2.2.1 General
R
Rationale - Clause 2.2.1
The exit provisions allow occupants to leave the fire area safely in the shortest possible time to a safe area.
E
Explanations & Illustrations
Clause 2.2.1 : General
( No illustration )
DETERMINING NUMBER AND ADEQUACY OF EXIT FACILITIES
It is very essential that the building designers establish the number, sizes and capacity of exit facilities, especially that of exit doorways and exit staircases, to ensure their adequacy in facilitating the evacuation of all the occupants from
that building during an emergency.
To determine the number and adequacy of exit doorways and staircases from a building or storey of a building, the following 3 steps must be taken:
a. Determine the occupant load, OL, on each storey of the building. This means computing the total number of persons that could be ‘accommodated’ in all spaces on a storey of the building. This is done on a storey by storey basis.
b. Determine the number of ‘unit of width’ of exit required facilitating escape for the above OL from each storey of that building. Cl.2.2.5 shall be referred for the explanation and application of the ‘unit of width’ for exit computation.
c. Determine the number of and the minimum widths of the exit doors and exit staircases required facilitating escape for that OL on each storey of that building.
The determination of exit requirements for a building shall be based upon the type of use or occupancy of the building, the occupant load, the floor area, the travel distance to an exit and the capacity of exits as provided in Table 2.2A and herein. Every storey of a building shall be provided with exit facilities for its occupant load. Vertical exits provided from any storey above ground level
may serve simultaneously all storeys above the ground level. Vertical exits provided from any storey below ground level may serve all storeys below ground level, subject to the provisions of Cl.2.3.5 which prohibit basement staircases being continuous with exit staircases serving the upper storeys, unless otherwise allowed by the SCDF.
2.2.2 Mixed occupancy
E
Explanations & Illustrations
Clause 2.2.2 : Mixed occupancy
MIXED OCCUPANCY - OFFICES, FACTORIES & WAREHOUSES
1. TRAVEL DISTANCE REQUIREMENT:-
For a storey of mixed occupancy building consisting of offices, factories and warehouses, the exit capacity of staircases may be based on the total of the occupancies computed separately for each usage type as per Table 1.4B. However the position of the exit staircases shall be so located that the maximum permissible travel distance from any remote point to the staircase
shall be based on that of the factory, having the stricter requirements in Table 2.2A.
That is, equal to 30m for two-way non-sprinkler-protected buildings and 60m for two-way sprinkler protected buildings, and not the 45m and 75m distances allowable for office developments. Hence:
Travel distance (in Figure 2.2.2-1) to the nearest exit staircase shall not exceed 30m or 60m (if sprinkler-protected).
The Direct distance to the nearest exit staircase, if there are no predetermined walls, shall not exceed 20m (2/3 x 30m) or 40m (2/3 x 60m, if sprinkler-protected).
Figure 2.2.2 - 1 : Example of a mixed development with factory, office & storage
The exit provisions in a mixed development may be assessed and provided separately if the differing purpose types are clearly defined and compartmentalized. For example, the escape distances for the offices’ area which is clearly located in
one part of the building as shown in Figure 2.2.2 – 2, may be based on the office configurations given in Table 2.2A.
The remaining part of the building with the industrial usage is then based on the factory configurations.
Figure 2.2.2 - 2 : Example of separate travel distance application
2. EXIT REQUIREMENT:-
Buildings with mixed occupancies the exit capacity of its exit staircases shall be based on the type of occupancy or usage having the strictest exit requirements given in Table 2.2A.
For example;
A storey of a building comprises dormitory, production and offices separated by usage with compartment walls, but shares common facilities like the staircases.
Then the exit capacity of its staircases shall be based on:
Dormitory occupancy which the number of persons per unit of exit width (500mm) of staircase is 45 persons.
Instead of:
Factory / Office / Warehouse occupancies which the number of persons per unit of exit width (500mm) of staircase is 60 persons.
Figure 2.2.2 - 3 : Mixed factory development with office & dormitory blocks sharing common exit staircases
The maximum permissible occupant load (OL) for the entire storey of the building in Figure 2.2.2 - 3, for example, shall be based on the capacity of the two exit staircases of 2m width each, assumed serving a dormitory building. i.e.
OL = 4 units x 45 persons x 2 staircases
= 360 persons (maximum per storey)
Section
Figure 2.2.2 - 4 : Building with mixed occupancy
Section
Figure 2.2.2 - 5 : Building with mixed occupancy
This capacity of staircase exit width shall be applicable for all levels or storeys of the building with such shared staircase arrangement. This is regardless of the dormitory being located on the second storey or the top most storey of
a multi-storey building. The only exemption is when the space with the more stringent requirement per unit of exit width, e.g. the dormitory, is located on only the ground level storey with direct escape to the external space.
(1) Travel distance requirement:
For a storey of mixed occupancy building consisting of offices, shops and place of public resort, the exit capacity of staircases may be based on the total of the occupancies computed separately for each usage type as per Table 1.4B. However the position of the exit staircases shall be so located that the maximum permissible travel distance from any remote point to the staircase
shall be based on that of the shop, having the stricter requirements in Table 2.2A
. That is, maximum 45m two-way escape travel distance for non-sprinkler-protected buildings and 60m two-way escape travel distance for sprinkler protected buildings shall be applicable and not the 45m and 75m distances allowable
for office developments. Hence:
Travel distance (in Figure 2.2.2 - 1) to the nearest exit staircase shall not exceed 30m or 60m (if sprinkler-protected).
The direct distance to the nearest exit staircase, if there are no predetermined walls, shall not exceed 30m (2/3 x 45m) or 40m (2/3 x 60m, if sprinkler-protected).
MIXED OCCUPANCY - OFFICES, SHOPS & PLACES OF PUBLIC RESORT
1. TRAVEL DISTANCE REQUIREMENT:
For a storey of mixed occupancy building consisting of offices, shops and place of public resort, the exit capacity of staircases may be based on the total of the occupancies computed separately for each usage type as per Table 1.4B. However the position of the exit staircases shall be so located that the maximum permissible travel distance from any remote point to the staircase
shall be based on that of the shop, having the stricter requirements in Table 2.2A.
That is, maximum 45m two-way escape travel distance for non-sprinkler-protected buildings and 60m two-way escape travel distance for sprinkler-protected buildings shall be applicable and not the 45m and 75m distances allowable for
office developments. Hence:
Travel distance (in Diagram 2.2.2-1) to the nearest exit staircase shall not exceed 30m or 60m (if sprinkler-protected).
The direct distance to the nearest exit staircase, if there are no predetermined walls, shall not exceed 30m (2/3 x 45m) or 40m (2/3 x 60m, if sprinkler-protected).
Figure 2.2.2 - 6
The exit provisions in a mixed development may be assessed and provided separately if the differing purpose types are clearly defined and compartmentalised.
For example, the escape distances for the offices’ area, which is clearly located in one part of the building as shown in Figure 2.2.2 - 6, may be based on the office configurations given in Table 2.2A. The remaining part of the building with the shopping usage is then based on the shop configurations.
Figure 2.2.2 - 7 Example of separate travel distance application
Figure 2.2.2 - 8
2. EXIT REQUIREMENT:
Buildings with mixed occupancies the exit capacity of its exit staircases shall be based on the type of occupancy or usage having the strictest exit requirements given in Table 2.2A.
