hospital and nursing home, the area of refuge shall be
sized adequately to accommodate the number of beds computed based on
occupant load factor of 2.8m2/person for the ward served by the area of refuge.
The area of refuge shall be able to accommodate a bed size of minimum
dimension 2.55m (length) by 1.1m (width). |
10 May 2019 |
Download
|
(ii) a protected lobby separated from the adjoining areas of the building by a wall and door of at least 1-hr fire resistance rating. The protected lobby shall have a minimum size of 4m (length) by 2m (width) and ventilated in accordance with
Cl 2.2.13b.(7)(a) or (b)
Effective Date: 01 Mar 2019
Amendment History
9.3.2b.(4)(a)(ii) |
|
01 Mar 2019 |
New |
|
--- |
-
|
(b) For area of refuge immediately adjacent to a patient ward, the routes leading to the area of refuge need not be through an external corridor provided both the area of refuge and the adjacent patient ward are:
(i) fire compartmented from each other by a wall and door of at least 1-hr fire resistance rating;
(ii) provided with engineered smoke control and the design smoke layer height shall be at least 2.5m above the finished floor; and
(iii) provided with minimum of 2 remotely located exit access between them.
Effective Date: 01 Mar 2019
Amendment History
9.3.2b.(4)(b) |
|
01 Mar 2019 |
New |
|
--- |
-
|
(5) Size and compartmentation of patient accommodation area
E
Explanations & Illustrations
Clause 9.3.2b.(5) : Healthcare occupancy
Figure 9.3.2b.(5)
The above figure shows 4 wards that are fire compartmented from the internal corridor by walls and doors having 1-hr and ½-hr fire resistance rating respectively.
(a) Each patient accommodation ward shall not exceed a floor area of 750m² and an occupant load of 75 persons, calculated on the basis of Accessible Floor Area (AFA) of 10m² per person.
(b) For single storey premises not protected by sprinkler, each patient accommodation ward shall be constructed as a compartment having at least 1-hr fire resistance rating and at least ½-hr fire resistance rating door for protection of door openings. It shall be provided with an automatic fire alarm system.
Effective Date: 01 Mar 2019
Amendment History
9.3.2b(5)(b) |
|
01 Mar 2019 |
Revised, formerly Cl.2.5.1(a)(iv)(2) |
|
--- |
-
|
(c) For sprinkler-protected premises, patient accommodation ward area shall not exceed a fire compartment size 2100m² and shall be separated by full-height smoke barrier (up to soffit of the slab) for patient rooms of aggregated area not exceeding 750m² within the ward.
Effective Date: 01 Mar 2019
Amendment History
9.3.2b(5)(c) |
|
01 Mar 2019 |
New |
|
--- |
-
|
(6) Provision of fire escape bed lifts
(a) At least two fire escape bed lifts shall be provided for premises with more than one storey. They shall be located remotely from each other and sited adjacent to a protected exit staircase. Each area of refuge shall also be served
by at least one fire escape bed lift. Fire lift can double-up as a fire escape bed lift provided there is more than one fire lift and at least one shall remain as a dedicated fire lift. Where the fire lift doubles up as fire escape bed lift, its dimension
shall be as specified in Cl.9.3.2b.(6)(c).
Effective Date: 01 Mar 2019
Amendment History
9.3.2b.(6)(a) |
|
01 Mar 2019 |
Revised, formerly Cl.2.5.1(a)(v)(1) |
|
--- |
-
|
(b) The fire escape bed lift shall be contained within a protected shaft, constructed to comply with the relevant requirements under Cl.3.8.
(c) The entry into the fire escape bed lift and the protected exit staircase shall be through a common protected lobby. The fire escape bed lift shall have a minimum clear platform size of 2.8m (depth) by 1.8m (width). The protected lobby shall have a minimum size of 5m (length) by 4m (width). In the situation where the protected lobby is also serving as a smoke-free lobby or fire lift lobby, the floor area of the lobby shall be of sufficient size to accommodate both the evacuation of the required number of beds, as well as the passage of other occupants into the protected staircase.
(d) A signage shall be displayed outside the bed lift stating “FIRE ESCAPE BED LIFT”.
E
Explanations & Illustrations
Clause 9.3.2b.(6)(c) : Healthcare occupancy
Figure 9.3.2b.(6)(c)
Escape bed lifts are used for the evacuation of patients who are bed-ridden. The escape bed lift shall be provided adjacent to a protected exit staircase. The protected shaft to the bed lift shall comply with Cl.3.8. The protected lobby serving the bed lift shall have a floor area of not less than 9m² and a depth of min 2.5m perpendicular to the lift landing door. A signage shall be posted outside the bed lift, stating “Fire Escape Bed Lift”.
(e) The escape route for the fire escape bed lift at the 1st storey level shall be protected from other occupancy areas by 1-hr fire resistance separation and shall discharge directly into an external space.
E
Explanations & Illustrations
Clause 9.3.2b.(6)(e) : Healthcare occupancy
Figure 9.3.2b.(6)(e)
The discharge route for the exit bed lift is to be protected from other occupancy by 1-hr fire-rated wall and ½-hr fire-rated door.
(f) An fire escape bed lift that opens directly into an external corridor and which is sited adjacent to a protected exit staircase does not require a protected lobby, provided there is no unprotected opening within 3m horizontally from the fire escape bed lift door opening. The fire escape bed lift provided in this situation may be treated as a common bed lift that can serve multiple compartments located on the same floor.
E
Explanations & Illustrations
Clause 9.3.2b.(6)(f) : Healthcare occupancy
Figure 9.3.2b.(6)(f)
The provision of protected lobby to the bed lift is not required, provided there is no unprotected opening within 3m horizontally from the bed-lift door opening.
(g) An fire escape bed lift shall be provided with the following features:
(i) a secondary power supply from an emergency generating plant;
R
Rationale - Clause 9.3.2b.(6)(g)(i)
The purpose of providing a secondary power supply from an emergency plant is to ensure that the escape bed lift will stay operational during a fire emergency or a power failure in the building.
(ii) a switch labelled “Fire Escape Bed Lift”, situated next to the lift landing door at the final exit storey, which enables an authorised person nominated by the building management to take control of the lift car during an emergency. The operating of the switch shall be similar to fire lift operational features stipulated in SS 550. Such a switch is not needed in two-storey buildings;
(iii) a communications system (except in two-storey buildings) shall be installed to allow communication between occupants at each lift landing and the operator in the lift car; and
(iv) the installation of fire escape bed lifts shall be in accordance with SS 550.
(7) Internal access to wards
Effective Date: 1 Mar 2024
E
Explanations & Illustrations
Clause 9.3.2b.(7) : Healthcare occupancy
Figure 9.3.2b.(7)
As the internal access corridor is an escape route for all the occupants in Wards 1 to 4, it shall be made protected from the ward areas.
A patient accommodation ward with access through an internal corridor shall comply with the following requirements:
(a) each ward shall be separated from the internal corridor by a wall having at least 1-hr fire resistance rating;
(b) doors opening into an internal corridor shall have at least ½-hr fire resistance rating and be fitted with an automatic self-closing device to comply with the requirements of Cl.3.9.2; or be held open by an electromagnetic or electromechanical device;
(c) requirements on fire compartmentation under Cl.9.3.2b.(7)(a) and Cl.9.3.2b.(7)(b) can be relaxed up to a size of 2100m² as per Cl.9.3.2b.(5)(c), if the premises is sprinkler-protected;
(d) an internal corridor shall be naturally cross ventilated in accordance with Cl.2.2.13b.(7)(c);
(e) an internal corridor can be provided with mechanical ventilation and pressurisation in lieu of natural ventilation; and
(f) other non-patient accommodation areas or spaces which open into or form part of the internal corridor, and which can jeorpadise the means of escape provision, shall be compartmentalised by 1-hr fire-rated enclosures and ½-hr fire-rated doors
unless otherwise allowed under Cl.9.3.2b.(4)(b) and Cl.9.3.2b.(6)(c).
Amendment History
9.3.2b.(7) |
1 Mar 2024 |
1 Mar 2024 |
Relaxation |
9.3.2b.(7) Internal access to wards
A patient………………………………
(a) ……….
(b) ……….
(c) ……….
(d) an internal corridor shall be naturally ventilated with fixed openings in an external wall, such ventilation openings being not less than 15% of the floor area of the internal corridor;
(e) the ventilation opening in the external walls shall not be less than 3.5m², with at least 1.75m2 on each side shall be unobstructed by parapet walls or balustrade levels upwards and be positioned on opposite sides of the internal corridor such that they provide effective cross ventilation throughout the entire space of the corridor;
(f) the ventilation openings in the external walls shall not be more than 12m from any part of the internal corridor;
(g) an internal corridor can be provided with mechanical ventilation and pressurisation in lieu of natural ventilation; and
(h) other non-patient accommodation areas or spaces which open into or form part of the internal corridor, and which can jeopardise the means of escape provision, shall be compartmentalised by 1-hr fire-rated enclosures and ½-hr fire-rated doors unless otherwise allowed under Cl.9.3.2b.(4)(b) and Cl.9.3.2b.(6)(c). |
25 Aug 2023 |
Download
|
(8) External access to wards
R
Rationale - Clause 9.3.2b.(8)
External corridor and lobby space facing external space will minimise the possibility of smoke-logged situation to facilitate safe evacuation of occupants in a fire emergency. These dimensions have been validated through a fire engineering study.
E
Explanations & Illustrations
Clause 9.3.2b.(8) : Healthcare occupancy
Figure 9.3.2b.(8)
External access to a patient accommodation ward shall be through external corridor complying with Cl.2.3.10.
(9) Smoke-free approach to exit staircase
E
Explanations & Illustrations
Clause 9.3.2b.(9) : Healthcare occupancy
Figure 9.3.2b.(9)
The clear space within a smoke-stop lobby shall not be less than 6m² to accommodate the people in wheelchairs, etc. In the above figure the smoke-stop lobby also performs as a fire escape bed-lift lobby. The floor area shall not be less than 9m² having a depth of minimum 2.5m perpendicular to the lift landing door.
(a) Entry into an exit staircase from any part of a building of more than four storeys above ground level shall comply with the requirements of smoke-free approach to an exit staircase, as stipulated in Cl.2.2.13.
(b) Where a smoke-free lobby is provided to an exit staircase to serve a patient accommodation floor, or any area where patients may need to be evacuated on mattresses or stretchers, the lobby shall have a minimum clear space (unobstructed by door swing)
of 6m².
(10) Staircase landing width/depth
E
Explanations & Illustrations
Clause 9.3.2b.(10) : Healthcare occupancy
Figure 9.3.2b.(10) - 1
Exit Capacity Calculation
Exit Door width = 1.45m
Unit of width = 2.5
Person per unit width = 30 persons
No of person provided = 30 X 2.5= 75 persons
Stair Landing Depth = 1.6m and clear width of staircase = 1.5m)
Unit of width = 3 (Using clear width of staircase as it is less than 1.6m)
Person per unit width = 15 persons
No. of person provided = 15 persons x 3 = 45 persons
No. of persons provided with means of escape for this staircase = 45 persons.