For example, see Figure 2.2.2 - 3
A storey of a building comprises office and hotel residential occupancy separated by compartment walls, but shares common facilities like the staircases and lifts.
Then the exit capacity of its shared staircase (staircase S2) shall be based on the most stringent type of mixed occupancies, i.e. hotel residential floors.
Office Occupancy (Staircase S1)
No. of persons per unit of exit width (500mm) of staircase = 60 persons.
Hotel Residential Occupancy (Staircase S2 & S3)
No. of persons per unit of exit width (500mm) of staircase = 45 persons.
Figure 2.2.2 - 9 : Mixed development with office, shop & restaurant sharing common exit staircases
In the case of restaurant, the maximum permissible occupant load can be based on the capacity of the three staircases. As Staircase S3 is for the exclusive use of restaurant, owing to its location, this staircase is inaccessible
to occupants from offices and shops. Therefore, Staircase S3 shall not be computed as a common exit staircase rather computed as exit staircase for restaurant only. That is:
Exit capacity of common staircases = 4 units x 60 persons x 2 staircases
(Staircases S1 & S2 of 2m width each) = 480 persons
Hence, each common exit staircase can accommodate 240 persons (½ of 480 persons)
It is acceptable to allow ½ the occupant load of restaurant to use Staircase S3 and the other ½ to use the common exit staircases S1 & S2. Therefore, the maximum permissible occupant load for shops and
offices shall include ½ the occupant load of restaurant, subject to not exceeding a total of 480 persons.
Section
Figure 2.2.2 - 10 : Situation where the exit capacities of entire staircase on all storeys are accounted similarly
The strictest capacity of staircase exit width (applicable to restaurant) shall be applicable to all levels or storeys of the building with such shared staircase arrangement. This is regardless of the restaurant being
located on the second storey or the top most storey of a multi-storey building.
Figure 2.2.2 - 11 : Mixed occupancy building
Auditorium space shares the internal corridor as the classrooms. Such space cannot be qualified as non-simultaneous occupancy within the same storey.
Where different parts of a building or storey of a building are designed for different types of occupancies or used for different purposes at the same time, the exit requirements of the entire building or storey of the building shall be determined on the basis of that type of occupancy or usage having the strictest exit requirements or the exit requirements for each building section shall be determined separately.
2.2.3 Multiple occupancy or use
E
Explanations & Illustrations
Clause 2.2.3 : Multiple occupancy or use
A multi-purpose hall is an example of a space with multiple occupancy or use. It may have the various uses as listed below. Its exit provisions shall be based on the usage with the greatest occupant load. In this case it should cater to that of the dance hall, being the most stringent basing on an area of 1m2 per person.
Examples of usage of multipurpose hall:
a. Sports gym
b. Dinner/buffet functions
c. Exhibitions/seminars
d. Church assembly
e. Lecture hall/classroom
f. Dance hall
Section
Figure 2.2.3 - 1 : Example of building with a multiple usage storey
Section
Figure 2.2.3 - 2 : Example of building with a multiple usage storey
In Diagram 2.2.3-1, the multi-purpose hall located on the 7th storey would have the highest occupant load. Hence, adequate number of exit staircases required to accommodate the evacuation of its occupant load shall be provided to the building. The total exit capacity of its exit staircases shall be determined based on its usage with the highest density of people. The exit staircases shall be carried right down to the ground level without any reduction in its width, regardless of the lower storeys having lesser number of occupants.
On the other hand, if the multi-purpose hall is located on an intermediate storey, then the exit requirements or provisions from that storey shall only be applicable to all the storeys below it. As for those storeys above that storey with the multipurpose hall, their exit capacities need only cater to what is the strictest above each respective storey.
Where a building or storey of a building or a part of a building is used for multiple purposes involving different activities at different times, that purpose or use involving the greatest number of occupants shall form the basis for determining the exit requirements.
2.2.4 Non-simultaneous occupancy
Effective Date: 25 Aug 2023
E
Explanations & Illustrations
Clause 2.2.4 : Non-simultaneous occupancy
Communal roof deck which is accessible to all residents shall be treated separately for the calculation of occupant load. For buildings under PG II, the occupancy load calculation is based on gross floor area of 15m2 per person, calculated on habitable areas. Spaces outside the residential units, such as lobbies, corridors would be excluded from calculation. Similarly, within the residential units, areas such as toilets, store room, kitchen and household shelter would be excluded from calculation. Living room, balconies and bedroom should be treated as habitable areas.
Figure 2.2.4 - 1 : Example of non-simultaneous areas
Staff canteens, if provided, is to be treated as simultaneous occupancies. This is due to the nature of its usage, whereby public or staff from other levels of the building would be patronising it through its operating hours. Pantries on the other hand, provided in the various levels of offices or production areas, catering to specific group of staff, may be treated as non-simultaneous areas. Hence, in applying the above clause, building owners has to be certain such rooms or spaces are not accessible to the public.
Figure 2.2.4 - 2 : Example of non-simultaneous areas (exaggerated)
Amendment History
2.2.4 |
25 Aug 2023 |
25 Aug 2023 |
Revised/Clarification |
2.2.4 Non-simultaneous occupancy
The floor areas of toilets, locker rooms, storage rooms, lobbies, corridors and similar rooms and spaces that serve other rooms and spaces on the same storey but are not occupied at the same time as such other rooms or spaces, can be omitted from the occupant load calculations of that storey of the building on which they are located. |
25 Aug 2023 |
Download
|
The floor areas of toilets, locker rooms, lobbies, and corridors that are not occupied at the same time as other rooms or spaces by building occupants, can be omitted from the occupant load calculations of that storey of the building in which the storey is located.
2.2.5 Capacity of exits and exit facilities
R
Rationale - Clause 2.2.5
Adhering to the design parameters will prevent overcrowding and will ensure the corridors, exit staircases and doors are adequate in size to receive all the occupants on that floor during evacuation.
E
Explanations & Illustrations
Clause 2.2.5 : Capacity of exits & exit facilities
To prevent overcrowding one has to ensure that the corridor and the exit staircases serving a storey of a building are adequate in size to receive all the occupants on that floor at the time of evacuation.
Figure 2.2.5 - 1 : Typical floor plan of standard slab design
The capacity of exit doors to the industrial units, corridor, exit doors to staircases and exit staircases are measured in units of width of one half of a metre i.e.:
Exit door/corridor/staircase clear width
|
Number of unit width
|
1m
|
2
|
1.5m
|
3
|
2m
|
4
|
Where a fraction of 250mm or more are added to one or more full units, half of a unit of width shall be credited, for example:
Exit door/corridor/staircase clear width
|
Number of unit width
|
1000 to 1249mm
|
2
|
1250 to 1499mm
|
2.5
|
1500 to 1749mm
|
3
|
1750 to 1999mm
|
3.5
|
2000mm (maximum)
|
4 (maximum number per exit)
|
The number of persons per unit of width shall be determined by the type of occupancy and type of exit as listed under Table 2.2A of the current Fire Code.
Example 1 : High hazard building
1 unit width = 500mm = 30 and 40 persons per unit width through staircase and doorway respectively.
Therefore: 1m doorway facilitates escape for 80 occupants from a high hazard factory, while 1m of its stairway permits escape for only 60 of its occupants.
The high hazard building has very much more stringent requirements than other buildings. It is due to the nature of its contents. In an emergency situation, because of the highly volatile or explosive nature of the contents, its occupants have very
little reaction time to evacuate to a safer area. Hence, exits must be designed such that they are more readily available for escape purposes.
Where a room or space is required to be provided with two exits, each exit shall be of sufficient width to accommodate not less than one half the total occupant load.
Figure 2.2.5 - 2 : Acceptable distribution of exit capacity
Figure 2.2.5 - 3 : Not Acceptable distribution of exit capacity
The above sub-clause is to address the problem, which may arise if staircases are not proportionately sized and distributed. For example, a fire near Stair A in Diagram 2.2.5 –3, which is designed to facilitate escape for 240
persons, can render it inaccessible. This would mean that, the other exit, stair B, which is only designed for 120 persons’ escape, would hence need to facilitate escape for the full OL of 360 persons from that storey.
This scenario would render stair B to be drastically inadequate to facilitate all the occupants’ timely escape, before the fire and smoke engulf the entire floor space. This is because it would require three times as long to evacuate
the occupants from that storey using only stair B.
Imagine the consequences, for a scenario where the entire staircase A with the larger exit capacity is totally damaged or not usable in a high-rise building fire.
a. The capacity of exits, exit staircases, exit passageways, corridors, exit doors and other exit facilities shall be measured in units of half a metre's width. The number of persons per unit of width shall be determined by the type of occupancy and type
of exit as listed under Table 2.2A. In the determination
of each exit width, fractions of a unit width less than 250mm shall not be factored in the measurement. Where 250mm or more are added to one or more full units, half of a unit of width shall be factored in.
b. Where a room or space is required to be provided with two exits, each exit shall be of sufficient width to accommodate not less than half the total occupant load.
2.2.6 Determination of travel distance
The maximum travel distance for the respective types of occupancies shall be not greater than as laid down in Table 2.2A and read in conjunction with all of the following:
a. In the case of a floor area designed with minimum two exits, the maximum travel distance as given in Table 2.2A shall be applicable. The maximum travel distance starting from the most remote point in any occupied space to the nearest exit, shall not exceed the limits specified in Table 2.2A.
R
Rationale - Clause 2.2.6a
The travel distance serves to limit the distance a person is required to travel from the occupied space to an exit staircase door, which every designer should observe. On the other hands, it must also be stated that conforming to the permissible travel distance alone does not necessarily guarantee building occupant life safety during an emergency.
E
Explanations & Illustrations
Clause 2.2.6a. : Determination of travel distance
Figure 2.2.6a. : Not acceptable separation of exit staircases
In the above figures, the exit staircases are not remotely located from each other to reduce the possibility that more than one staircase can be blocked off by fire or other emergency condition. The escape routes AB, CD, EF, and GH are all considered
as one-way direct travel as there is no alternative escape route. Occupants escaping in a fire emergency are unable to reach the nearest staircase as the escape routes are blocked by fire. The distribution of the staircases does not meet the intents
of Cl.2.3.12 of current Fire Code, which require that “such exits shall be remotely located from each other and shall be arranged
and constructed to minimise the possibility that more than one can be blocked by any fire or other emergency condition”.
In the above figures, direct travel distances, which are highlighted, will be considered as one-way direct travel instead of two-way direct distance travel. To overcome the problems of one-way direct travel, relocation or addition of an exit staircase
would be necessary, subject to meeting the direct travel distance requirements.
b. In a large floor area without sub-division of rooms, corridors and so forth, the travel distance can adopt the “direct distance” concept as a guide and shall not exceed two-third of the maximum travel distance permitted under Table 2.2A. Where the large floor area is undergoing sub-division of rooms, corridors, etc., the maximum travel distance shall be in accordance with Table 2.2A.
R
Rationale - Clause 2.2.6b
The two-third direct distance method is intended to guide designer for planning of large open floor layout for facilitating flexibility for future inclusions and changes in layout. This guide serves to minimise problem of complying with travel distance during subsequent A/A works.
E
Explanations & Illustrations
Clause 2.2.6b. :Determination of travel distance
Similarly, if the details of the internal layout are furnished on the building plan submissions, hence the actual travel distances permissible under the Table 2.2A would be taken into account.
However, in most situations during the planning and building plan submission stages of a building, its designer is unable to confirm the layout of the storey spaces. It is therefore recommended that the direct distance measurements, which are two thirds
of the allowable travel distances, be strictly applied to such ‘open’ plans.
Example
Figure 2.2.6b. - 1 : Typical single tenancy single office storey
The dotted walls in Figure 2.2.6(b) - 1, for example, may not be shown on plan and/or may be of differing configurations. In such indefinite situation, a straight line drawn from the most remote point A to B or C shall be taken as the two-way
direct distance. If the maximum permissible two-way travel distance given in Table 2.2A for such usage is 60m (sprinkler-protected), then the direct distances (straight lines AB or AC) shall not exceed 40m, i.e. ⅔ x 60m. This shall also apply to the one-way distances BD and CF, as the actual one-way distances could possibly be D1HB
and F1JC.
This application of the direct distance measurements, besides facilitating flexibility for future inclusions and changes in layout, ensures that escape distances for the occupants would not subsequently be excessive and life threatening in a
fire emergency.
(Note: “travel distance” is to be taken as direct distance).
Maximum escape distance design parameters
Item
|
Sprinklered
|
Non-sprinklered
|
Shops
|
Offices
|
Places of public resort
|
Shops
|
Offices
|
Places of public resort
|
1-way Travel Distance (m)
|
25
|
30
|
25
|
15
|
15
|
15
|
1-way Direct Distance (m)
|
16.6
|
20
|
16.6
|
10
|
10
|
10
|
2-way Travel Distance (m)
|
60
|
75
|
60
|
45
|
45
|
45
|
2-way Direct Distance (m)
|
40
|
50
|
40
|
30
|
30
|
30
|
Figure 2.2.6b. - 2 : Typical storey plan of an office building
DIRECT DISTANCE = ⅔ TRAVEL DISTANCE
The actual path that an occupant needs to take from any part of a storey space to the nearest exit door to the external space or exit staircase, will be measured for escape travel distance compliance. This distance takes into account the internal
partitions within that floor space and it shall comply with the relevant travel distances stipulated in Table 2.2A.
Thus, where details of the internal layout are furnished in the building plan submissions, for example Figure 2.2.6 (a) & (b) – 1, the full travel distances permissible under the Table 2.2A would be applied.
However, in most situations during the planning and building plan submission stages of a building, the designer is unable to confirm the internal layout of the storey spaces. It is recommended that the direct distance measurement, which is two
thirds of the allowable travel distances, should be applied to such ‘open’ layout plans.
Example
Figure 2.2.6b. - 3
Figure 2.2.6b. - 4
A to B is considered as one-way travel distance and it shall be not more than 25m (sprinkler-protected). In computing two-way travel distance, the escape route from point A, B, C shall not exceed 60m (sprinkler-protected)
Figure 2.2.6b. - 5
Point A to C and Point A to B are considered two-way travel distance if the separation distance between exit doors of the two staircases is equal to or more than ½D or ⅓D (sprinkler-protected). If the storey space is to be subdivided
for occupation by more than one occupier, a common corridor around the service core shall be created to meet the travel distance requirements.