Figure 9.3.2b.(10) - 2
In Figure 9.3.2b.(10) - 2, each block is provided with at least 2 exit staircases, except for Blk 2, which is provided with only one exit staircase. This is because blocks 1 and 3 serve as areas of refuge for Blk 2. The holding area in Blk 1 and 3 shall be based on the area of 2.8m²/person. See Cl.9.2 and Cl.2.2.6e. for further explanation. Administration block is self-sufficient in the provision of exit staircases
Owing to the design using area of refuge concept, the 2m wide corridors are required to be designed and maintained as open-sided at all times. This will prevent the corridors from being filled with smoke during a fire emergency. The max. 2-way travel distances shall not exceed 30m or 45m if sprinkler-protected. The direct distances for Blk 1 and 3, from point H to I and point E to F respectively shall not exceed ⅔ of 30m or ⅔ of 45m, if sprinkler-protected, for open plan layout. The direct distance for Blk 2 from point A to D, entry point to Blk 3 as area of refuge, shall not exceed ⅔ of 30m or ⅔ of 45m if sprinkler-protected, for open plan layout. Travel distances shall comply with Table 2.2A when internal partitioning work is introduced to create patients’ rooms etc..
Where the occupant load of any room exceeds 50 persons, the doors to the room shall be made to swing outwards. Care should be taken to ensure that the corridor width is not affected.
(a) Exit staircases that serve a patient accommodation floor to be used by patients in an emergency fire situation shall be designed to allow the evacuation of patients on mattresses or stretchers.
(b) The width of stairs, and staircase landing width and depth shall comply with Table 9.3A
.
c. Nursing home, convalescent home, home for the aged and hospice
They shall comply with the full requirements stated under Cl.9.3.2a. and
b. for
hospital.
E
Explanations & Illustrations
Clause 9.3.2c. : Healthcare occupancy
Figure 9.3.2c. - 1
Nursing home shall also include hospices. Each floor of the patient sleeping area shall be provided with at least 2 exit staircases. Most of the occupants of nursing homes are considered as non-ambulatory or bedridden and incapable of self-preservation. As such, the homes shall be manned on a 24-hr basis by trained staff who knows how to evacuate the patients during a fire emergency.
In the above Figure 9.3.2c. - 1, which shows an open plan layout, the direct distance requirements i.e. ⅔ of travel distance shall be used to ensure that actual travel distances would comply with Table 2.2A when internal partitioning work is introduced to create patients’ rooms etc.. The direct distance from points A to B and A to C shall not exceed ⅔ of 30m or ⅔ of 45m if sprinkler-protected.
Figure 9.3.2c. - 2 : Path of travel and dead-end corridors in a nursing home
d. Custodian care facility
It shall comply with the following additional requirements:
(1) where such facilities are located within a building of mixed use, they shall be compartmentalised from other spaces and occupancies by walls and doors having at least 1-hr fire resistance rating. The requirement on the provision of fire compartmentation will not apply if the building is sprinkler-protected. In addition, the following requirements shall be complied with:
Effective Date: 1 Sep 2021
E
Explanations & Illustrations
Clause 9.3.2d. : Healthcare occupancy
Figure 9.3.2d.
In the above figure, a child care centre or nursery is located in one part of the office building. The child care centre shall be provided with direct access to at least 2 exit staircases. Routes leading to exit staircases outside the child care centre shall be made protected.
Occupants of custodian-care facilities are generally capable of movement with limited assistance. They do not require to be evacuated in beds or stretchers, or bedsheets.
Institutions for mentally retarded patients would have locked exit doors, windows with security bars to confine and protect them. QPs shall consult the SCDF regarding the fire safety features in the security control system before submission of building plan. The maximum 2-way travel distances shall not exceed 30m or 45m, if sprinkler-protected. The direct distance from point A to B shall not exceed of ⅔ of 30m or ⅔ of 45m if sprinkler-protected for open floor plan layout.
Amendment History
9.3.2d. |
1 Sep 2021 |
1 Sep 2021 |
Reinstatement |
Custodian care facility It shall comply with the following additional requirements: (1) where such facilities are located within a building of mixed use, they shall be compartmentalised from other spaces and occupancies by walls and doors having at least 1-hr fire resistance rating; Exception: The requirement on the provision of fire compartmentation will not apply if the building is sprinkler-protected. (2) where such facilities are located on the 1st storey, they shall be provided with direct access to the exterior of the building; (3) where located on upper storeys, they shall be sited adjacent to an exit staircase with direct access through a smoke-free lobby to the staircase (minimum one exit staircase); (4) where there is no fire lift lobby or smoke-free lobby, there shall be at least one direct access to the exit staircase; (5) institutions for the mentally disabled shall be designed with each storey having an area of refuge in accordance with Cl.1.4.9 and Table 1.4B; and (6) fire safety requirements under Cl.9.3.2b. - Hospital, shall be fully complied with, except Cl.9.3.2b.(6) on provision of escape bed lift and Cl.9.3.2b(10) on staircase landing width/depth. |
1 Sep 2021 |
Download
|
(a) where such facilities are located on the 1st storey, they shall be provided with direct access to the exterior of the building;
Effective Date: Immediate
Amendment History
9.3.2d(2) |
10 May 2019 |
10 May 2019 |
Change in requirements |
(2) where such facilities are located on the 1st storey, they shall be provided with direct access to the exterior of the building;
|
10 May 2019 |
Download
|
9.3.2d(3) |
10 May 2019 |
Immediate |
Change in requirements |
where located on upper storeys, they shall be sited adjacent to an exit staircase with have direct access through a smoke-stop lobby to the exit staircase (minimum one exit staircase); |
10 May 2019 |
Download
|
(b) where located on upper storeys, they shall be sited adjacent to an exit staircase with direct access through a smoke-free lobby to the staircase (minimum one exit staircase); and
(c) where there is no fire lift lobby or smoke-free lobby, there shall be at least one direct access to the exit staircase.
(2) Institutions for the mentally disabled shall be designed with each storey having an area of refuge in accordance with Cl.1.4.9 and Table 1.4B. Fire safety requirements under Cl.9.3.2b. - Hospital, shall be fully complied with, except Cl.9.3.2b.(6) on provision of escape bed lift and Cl.9.3.2b.(10) on staircase landing width/depth.
e. Supervisory care facility
It shall comply with Cl.9.3.2a. and
b., except
Cl.9.3.2b.(6) on provision of fire escape bed lift and Cl.9.3.2b.(10) on staircase landing width/depth.
E
Explanations & Illustrations
Clause 9.3.2e. : Healthcare occupancy
( No illustration )
Supervisory care facility used for housing for 4 or more mental health patients would require security measures such as locked exit doors, windows with security bars etc.. It must be recognised that such measures, which contravenes the Code would be necessary to restrain the patients and for their own safety.
The facility would be manned by trained staff on a 24 hours basis. QPs shall consult the SCDF on the provision of locking devices to exit doors and how such doors would be released in times of emergency to allow orderly evacuation of patients before making building plan submission.
f. Ambulatory healthcare centre
It shall comply with the following additional requirements:
(1) if located within a building of mixed use, shall be compartmentalised from other tenants and occupancies by walls and doors having at least 1-hr fire resistance rating;
(2) shall be provided with its own means of escape to at least one exit staircase; and
(3) shall fully comply with Cl.9.3.2a. and b.,
except Cl.9.3.2b.(4) on provision of area of refuge for horizontal evacuation,
Cl.9.3.2b.(6) on provision of fire escape bed-lift and
Cl.9.3.2b.(10)on staircase landing/depth.
E
Explanations & Illustrations
Clause 9.3.2f. : Healthcare occupancy
Figure 9.3.2f.
In an ambulatory healthcare centre, some of the patients are not capable of perceiving threats and taking appropriate action for self-preservation under emergency conditions without assistance from others, such as hemaedialysis units or freestanding emergency medical units.
Staff shall be trained to carry out evacuation procedures during a fire emergency. The building or part of the building used as an ambulatory healthcare centre shall be provided with at least 2 exit staircases.
g. Other outpatient clinics
Outpatient clinics shall be categorised as PG V occupancy and shall comply with all relevant requirements for such premises/ usage.
Effective Date: 15 Sep 2020
Amendment History
9.3.2g ( dated 15 Sep 2020) |
15 Sep 2020 |
15 Sep 2020 |
Clarification |
Other outpatient clinics For outpatient clinics that do not fall under the above categories, the fire safety requirements under Cl.9.3.2b. are not applicable. Instead, these clinics shall comply with the provision of fire-rated wall to separate the clinics from other usage as stipulated in Cl.3.2.5b., except for the frontage of the clinic. |
15 Sep 2020 |
Download
|
9.3.2g. |
|
01 Mar 2019 |
Revised, formerly Cl.2.5.1(f) |
|
--- |
-
|
9.3.3 Workers’ dormitory
Effective Date: 1 Feb 2021
Workers’ dormitories shall comply with the following additional requirements:
a. Size
Each dormitory bedroom shall not exceed 120m2 and an occupant load of 20 persons.
Effective Date: 1 Feb 2021
Amendment History
9.3.3 |
30 July 2020 |
1 Feb 2021 |
Revised |
Workers’ dormitory Workers’ dormitories shall comply with the following additional requirements: a. Size Each dormitory bedroom shall not exceed 120m2 and an occupant load of 40 persons. b. Occupant load The occupant load shall be based on accessible floor area on the basis of 3m² per person. c. ………… |
30 July 2020 |
Download
|
b. Occupant load
The occupant load shall be based on 4.2m² per person in accordance with Table 1.4B.
Effective Date: 1 Sep 2022
Amendment History
9.3.3b. |
|
01 Mar 2019 |
Revised, formerly Cl.2.9.2(b) |
|
--- |
-
|
9.3.3b.(dated 1 Sep 2022) |
1 Sep 2022 |
1 Sep 2022 |
Revised/Clarifications |
Workers’ dormitory
Workers’ dormitories shall comply with the following additional requirements:
a. Size
Each dormitory bedroom........
b. Occupant load
The occupant load shall be based on accessible floor area on the basis of 6m² per person.
c. …………
|
|
1 Mar 2022 |
Download
|
c. Number of exit staircases or exits per storey
There shall be at least two independent exit staircases or other exits from every storey of a workers’ dormitory.
d. Maximum travel distance
The travel distance, measured from the most remote point of the dormitory bedroom to the nearest exit staircase or other storey exit, shall not exceed the maximum travel distance permitted under Table 2.2A.
e. Internal corridor to dormitory bedrooms
Dormitory bedrooms with access through an internal corridor shall comply with the following requirements:
R
Rationale - Clause
The minimum size of ventilation openings along the internal dormitory corridors minimises the risk of a smoke-logged situation. These dimensions have been validated through a fire engineering study.