Figure 2.2.6b. - 6
Escape routes AB, AC are considered two-way direct travel. Escape routes DE, FG are considered one-way direct travel distances.
Figure 2.2.6b. - 7
The numerous one-way direct travel distances are illustrated by dashed lines.
The provision of fixed corridors and rooms in an open floor space would create numerous “common paths” from the rooms to the exit staircases as shown in the above figure. Common paths of travel are one-direction
travel only without the choice of travelling in another separate direction toward an exit.
Figure 2.2.6b. - 8
In determining the types of travel distance, Point A, B or C is considered one-way travel distance or “common path”. At point C, where an occupant has the choice of more than one escape direction, would be considered
as the starting point for 2-way travel distance. Hence, escape routes C E and C D are considered two-way travel distance.
Figure 2.2.6b. - 9 : Example of 1-way direct & travel distances from subdision of storey spaces
Escape routes AB, AC are considered two-way direct travel. Escape routes DE, FG are considered one-way direct travel distances.
c. For the purpose of this clause, the most remote point from which the travel distance is measured shall be taken as being 400mm from the enclosure walls of the room or space.
E
Explanations & Illustrations
Clause 2.2.6c. : Determination of travel distance
Axonometric Section
Figure 2.2.6c.
d. In the case of a residential apartment or maisonette, the travel distance shall be determined based on the provisions under Cl.9.2.1a.(5).
e. Where area of refuge is provided in lieu of required exits, travel distance shall be measured to the exit door at the corridor leading to the area of refuge.
E
Explanations & Illustrations
Clause 2.2.6e. : Determination of travel distance
Where an area is designated as ‘area of refuge’ (Building B in Figure 2.2.6e., it must have adequate provision of exit facility and shall be adequate in size to hold the occupant load it receives from the floor area (Building A) it
serves, allowing at least 0.3m² per person. Area of refuge acts as a temporary holding area allowing the occupants more time for evacuation. Hence, it shall be protected from the fire and smoke risk from building A via the provision of cross-ventilated
bridges or external corridors.
Reference shall also be made to Cl.1.4.9 and Cl.2.2.15 for more explanations and details on the area of refuge.
Figure 2.2.6e. Area of refuse located in other compartment
of the same building connected through a linkway/bridge
Where an area is designated as ‘area of refuge’ (Building B in Figure 2.2.6e. – 1 & 2), it must be adequate in size to hold the occupant load it receive from the floor area (Building A)
which it serves as area of refuge. Area of refuge acts as a temporary holding area allowing the occupants more time for evacuation. Hence, it shall be protected from the fire and smoke risk from Building A via the provision of cross-ventilated bridges
or external corridors.
While some conditions for the area of refuge is given below, reference shall also be made to Cl.1.4.9 and Cl.2.2.15 for more explanations and details on the area of refuge.
Figure 2.2.6e. - 2 : Area of refuge located in other building
connected through a linkway/bridge
Lines EA and ED are taken as two-way direct distance measurements.
General conditions for area of refuge
a. Occupant Load for area of refuge to be based on 0.3m2 per person.
b. Each connecting area shall have at least one protected staircase or exit facility of adequate width discharging at ground level.
c. Access door to area of refuge shall be kept accessible at all times
d. Door No 1, {in Figure 2.2.6e. – 2} leading to area of refuge can also be treated as a required exit from the area served by it, and hence travel distance can also be measured to this door.
Figure 2.2.6e. - 3 : Area of refuge located in other building connected through an external corridor
General conditions for area of refuge
a. Area of Refuge shall be adequate in size to hold the occupant load it receives from Building A, in addition to its own occupant load calculated on the basis 0.3m2 per person.
b. Each connecting area or floor served by an area of refuge shall have at least one protected staircase or exit facility of adequate width discharging at ground level.
c. Access door to area of refuge shall be kept accessible at all times.
d. Door D & E, {in Figure 2.2.6e. – 2 & 3 respectively} leading to area of refuge can also be treated as a required exit from the area served by it, and hence travel distance can also be measured to these doors.
f. Where permitted under Cl.2.3.3 for exit staircases to be entered without the provision of an exit
door, the travel distance shall be measured to a position where the exit door would be installed if otherwise required.
E
Explanations & Illustrations
Clause 2.2.6f. : Determination of travel distance
Figure 2.2.6f.
g. Ancillary office within other purpose groups
Where an ancillary office is housed within a space belong to other Purpose Groups, the travel distance requirement for the ancillary office is allowed to be based on PG IV, provided:
E
Explanations & Illustrations
Clause 2.2.6g. : Determination of travel distance
Figure 2.2.6g. : Example of separate travel distance application
The fire risk in office space is lower than factory space. If there is fire separation between office and factory spaces as shown above, the travel distance requirement for the ancillary office is allowed to be based on office use under PG IV.
(1) the ancillary office is fire compartmented from spaces belonging to the other purpose groups; and
(2) the ancillary office occupants shall have access to exit(s) within the ancillary office compartment leading to direct discharge at ground level into an external space, exit staircase, or internal/ external exit passageway.
2.2.7 Minimum width of exit access door, exit door or other exit facilities
a. No exit, exit staircase or other exit facilities shall be narrower than the minimum width requirement as specified under Table 2.2A.
The minimum clear width of an exit door/ exit access opening shall be not less than 850mm.
Effective Date: 1 Mar 2022
E
Explanations & Illustrations
Clause 2.2.7a. : Minimum width of exit access door,
exit door or other exit facilities
Section
Figure 2.2.7a. - 1
Figure 2.2.7a. - 2
Other exit facilities refer to passageways, defined corridors, etc.
Figure 2.2.7a. - 3
In the case of PG I dwelling unit, the minimum width of corridor and access staircase is 900mm. This relaxation is not applicable to all other purpose group buildings.
Figure 2.2.7a. - 4
Clear width of exit door opening shall not be less than 850mm. It shall be measured clear of any protrusion except doorknob or lockset, subject to complying with exit requirements. 850mm is equivalent to 1½ units of width only, for the purpose of determining the exit capacity.
Figure 2.2.7a. - 5
Clear width of corridor leading to an exit shall not be less than 1200m.
Section A-A
Figure 2.2.7a. - 6.
Section
Figure 2.2.7a. - 7
Figure 2.2.7a. - 8
Clear width of exit staircase shall not be less than 1000mm. Please refer to Cl.2.2.9a. for details on measuring of width.
Figure 2.2.7a. - 9
Clear width of internal access staircase in maisonnette unit can be less than 1m but not less than 900mm. This relaxation is only permitted for PG I residential building.
Figure 2.2.7a. - 10
Clear width of internal access staircase in factory unit with mezzanine level office shall not be less than 1000mm. The one-way travel distance from the most remote point of the ancillary office on mezzanine level to the exit door on the main storey level of factory shall not exceed the permissible limits of Table 2.2A.
Amendment History
2.2.7a. |
1 Mar 2022 |
1 Mar 2022 |
Clarification |
No exit, exit staircase or other exit facilities shall be narrower than the minimum width requirement as specified under Table 2.2A. The minimum clear width of an exit door opening shall be not less than 850mm. |
1 Mar 2022 |
Download
|
b. Exit access doors serving a room with an occupant load of not more than two persons shall not be less than 610mm in clear width.
c. A single leaf swing door along the means of egress shall not exceed 1.25m in clear width.