(1) dormitory bedrooms shall be separated from the internal corridor by a wall having at least 1-hr fire resistance;
(2) doors opening into internal corridors shall have at least ½-hr fire resistance and be fitted with an automatic self-closing device to comply with the requirements of Cl.3.9.2; and
E
Explanations & Illustrations
Clause 9.3.3e.(1) & (2) : Workers' dormitory
Figure 9.3.3e.(1) & (2)
(3) an internal corridor shall be naturally cross ventilated in accordance with Cl.2.2.13b.(7)(c);
Effective Date: 1 Mar 2024
R
Rationale - Clause 9.3.3e.
Natural ventilation is a permanent and more reliable method for ventilating internal corridor in workers' dormitory. It ensures effective smoke dispersal and unlike mechanical ventilation and pressurisation systems which may fail during an fire emergency if they are not properly maintained.
E
Explanations & Illustrations
Clause 9.3.3e.(3) to (5) : Workers' dormitory
Figure 9.3.3e.(3) to (5) - 1
Area of each external opening = W x H
= min. 1.75m²
Area of external opening = 2(W x H)
Percentage of external openings = 2(W x H) x 100
over internal corridor L x B
= Min. 15%
Internal corridor shall either be cross-ventilated as illustrated above or provided with natural ventilation as illustrated in Figure 9.3.3e.(3) to (5) – 2. Pressurisation of internal corridor is not allowed.
Figure 9.3.3e.(3) to (5) - 2 : Ventilation of corridors to workers' dormitory
Ventilation breaks (02, 03 & 04) as illustrated above are provided to cross ventilate the internal corridor.
Amendment History
9.3.3e. |
1 Mar 2024 |
1 Mar 2024 |
Relaxation |
9.3.3e. Internal corridor to dormitory bedrooms
Dormitory bedrooms with access through an internal corridor shall comply with the following requirements:
(1) …….
(2) …….
(3) an internal corridor shall be naturally ventilated with fixed openings on the external walls, with such ventilation openings having an aggregate free area of:
(a) at least 15% of the total floor area of the internal corridor, or
(b) at least 3.5m²m whichever is greater.
(4) each ventilation opening in the external walls shall have at least 1.75m2 free area, unobstructed by parapet walls or balustrade levels upwards such that they provide effective cross ventilation throughout the entire space of the corridor;
(5) the ventilation openings in the external walls shall be at most 12m from any part of the corridor;
(6) pressurisation of internal corridors in lieu of natural ventilation is not permitted; and
(7) other rooms or spaces ……… |
25 Aug 2023 |
Download
|
(4) pressurisation of internal corridors in lieu of natural ventilation is not permitted; and
(5) other rooms or spaces which open into or form part of the bedroom corridor and which can jeopardise the means of escape shall be compartmented by enclosures with at least 1-hr fire-resistance rating and doors with at least ½-fire resistance rating.
E
Explanations & Illustrations
Clause 9.3.3e.(7) : Workers' dormitory
Figure 9.3.3e.(7)
Store shall be fire compartmented as it opens into the designated internal escape corridor.
f. External access to dormitory bedrooms
External access to dormitory bedrooms shall be through an external corridor complying with Cl.2.3.10.
E
Explanations & Illustrations
Clause 9.3.3f. : Workers' dormitory
Figure 9.3.3f.
g. Smoke-free approach to exit staircase
Entry into an exit staircase from any part of a building of more than four storeys above ground level shall comply with requirements of Cl.2.2.13 - requirements of smoke-free approach to exit staircase. Pressurisation of a staircase in lieu of the provision of smoke-free lobby is not permitted.
E
Explanations & Illustrations
Clause 9.3.3g. : Workers' dormitory
Figure 9.3.3g.
Under Cl.2.2.13c., exit staircases to buildings under PG III will not be allowed to omit the smoke-stop lobby.
h. Bedroom compartmentation
(1) Each dormitory bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having at least 1-hr fire resistance rating, unless otherwise permitted under Cl.9.3.3f. for the provision of window openings between the bedroom and external corridor; and
(2) Dormitory bedrooms and other rooms or spaces which open into or form part of the dormitory bedroom corridor shall be separated from the corridor to comply with Cl.9.3.3e. and Cl.9.3.3f..
E
Explanations & Illustrations
Clause 9.3.3h. : Workers' dormitory
Figure 9.3.3h. - 1
Figure 9.3.3h. - 2
Figure 9.3.3h. - 3
Amendment History
9.3.3h. |
25 Aug 2023 |
25 Aug 2023 |
Revised/Clarifications |
9.3.3h. Bedroom compartmentation
(1) Each dormitory bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having at least 1-hr fire resistance rating, unless otherwise permitted under Cl.9.3.3f. for the provision of window openings between the bedroom and external corridor;
(2) Dormitory bedrooms and other rooms or spaces which open into or form part of the dormitory bedroom corridor shall be separated from the corridor to comply with Cl.9.3.3e. and Cl.9.3.3f.; and
(3) Kitchen shall be enclosed with at least 1-hr fire-rated compartment wall, including at least ½-hr fire-rated door. Kitchen can be located within each floor but shall not be within the dormitory bedroom. |
25 Aug 2023 |
Download
|
i. Kitchen compartmentation
A kitchen with open-flame cooking activity shall be enclosed with at least 1-hr fire-rated compartment wall and ½-hr fire-rated door. The kitchen shall not be located within the dormitory unit.
R
Rationale - Clause 9.3.3h.(3)
Dormitory bedrooms are meant for resting and sleeping. Hence, cooking activity, which normally involves the use of open flame, shall not be allowed in the bedrooms. This will help to reduce the risk of fire occurring in workers' dormitory.
Amendment History
9.3.3h. |
25 Aug 2023 |
25 Aug 2023 |
Revised/Clarifications |
9.3.3h. Bedroom compartmentation
(1) Each dormitory bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having at least 1-hr fire resistance rating, unless otherwise permitted under Cl.9.3.3f. for the provision of window openings between the bedroom and external corridor;
(2) Dormitory bedrooms and other rooms or spaces which open into or form part of the dormitory bedroom corridor shall be separated from the corridor to comply with Cl.9.3.3e. and Cl.9.3.3f.; and
(3) Kitchen shall be enclosed with at least 1-hr fire-rated compartment wall, including at least ½-hr fire-rated door. Kitchen can be located within each floor but shall not be within the dormitory bedroom. |
25 Aug 2023 |
Download
|
9.3.4 Temporary workers’ quarter in uncompleted permanent buildings on construction sites
Effective Date: 30 July 2020
Amendment History
9.3.4 |
|
Immediate 1 Mar 2019 (revised portion) |
Relocated from Appendix 16 of Fire Code 2013, revised |
|
--- |
-
|
9.3.4 ( dated 30 Jul 2020) |
30 July 2020 |
30 July 2020 |
Reinstatement of past requirement |
9.3.4 Temporary workers’ quarter in uncompleted permanent buildings on construction sites
a. General (1) The temporary workers’ quarters shall not be located higher than 10m above the fire engine access road level of the uncompleted building and shall not be lower than first basement level. (2) The temporary workers’ quarters shall only be used for housing workers working within the construction site. (3) Hot work is not allowed in the basement(s) where the temporary workers’ quarters are located. b. Means of escape (1) For above ground levels, provision of only one exit staircase is permitted provided that the one-way travel distance is complied with and the occupant load does not exceed 20 persons on any storey. The exit staircase shall discharge directly to exterior open space. (2) At least two independent exit staircases shall be provided for the temporary workers’ quarters located in basement levels or when the occupant load exceeds more than 20 persons on any storey. c. Compartmentation (1) Cooking is only allowed at a designated kitchen area, including basement(s). Such kitchen, shall be enclosed with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated door and shall not be located within the dormitory unit. (2) Office and storage are allowed in the basement(s) where the temporary workers’ quarters are located. They shall be compartmented from the accommodation areas with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated door. d. Fire engine access (1) Provision of fire engine access road shall be provided in accordance with the requirements for the development. Only the portion of the fire engine access road serving the temporary workers’ quarters shall be made available. (2) Where the remotest temporary workers’ quarter is located not more than 100m away from the site entrance at the public road, provision of working private fire hydrant is exempted. (3) A temporary “dry” fire hydrant is allowed. The “dry” fire hydrant shall be connected to a 150mm diameter pipe, which shall be connected the other end to a 4-way breeching inlet. This breeching inlet shall be within 18m from any fire engine accessway or fire engine access road having minimum 4m width and within 50m from any wet fire hydrant. e. Emergency power supply Emergency power supply lasting at least 2-hr shall be provided for all systems requiring it. f. Firefighting systems (1) Where dry riser system is required for the main development, they shall be commissioned and made operable for the storeys housing the temporary workers’ quarters during the accommodation period. (2) Provision of automatic sprinkler system and smoke control system is exempted for basement provided all of the following requirements are complied with: (a) The basement is effectively cross-ventilated as follows: (i) no point within the basement(s) is more than 12m from any vertical opening or void for spaces that are in between two openings or voids; (ii) no point shall be more than 6m from any opening or void for spaces that are ventilated by such opening or void on only one side; (iii) all ventilation openings shall be at least 1000 x 600mm; and (iv) the total aggregate area of these voids and vertical openings shall be at least 20% of the total basement floor area. (b) The occupant load is computed based on 6m2 per person. (3) An automatic fire alarm system shall be provided if provision of automatic fire sprinkler system is exempted for the temporary workers’ quarters located in the basement(s). (4) For temporary workers’ quarters located above ground level, fire alarm system shall be provided as stipulated under Table 6.3A. (5) Connection of fire protection systems to the approved alarm monitoring company is not required. g. Engineered smoke control system Engineered smoke control and sprinkler systems shall be required for the basement levels where the workers’ quarters are located, if the provision of cross ventilation stipulated in Cl.9.3.4.f. cannot be fulfilled. h. Storage of hazardous materials All stores of highly flammable substances shall be sited in open space at a minimum distance of 5m away from the building where the temporary workers’ quarters are located and shall comply with the relevant standards. Temporary workers’ quarter in uncompleted permanent buildings on construction sites a. General (1) The temporary workers’ quarters shall not be located higher than 10m above the fire engine access road level of the uncompleted building and shall not be lower than first basement level. (2) The temporary workers’ quarters shall only be used for housing workers working within the construction site. (3) Hot work is not allowed in the basement(s) where the temporary workers’ quarters are located. b. Means of escape (1) For above ground levels, provision of only one exit staircase is permitted provided that the one-way travel distance is complied with Table 2.2A and the occupant load does not exceed 20 persons on any storey. The exit staircase shall discharge directly to exterior open space. (2) At least two independent exit staircases shall be provided for the temporary workers’ quarters located in basement levels or when the occupant load exceeds more than 20 persons on any aboveground storey. (3) Every storey shall be provided with exit facilities for its occupant load. Only those exits designated for escape of the workers shall be included in the exit capacity calculations. c. Compartmentation (1) Cooking is only allowed at a designated kitchen area, including basement(s). Such kitchen, shall be enclosed with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated door and shall not be located within the dormitory unit. (2) Office and storage are allowed in the basement(s) where the temporary workers’ quarters are located. They shall be compartmented from the