R
Rationale - Clause 2.2.7c
The purpose of controlling the width of single leaf door is to discourage the use of bigger, heavier leaf doors. This is because there is risk of door sagging and thus require more effort to open the door. To overcome it, 2-leaf doors should be used in larger openings instead of single leaf swing door.
2.2.8 Maximum width of exit staircases
R
Rationale - Clause 2.2.8
The purpose of limiting the maximum effective exit capacity of an exit staircase is to prevent concentration of evacuees at any point of the exit. The consequence of permitting exit staircase without capacity limits could be disastrous if that staircase were rendered unusable in an emergency situation. Dividing staircase into segments not wider than 2m enables better crowd control and orderly evacuation in times of emergency.
E
Explanations & Illustrations
Clause 2.2.8 : Maximum width of exit staircases
Figure 2.2.8 - 1
The above sub clause does not preclude the design of staircases wider then 2000mm. It is intended to limit the number of occupants to be allocated to a single exit staircase, and thereby, prevent the concentration of the occupant’s escape at any one point of exit. The consequences, if higher capacity is to be permitted through an exit without capping would be disastrous, if that staircase is to be rendered unusable, in an emergency situation.
Hence, where a staircase is designed with a width greater than 2000mm, its total exit capacity shall be based on the capacity of only 4 units of exit width when determining the adequacy of exit provisions from that storey of building served by that staircase.
This staircase is also required to be sub-divided equally into 2 or more sections with handrails such that the spacing between the handrails are not less than 1000mm and not more than 2000mm.
Axonometric Section
Figure 2.2.8 - 2
Axonometric view
Figure 2.2.8 - 3
The width of staircase of 2500mm is being divided into 2 sections of 1250mm each by the introduction of an intermediate handrail. Although the staircase is 2500mm clear, it is still computed as 2000mm only. Dividing staircase wider than 2000mm enables better crowd control and orderly evacuation in times of emergency.
a. The maximum width of exit staircases shall be not more than 2m. Where staircases exceed 2m in width, handrails shall be used to divide the staircase into sections of width not less than 1m or more than 2m.
b. For the purpose of determining the exit capacity of a staircase that is wider than 2m that forms part of the required means of escape from any storey of the building, that part of its width in excess of 2m shall not be taken into account.
2.2.9 Measurement of width
R
Rationale - Clause 2.2.9
The allowance of 80mm projection of handrail is considered acceptable as the projection would normally occur at the waist-height of a person. Therefore, it is unlikely to affect the egress within a protected staircase.
The measurement of width referred to under Cl.2.2.7 and Cl.2.2.8 shall be the clear width, including the width of plinth to balustrade or parapet wall:
a. For an exit staircase
The clear width shall be measured between:
(1) the finished surfaces of the walls, if the staircase is enclosed on both sides by walls only, or
E
Explanations & Illustrations
Clause 2.2.9a.(1) : Measurement of width
Figure 2.2.9a.(1)
(2) the finished surface of the wall and the inner side of the balustrade, if the staircase has a wall on one side and a balustrade on the other side, or
E
Explanations & Illustrations
Clause 2.2.9a.(2) : Measurement of width
Figure 2.2.9a.(2) - 1
Section
Figure 2.2.9a.(2) - 2
(3) the inner sides of the balustrades if the staircase has balustrades on both sides.
E
Explanations & Illustrations
Clause 2.2.9a.(3) : Measurement of width
Figure 2.2.9a.(3) - 1
Section
Figure 2.2.9a.(3) - 2
If the projection of handrail exceeds 80mm, the clear width shall be measured between the inner sides of the handrails.
Note: The projection of handrail into the clear width of a staircase shall not exceed 80mm on each side of the staircase. If the projection exceeds 80mm, the clear width of the staircase shall be measured from the inner sides of the handrails.
b. For an exit door
E
Explanations & Illustrations
Clause 2.2.9b. : Measurement of width
Figure 2.2.9b. - 1 : Single leaf door
Figure 2.2.9b. - 2 : 2-leaf door
The terminology “2-leaf” is generally known as “multi-leaf” a common term in the building industry. It may comprise of leaf door panels of different sizes. The smaller leaf door may be bolted onto the floor and opened only to facilitate shifting of bulky items. The smaller leaf door if intended to be kept in closed position and not use as escape, it need not be provided with door closer.
Figure 2.2.9b. - 3 : Minimum clear width
Determining the egress width of swinging doors for purposes of calculating capacity, only the clear width of the doorway when the door is open 90 degrees shall be measured. In determining the egress width for other types of doors for purposes of calculating capacity, only the clear width of the doorway when the door is in the full open position shall be measured. Clear width of doorways shall be measured between the face of the door and door frame.
(1) In the case of an exit door having a single leaf door, the opening shall be measured between the edge of the door jamb and the surface of the door when opened at an angle of 90°. See Diagram 2.2.9b..
(2) In the case of a 2 leaf exit door fitted with an approved automatic flush bolt, the clear openings shall be measured between the surface of one leaf to the other door leaf when opened at an angle of 90°.
(3) If one of the door leaves is bolted to the door frame and/ or floor by a manually operated bolt, this door leaf shall not be considered for the purpose of determining the exit capacity of the door. The opening of the other door leaf shall have a clear width of not less than 850mm, measured between the edge of the bolted door leaf and the surface of the other door leaf, when opened at an angle of 90°.
(4) Door hardware and handrails which do not protrude more than 80mm into the clear width of exit opening can be disregarded.
2.2.10 Number of exits from rooms and spaces
There shall be at least two door openings remote from each other which lead to exits from every room or enclosed space in which the total occupant load exceeds the maximum permissible occupant load for one door as listed in the table below:
TABLE 2.2.10 - PERMISSIBLE OCCUPANT LOAD FOR ONE DOOR |
---|
Type of Occupancy | Max. Occupant Load |
---|
High hazard | 25 |
Patient accommodation area | 50 |
Classrooms | 50 |
Godowns, stores, and factories not of high hazard type | 50 |
Assembly | 50 |
Note: (a)
The number and minimum width of exits for rooms and spaces with occupancy of more than
50 persons shall comply with
provisions
in Table 9.7.3a. for assembly occupancy (b)
For residential occupancy, see Cl.9.2 (c)
For healthcare occupancy, see Cl.9.3.2 (d)
For office/shop/factory/warehouse occupancy, see Cl.9.4, Cl.
9.5, Cl.9.6, and Cl.
9.8 (e)
For hotels, see Cl.9.7.2 (f)
For assembly occupancy, see Cl.9.7.3 |
2.2.11 Number of exit staircases or exits per storey
Effective Date: 1 Sep 2024
R
Rationale - Clause 2.2.11
Where possible, occupants should not be denied of alternate egress to an exit staircase. By having minimum two exit staircases, it provides an alternative for occupants to access either. This clause also addresses exit provision for non-habitable roofs and incorporates fixed ladder and access hatches requirements.
E
Explanations & Illustrations
Clause 2.2.11 : Number of exit staircases or exits per storey
Figure 2.2.11
Minimum requirement – 2 exit staircases per storey
Single exit is permissible if the storey of the building can satisfy the conditions stipulated in Cl.2.2.10 and Cl.2.6.
Single staircase provision is permitted for residential buildings under Cl.9.2.1a.(3), Cl.9.2.1a.(4) and commercial/industrial buildings under Cl.9.4.1a., 9.5.1a., 9.6.1a. or, 9.8.1a..
Amendment History
2.2.11 |
|
16 Jun 2016 |
Revised, extracted from SCDF's circular |
|
15 Dec 2015 |
-
|
2.2.11 (dated 25 Aug 2023) |
25 Aug 2023 |
25 Aug 2023 |
Revised/Clarification |
2.2.11 Number of exit staircases or exits per storey
There shall be at least two independent exit staircases or other exits from every storey of a building, unless otherwise permitted under other subsequent provisions of the Code. For non-habitable roof, at least one exit staircase shall be provided. Where the area of non-habitable roof is large and one-way travel distance to the exit cannot be met, an additional cat/ship ladder adequately separated in accordance with Cl.2.3.12 and leading to the circulation area of the floor below shall be provided. All access hatches, if provided, shall be readily accessible from the roof. Access hatch opening shall have a minimum clear width of 1m in diameter. The travel distances can be based on that for a sprinkler protected building for roof areas which are open-to-sky.
For protruding structures above the non-habitable roof, namely exit staircase shaft and lift motor room is exempted from this clause. |
25 Aug 2023 |
Download
|
2.2.11( dated 1 Sep 2024) |
1 Sep 2024 |
1 Sep 2024 |
Relaxation |
2.2.11 Number of exit staircases or exits per storey ……....................................................................... Exception: a. ……. b. ……. c. ……
|
1 Mar 2024 |
Download
|
2.2.11( dated 15 Sep 2020) |
15 Sep 2020 |
15 Sep 2020 |
Clarification |
Number of exit staircases or exits per storey There shall be at least two independent exit staircases or other exits from every storey of a building, unless otherwise permitted under other subsequent provisions of the Code. For non-habitable roof, at least one exit staircase shall be provided. Where the area of non-habitable roof is large and one-way travel distance to the exit cannot be met, an additional cat/ship ladder adequately separated in accordance with Cl.2.3.12 and leading to the circulation area of the floor below shall be provided. All access hatches, if provided, shall be readily accessible from the roof. Access hatch opening shall have a minimum clear width of 1m in diameter. The travel distances can be based on that for a sprinkler-protected building for roof areas which are open-to-sky. |
15 Sep 2020 |
Download
|
There shall be at least two independent exit staircases or other exits from every storey of a building, unless otherwise permitted under other subsequent provisions of the Code.
Exception
a. For non-habitable roof that is able to comply with one-way travel distance, at least one exit staircase shall be provided. The travel distances for roof areas which are open-to-sky shall be based on the requirements for sprinkler-protected buildings.
b. For non-habitable roof that is unable to comply with one-way travel distance to the exit staircase, an additional cat/ ship ladder adequately separated in accordance with Cl.2.3.12 and leading to the circulation area of the floor below shall be provided. All access hatches, if provided, shall be readily accessible from the roof. Access hatch opening shall have a minimum clear width of 1m in diameter. The travel distances for roof areas which are open-to-sky shall be based on the requirements for sprinkler-protected buildings.
c. Roof of the protruding structures above the non-habitable roof, namely exit staircase shafts and lift motor rooms.
d. For green roofs which are accessible for maintenance purposes only, the means of access shall comply with Cl.10.2.1b.(1)(a).
2.2.12 Location of exits & access to exits
Effective Date: 15 Mar 2021
Amendment History
2.2.12b. |
15 Mar 2021 |
15 Mar 2021 |
Revised |
2.2.12b. Every occupant or tenant within a building or storey of a building shall have direct access to the required exit or exits without the need to pass through the spaces or rooms occupied by other occupants or tenants |
15 Sep 2020 |
Download
|
All exits and access facilities shall be required to comply with all of the following:
a. Exits and access facilities shall be clearly visible or their locations shall be clearly indicated and shall be kept readily accessible and unobstructed at all times.
b. Every occupant within a building or storey of a building shall have direct access to the required exit or exits without the need to pass through another room(s) or other tenanted space(s). Where direct access to the required exit or exits of the storey is not possible, occupants shall only be allowed to pass through a maximum of one other room or space belonging to the same tenant with the following conditions being complied with:
(1) the exit access door separating the rooms or spaces which the egress route passes through shall only be fitted with electromechanical device designed in accordance with Cl.2.3.9k.(2);
(2) the doorway of the exit access door shall not be blocked/obstructed and be kept clear at all times.
(3) warning signs of wording “Exit Access Door - Keep Clear” shall be placed prominently on both sides of the exit access door, and
(4) the egress paths through the exit access door shall be suitably demarcated.
Effective Date: 15 Mar 2021
E
Explanations & Illustrations
Clause 2.2.12b. : Location of exits & access to exits
Where any storey of a building is occupied by more than one tenant, it is imperative that each occupant from any of the tenancies shall have direct accessibility to alternate exit staircases without having to enter other tenancies. This could be facilitated via common or neutral spaces like corridors or lobbies that are accessible to all occupants on that storey.
Examples of correct method of determining access travel routes to the required exits:
Figure 2.2.12b. - 1 : Multiple tenancy - each with access to the two exit staircases
Figure 2.2.12b. - 2 : Two tenancies, both with access to two smoke-stop lobbies
Figure 2.2.12b. - 3 : Example of incorrect method of locating exits
The above figure shows an incorrect method of determining access travel routes as the paths have to traverse through other tenancies. Though tenants A and C may have adequate exits, tenants B and D will not be able to meet required exit provisions and hence it would not be allowed.
Figure 2.2.12b. - 4 : Another example of a layout that is NOT acceptable
This arrangement of exits for the separate tenancies is not acceptable because the central door, circled in Figure 2.2.12b. – 4, would be kept locked for security reasons and to prevent or avoid any intrusion from one another. This would render the occupants from that storey with insufficient number of exits for escape in an emergency.
Amendment History
2.2.12b. |
15 Mar 2021 |
15 Mar 2021 |
Revised |
2.2.12b. Every occupant or tenant within a building or storey of a building shall have direct access to the required exit or exits without the need to pass through the spaces or rooms occupied by other occupants or tenants |
15 Sep 2020 |
Download
|
c. When more than one exit is required from any room or space or a storey of a building, each exit shall be placed as remote as possible from the other as permitted under Cl.2.3.12a., b., c. or d..
R
Rationale - Clause 2.2.12c
To reduce the possibility of more than one exit staircase being rendered unusable simultaneously by fire or other emergency situations, the exit staircases are to be remotely located from each other.
E
Explanations & Illustrations
Clause 2.2.12c. : Location of exits & access to exits
Figure 2.2.12c. - 1 : Acceptable locations of exits
The distance between the sides of the two exit doors to the scissor staircases A and B shall be equal to or more than one half the length of the maximum overall diagonal dimension (D) of the lobby, or 7m, whichever is greater. Please refer to Cl.2.3.4 as these are conditions for compliance of scissor staircase.
Permanently fixed ventilation openings in the external walls to the lobby shall not be less than 15% of the lobby floor area and located not more than 9m from any part of the lobby (see Cl.2.2.13b.(7)(a) & (b)).
Figure 2.2.12c. - 2 : Acceptable locations of exits
This method of measurement for unit exit door is only applicable to residential buildings.