accommodation areas with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated door. (3) Only non-combustible materials shall be used for the construction of temporary workers’ quarters. (4) The floor area of each worker bedroom or the total floor area of a group of small worker bedrooms shall not exceed 120m2. Compartment wall of having fire resistance rating of at least 1-hr shall be provided to separate the bedrooms so as to limit each compartment size to a maximum of 120m2. (5) The worker bedrooms shall be separated from the internal corridor by a wall having fire resistance rating of at least 1-hr. Doors opening into the internal corridor shall have fire resistance rating of at least half an hour. (6) The worker bedrooms shall be separated from the external corridor by a wall having fire resistance rating of at least 1-hr, except that ventilation openings of non-combustible construction can be fixed at or above a level of 1.1m, measured from the finished floor level of the external corridor to the sill height of the opening. Doors opening into the external corridor are not required to have fire resistance rating. d. Fire engine access (1) Provision of fire engine access road shall be provided in accordance with the requirements for the development. Only the portion of the fire engine access road serving the temporary workers’ quarters shall be made available. (2) Every part of the required fire engine access road shall be within an unobstructed distance of 50m from the nearest working fire hydrant. Where the remotest temporary workers’ quarter is located not more than 100m away from the site entrance at the public road, provision of working private fire hydrant is exempted. (3) A temporary “dry” fire hydrant is allowed. The “dry” fire hydrant shall connected to a 150mm diameter pipe, which shall be connected the other end to a 4-way breeching inlet. This breeching inlet shall be within 18m from any fire engine accessway or fire engine access road having minimum 4m width and within 50m from any wet fire hydrant. e. Emergency power supply (1) Emergency power supply lasting at least 2-hr shall be provided for all firefighting systems serving the temporary workers’ quarters. (2) The location, arrangement, control and installation of electrical wiring of the secondary source of power supply, be it in the form of battery, standby generator, inverter or other accepted equipment, shall be in accordance with Chapter 5. f. Firefighting systems (1) Where dry riser system is required for the main development, they shall be commissioned and made operable for the storeys the temporary workers’ quarters during the accommodation period. (2) Provision of automatic sprinkler system and smoke control system is exempted for basement provided the basement is effectively cross-ventilated as follows: (a) no point within the basement(s) is more than 12m from any vertical opening or void for spaces that are in between two openings or voids; (b) no point shall be more than 6m from any opening or void for spaces that are ventilated by such opening or void on only one side; (c) all ventilation openings shall be at least 1000 x 600mm; and (d) the total aggregate area of these voids and vertical openings shall be at least 20% of the total basement floor area. (3) An automatic fire alarm system shall be provided if provision of automatic fire sprinkler system is exempted for the temporary workers’ quarters located in the basement(s). (4) For temporary workers’ quarters located above ground level, fire alarm system shall be provided as stipulated under Table 6.3A. (5) Connection of fire protection systems to the approved alarm monitoring company is not required. (6) Standby fire hoses can be installed in lieu of the dry riser system, on condition that the temporary workers’ quarters are adequately covered by fire hose reel(s). (7) Provision of fire extinguishers shall be in accordance with Cl.6.1. (8) Provision of fire hose reels shall be in accordance with Cl.6.2.8. g. Engineered smoke control system Engineered smoke control and sprinkler systems shall be required for the basement levels where the workers’ quarters are located, if the provision of cross ventilation stipulated in Cl.9.3.4.f. cannot be fulfilled. h. Storage of hazardous materials (1) All stores of highly flammable substances shall be sited in open space at a minimum distance of 5m away from the building where the temporary workers’ quarters are located and shall comply with the relevant standards. (2) All LPG cylinder installations serving the temporary workers’ quarters shall be in accordance with Cl.10.1. i. Occupant load The occupant load shall be based on the floor area of the temporary workers’ quarters on the basis of 3m2 per person, excluding non-simultaneous areas such as toilets, kitchens etc., or the actual number of occupants for which each occupied space of the floor is designed as shown on the plan, whichever is greater. j. Emergency lighting and exit signs Emergency lightings and exit signs serving the temporary workers’ quarters shall be in accordance with Cl.8.1. |
30 July 2020 |
Download
|
a. General
(1) The temporary workers’ quarters shall not be located higher than 10m above the fire engine access road level of the uncompleted building and shall not be lower than first basement level.
(2) The temporary workers’ quarters shall only be used for housing workers working within the construction site.
(3) Hot work is not allowed in the basement(s) where the temporary workers’ quarters are located.
b. Means of escape
(1) For above ground levels, provision of only one exit staircase is permitted provided that the one-way travel distance is complied with Table 2.2A and
the occupant load does not exceed 20 persons on any storey. The exit staircase shall discharge directly to exterior open space.
(2) At least two independent exit staircases shall be provided for the temporary workers’ quarters located in basement levels or when the occupant load exceeds 20 persons on any aboveground storey.
(3) Every storey shall be provided with exit facilities for its occupant load. Only those exits designated for escape of the workers shall be included in the exit capacity calculations.
c. Compartmentation
(1) Cooking is only allowed at a designated kitchen area, including basement(s). Such kitchen, shall be enclosed with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated door and shall not be located within the dormitory unit.
(2) Office and storage are allowed in the basement(s) where the temporary workers’ quarters are located. They shall be compartmented from the accommodation areas with at least 1-hr fire-rated compartment wall and at least ½-hr fire-rated
door.
(3) Only non-combustible materials shall be used for the construction of temporary workers’ quarters.
(4) The floor area of each worker bedroom or the total floor area of a group of small worker bedrooms shall not exceed 120m2.
Compartment wall of having fire resistance rating of at least 1-hr shall be provided to separate the bedrooms so as to limit each compartment size to a maximum of 120m2.
(5) Notwithstanding subclause (4), the worker bedrooms shall be separated from
any internal corridor by a wall having fire resistance rating of at least 1-hr. Doors opening into the internal corridor shall have fire resistance rating of at least half an hour.
(6) The worker bedrooms shall be separated from
any external corridor by a wall having fire resistance rating of at least 1-hr, except that ventilation openings of non-combustible construction can be fixed at or above a level of 1.1m, measured from the finished floor level of the external corridor
to the sill height of the opening. Doors opening into the external corridor are not required to have fire resistance rating.
d. Fire engine access
(1) Provision of fire engine access road shall be provided in accordance with the requirements for the development. Only the portion of the fire engine access road serving the temporary workers’ quarters shall be made available.
(2) Every part of the required fire engine access road shall be within an unobstructed distance of 50m from the nearest working fire hydrant. Where the remotest temporary workers’ quarter is located not more than 100m away from the site entrance
at the public road, provision of working private fire hydrant is exempted.
(3) A temporary “dry” fire hydrant is allowed. The “dry” fire hydrant shall be connected to a 150mm diameter pipe, which shall be connected the other end to a 4-way breeching inlet. This breeching inlet shall be within 18m
from any fire engine accessway or fire engine access road having minimum 4m width and within 50m from any wet fire hydrant.
e. Emergency power supply
(1) Emergency power supply lasting at least 2-hr shall be provided for all firefighting systems serving the temporary workers’ quarters.
(2) The location, arrangement, control and installation of electrical wiring of the secondary
source of power supply, be it in the form of battery, standby generator, inverter or other accepted equipment, shall be in accordance with Chapter 5.
f. Firefighting systems
(1) Where dry riser system is required for the main development, they shall be commissioned and made operable for the storeys housing the temporary workers’ quarters during the accommodation period.
(2) Provision of automatic sprinkler system and smoke control system is exempted for basement provided the basement is effectively cross ventilated as follows:
(a) no point within the basement(s) is more than 12m from any vertical opening or void for spaces that are in between two openings or voids;
(b) no point shall be more than 6m from any opening or void for spaces that are ventilated by such
opening or void on only one side;
(c) all ventilation openings shall be at least 1000 x 600mm; and
(d) the total aggregate area of these voids and vertical openings shall be at least 20% of the total basement floor area.
(3) An automatic fire alarm system shall be provided if provision of automatic fire sprinkler system is exempted for the temporary workers’ quarters located in the basement(s).
(4) For temporary workers’ quarters located above ground level, fire alarm system shall be provided as stipulated under Table 6.3A.
(5) Connection of fire protection systems to the approved alarm monitoring company is not required.
(6) Standby fire hoses can be installed in lieu of the dry riser system, on condition that the temporary workers’ quarters are adequately covered by fire hose reel(s).
(7) Provision of fire extinguishers shall be in accordance
with Cl.6.1.
(8) Provision of fire hose reels shall be in accordance with Cl.6.2.8.
g. Engineered smoke control system
Engineered smoke control and sprinkler systems shall be required for the basement levels where the workers’ quarters are located, if the provision of cross ventilation stipulated in Cl.9.3.4.f. cannot be fulfilled.
h. Storage of hazardous materials
(1) All stores of highly flammable substances shall be sited in open space at a minimum distance of 5m away from the building where the temporary workers’ quarters are located and shall comply with the relevant standards.
(2) All LPG cylinder installations serving the temporary workers’ quarters shall be in accordance with Cl.10.1.
i. Occupant load
The occupant
load shall be based on the floor area of the temporary workers’ quarters on the basis of 4.2m2 per person, excluding non-simultaneous areas such as toilets, kitchens etc., or the actual number of occupants for which each occupied
space of the floor is designed as shown on the plan, whichever is greater.
j. Emergency lighting and exit signs
Emergency lightings and exit signs serving
the temporary workers’ quarters shall be in accordance with Cl.8.1.
Effective Date: 1 Sep 2022
Amendment History
9.3.4i |
30 July 2020 |
1 Feb 2021 |
Revised |
Occupant load The occupant load shall be based on the floor area of the temporary workers’ quarters on the basis of 3m2 per person, excluding non-simultaneous areas such as toilets, kitchens etc., or the actual number of occupants for which each occupied space of the floor is designed as shown on the plan, whichever is greater. |
30 July 2020 |
Download
|
9.3.4i. (dated 1 Sep 2022) |
1 Sep 2022 |
1 Sep 2022 |
Revised/Clarification |
Occupant load
The occupant load shall be based on the floor area of the temporary workers’ quarters on the basis of 6m2 per person, excluding non-simultaneous areas such as toilets, kitchens etc., or the actual number of occupants for which each occupied space of the floor is designed as shown on the plan, whichever is greater.
|
1 Mar 2022 |
Download
|
TABLE 9.3A STAIRCASE LANDING WIDTH/DEPTH |
---|
Stair Width | Minimum Landing width | Minimum Landing Depth |
---|
1 | 2.8 | 1.9 | Allows mattress or stretcher evacuation only (i.e. no pedestrian passing) |
1.25 | 2.8 | 1.9 | Allows mattress or stretcher evacuation and restricted ambulant passing |
1.5 | 3.2 | 1.55 |
1.75 | 3.6 | 1.35* | Allows mattress or stretcher evacuation and ambulant passing. |
2 | 4 | 1.25* |
Note: * = Clear landing depth, instead of the clear stair width, shall be taken for
the purpose of calculating the exit capacity of the staircase. |