Figure 2.2.12c. - 3 : Not acceptable locations of exits
The distance between the sides of two exit doors to the staircases A and B is less than one half the length of the maximum overall diagonal dimension (D) of the lobby.
Figure 2.2.12c. - 4
Distance between exit door to staircase 1 & 2 shall be at least ½ (or ⅓, if sprinkler-protected) the longest diagonal of the building indicated as (D) in the above figure.
One-way travel distance exists where a space is arranged so that occupants within that space are able to travel in only one direction to reach any of the exits or to reach the point at which the occupants have the choice of two-way travel to remote exits.
For example, the portions of the escape routes from points a to b and e to f are one-way travel, which shall not exceed 15m or 25m (sprinkler-protected). The option to travel in another escape route occurs at points b and f, which provide two-way travel distances to the exit staircases 1 & 2 respectively. One-way travel distances are indicated by the dashed lines. See further illustrations under Cl.2.3.12b., c. or d.
2.2.13 Smoke-free approach to exit staircase
Effective Date: 25 Aug 2023
R
Rationale - Clause 2.2.13
The smoke-free approach is intended to act as a buffer space to minimise smoke entry into the exit staircase when used by evacuees and firefighters during a fire emergency.
Entry at every storey level (including 1st storey) to an exit staircase serving more than four storeys above ground level shall be through any one of the following:
a. An external exit passageway or external corridor
The openings for natural ventilation to the corridor shall be located such that they face and are open to any of the following:
E
Explanations & Illustrations
Clause 2.2.13a. : Smoke-free approach to exit staircase
Figure 2.2.13a. - 1
Axonometric Section
Figure 2.2.13a. - 2
Section
Figure 2.2.13a. - 3
External exit passageway is a protected area, which is an extension of the vertical exit staircase. It is used to overcome excessive travel distances as shown in the above figure.
The provision of smoke screen above the passageway before the staircase is to prevent smoke from entering the stairwell at ceiling level.
Main differences between external corridor, smoke-stop lobby and external exit passageway
# | External corridor | Smoke-Stop Lobby | External exit passageway |
---|
Entrance door | No fire rating | At least ½-hr fire rating | At least ½-hr fire rating |
Usage | As smoke-free approach | As smoke-free approach | As extension of the vertical exit (to overcome travel distance deficiency) |
Corridor/lobby – air well ventilation | Min 1.2m high opening Max 3m roof over 1m <parapet wall<1.1m Air well - Min 6m wide / area 93m² | Opening 15% of lobby area Max 9m from opening Air well - min 6m wide / area 93m² | Min 1.2m high opening Max 3m roofed over 1m<Parapet wall <1.1m Comply with Table 1.2.1A if facing air well |
Cross ventilation | Min 1.2m high opening Max 3m roof over | Opening 50% of opposing wall superficial area Max 12m from opening No obstruction | Min 1.2m high opening Max 3m roof over 1m<Parapet wall <1.1m Comply with Table 1.4.2 |
Vent openings btw unit & corridor/smoke-stop lobby | Above 1100mm from finished floor level of corridor | No opening allowed | Above 1800mm from finished floor level of passageway |
Risers | No fire rating for shaft door | Fire rated shaft and doors | No services allowed |
Exposed M&E services (Cl 3.9.6) | Service allowed only if enclosed with fire rated enclosure | No services allowed unless enclosed in 1hr rated enclosure | No services allowed |
It is important that exit staircases are kept free of any smoke at all times, especially in times of a fire emergency, as it is the main essential means for evacuating occupants from the building. To facilitate this smoke free environment, a buffer zone that can quickly dispel any smoke entering it from occupied spaces to the external space is created before entry into the staircases. Hence the passage or route through these areas (or buffer zone) which is relatively free of smoke for safe escape for the occupants and leading to the exit staircases is referred here as the smoke free approach.
Figure 2.2.13a. - 4
Travel Distance measurement, as shown by line AB in Diagram 2.2.13 (a)(iii)-4, in the external corridor situation is taken from any remote point within the occupied area to the exit door of the exit staircase.
External Exit passageway, as shown in Diagrams 2.2.13 (a) – 2 below, is a protected area, which is an extension of the vertical exit staircase. It is used to overcome excessive travel distances.
A smoke screen may be provided above the passageway before the entry into the exit staircase to prevent smoke at the ceiling level from entering the stairwell.
Figure 2.2.13a. - 5 : Approach to exit staircase through external exit passageway
Figure 2.2.13a. - 6
The height of parapet walls of corridors alongside an air-well shall not exceed 1000mm measured from its finished floor level. It shall be noted here that the ventilation openings for exit staircases in the above design layout shall not open into the air-well.
(1) an external space complying with Cl.2.3.11, or
(2) a street, service road or other public space which is open to the sky, or
(3) an air well which opens vertically to the sky and has a minimum width of 6m and a superficial plan area of not less than 93m², except that for external corridors, it shall comply with the requirements of Cl.2.3.10.
b. Smoke-free/ fire lift lobby
E
Explanations & Illustrations
Clause 2.2.13b. : Smoke-free approach to exit staircase
Figure 2.2.13b.
Note : A smoke-free approach (i.e. smoke-stop lobby) is to be provided for entry into the exit staircases, even at 1st storey.
(1) A smoke-free lobby shall be separated from the adjoining areas of the building by a wall having 1-hr fire resistance.
(2) The exit access door shall have ½-hr fire resistance fitted with automatic self-closing device conforming to the requirements of Cl.3.9.2.
(3) The design of a smoke-free lobby shall be such as not to impede movement of occupants through the escape route.
(4) The floor area of a smoke-free lobby shall be at least 3m² and with minimum clear width of 1.2m. If a smoke-free lobby also serves as a fire lift lobby, the floor area shall be not smaller than 6m² and with minimum clear width of 2m.
(5) The floor shall be graded from the lift door towards the lobby door with a fall not exceeding 1 in 200.
(6) A smoke-free lobby, including fire lift lobby, which acts as buffer space for entry into the exit staircase and use by firefighters during emergency, shall be maintained as common property.
(7) A smoke-free lobby shall be ventilated through any of the following:
R
Rationale - Clause 2.2.13b.(7)
Access routes to exits shall be kept smoke-free by a smoke-stop lobby, either naturally or mechanically ventilated, in order to provide a reliable means of escape for occupants and access for firefighters.
(a) Permanent fixed ventilation openings which are located in the external wall of the lobby and have a total area of not less than 15% of the floor area of the lobby.
Each opening shall not be less than 1m2 and shall abut an external space or air well, each having a minimum clear area of 93m2 and minimum width of 6m and without obstruction vertically throughout the airspace for ventilation. No part of the lobby floor area shall be more than 9m away from the air well or external space.
Effective Date: 10 May 2019
R
Rationale - Clause 2.2.13b.(7)(a)
The minimum width of 6m and a superficial plan area of not less than 93m² of an air well have been validated through fire engineering study to provide effective smoke ventilation for a smoke-stop lobby.
E
Explanations & Illustrations
Clause 2.2.13b.(7)(a) : Smoke-free approach to exit staircase
Figure 2.2.13b.(7)(a) - 1
To ensure that every part of the lobby is well ventilated, the distance between the external openings and any part of the lobby should not exceed 9m. In order that the smoke stop lobby can remain an effective buffer to the protected staircase, the former must be a common space, i.e. it should not be part of the apartment unit.
For effective natural ventilation, the smoke-stop lobby shall be within 9m of its ventilation openings. To ensure the integrity of smoke-stop lobby as dedicated buffers protecting exit staircase from smoke infiltration, it must be located in natural spaces. This arrangement would prevent any misuse by tenants, as the case may be if the lobby is to be located within a privately owned space.
Figure 2.2.13b.(7)(a) - 2
For high-rise residential blocks with single exit staircase, the approach to the exit staircase is through a cross-ventilated lobby. See Cl.9.2.1a.(4)(e) & (f) for details the provision of openings to the lobby. To comply with the provision of single exit staircase, designer has to make reference to Cl.9.2.1a.(4) of the Fire Code.
Amendment History
2.2.13b(7)(a) |
10 May 2019 |
10 May 2019 |
Clarification |
Permanent fixed ventilation openings which are located in the external wall of the lobby and have a total area of not less than 15% of the floor area of the lobby.
Each opening shall not be less than 1m2 and shall abut an external space or air well, having a minimum clear area of 93m2 and minimum width of 6m and without obstruction vertically throughout the airspace for ventilation. No part of the lobby floor area shall be more than 9m away from the air well or external space. |
10 May 2019 |
Download
|
(b) Mechanical ventilation, except for PG II buildings, which complies with the requirements in Chapter 7.
E
Explanations & Illustrations
Clause 2.2.13b.(7)(b) : Smoke-free approach to exit staircase
Figure 2.2.13b.(7)(b) : Smoke-stop lobby
(c) Cross-ventilated corridor/lobby which complies with all of the following:
E
Explanations & Illustrations
Clause 2.2.13b.(7)(c) : Smoke-free approach to exit staircase
Figure 2.2.13b.(7)(c) - 1 : Acceptable layout
For the purpose of measuring the horizontal distance of max. 12m from any floor space of the corridor to the ventilation openings, the ventilation openings shall be assumed to be located at the edge of the building and not at the edge of the corridor.
It is important to note that the above requirements shall not be taken to equal other clauses that call for smoke-free approach and cross ventilated lobby approach under Cl.9.2.1a.(4)(e) & (f).
Figure 2.2.13b.(7)(c) - 2 : Acceptable layout
Figure 2.2.13b.(7)(c) - 3 : Not acceptable layout
The above provision of cross-ventilated corridor is not acceptable, as the ventilation opening on one side of the building is narrower than the width of the corridor. This could adversely affect the movement of air currents through the corridor, intended to draw out any smoke in the corridor area before it can affect the staircase.
Figure 2.2.13b.(7)(c) - 4
(i) The corridor/lobby shall have fixed ventilation openings abutting an external space. The ventilation openings shall be located on opposite sides of the corridor/lobby at high level and shall not be less than 50% of the superficial area of the opposing external walls.
(ii) No part of the floor area of the corridor/lobby shall be at a distance of more than 12m from the ventilation openings.
(iii) The distance of 12m can be measured along the internal corridor via the intermediate ventilation opening to the external space, provided there is no unprotected openings in the walls along the path to the external space. The intermediate ventilation opening shall not be less than 2m in width and 1.2m in height and the width of the path to the external space shall not be less than 2m.
Note: For residential buildings of habitable height more than 24m with single exit staircase, the requirements for the cross-ventilated corridor/lobby stipulated in Cl.9.2.1a.(4)(e) shall be complied with.
c. Exception
Effective Date: 25 Aug 2023
(1) The omission of the smoke-free lobby required under Cl.2.2.13b. leading to the exit staircase
of any building exceeding four storeys is allowed under any of the following situations, provided the door opening into the exit staircases shall have 1-hr fire resistance rating and fitted with an automatic self-closing device to comply with the
requirements of Cl.3.9.2:
E
Explanations & Illustrations
Clause 2.2.13c.(1) : Smoke-free approach to exit staircase
Figure 2.2.13c.(1) - 1
Any internal exit staircase with dedicated pressurisation system (without natural ventilation) and its height not exceeding 24m will be permitted without the provision of smoke-stop lobby. The door opening into the staircase is required to have minimum 1-hr fire resistance rating.
The above smoke-stop lobby exemption is not applicable to the exit staircase adjacent to a fire lift and buildings under PG III & VII.
Figure 2.2.13c.(1) - 2
Smoke-stop lobby is exempted if an external exit staircase located along the perimeter wall of the building is required to be cross-ventilated having uninterrupted external openings of minimum 50% of the planal area of the staircase.
The above smoke-stop lobby exemption is not applicable to the exit staircase adjacent to a fire lift and buildings under PG III & VII.
(a) Where the internal exit staircase is provided with pressurisation up to a habitable height of 24m in compliance with the requirements of Chapter 7;
R
Rationale - Clause 2.2.13c.(1)(a)
The positive pressure in the pressurised staircase acts to force smoke away from the doorway of the exit staircase when the exit door is opened, thereby preventing smoke from entering the exit staircase.
(b) Where an external exit staircase is constructed to comply with Cl.2.3.3b.;
R
Rationale - Clause 2.2.13c.(1)(b)
Open sides of an external exit staircase allow for quick dispersal of any smoke infiltrated through the doorway when the door is opened. As such, a smoke-stop lobby before the external exit staircase is not necessary.
(c) In an open-sided car park floor where cross-ventilation is provided in accordance with Cl.3.2.8a. & b., the fire door to the exit staircase can be ½-hr fire-rated.
R
Rationale - Clause 2.2.13c.(1)(c)
The doorway before the exit staircase is unlikely to be smoke logged during a fire emergency. This is because the substantial ventilation openings along the perimeter of the car park allow for quick dispersal of smoke.
(d) On M&E floor of headroom not exceeding 1.5m.
(2) The omission of a smoke-free lobby to exit staircases shall not be allowed under any of the following situations:
E
Explanations & Illustrations
Clause 2.2.13c.(2) : Smoke-free approach to exit staircase
Figure 2.2.13c.(2) - 1
The positive pressure in the pressurised staircase Figure 2.2.13c.(2) - 1 acts to force smoke away from the doorway of the staircase when that exit door is opened, thereby preventing smoke entry into the staircase. The above exemption shall apply to building of which the habitable height does not exceed 24m. This is to meet the requirements under Cl.2.3.3d.(8) and Cl.7.2.1a. which specifically require all internal staircases of building having a habitable height exceeding 24m to be pressurised. If the habitable height of the building exceeds 24m, the entry to the internal exit staircase shall be through smoke-stop lobby or external approach.
Figure 2.2.13c.(2) - 2
In the case of the cross-ventilated staircase (Figure 2.2.13c.(2) - 2), its open sides allow for quick dispersal of any smoke infiltrating the doorway when opened.
Hence, in both these situations, it is possible to achieve a relatively safe smoke free environment in the exit staircase for facilitating escape for its occupants. Another reason to note is that these premises warrant emergency plans and fire drills to familiarise its occupants on their procedural actions in fire emergencies.
Figure 2.2.13c.(2) - 3
Figure 2.2.13c.(2) - 4 : Open-sided multi-storey car park
Section
Figure 2.2.13c.(2) - 5 : Open-sided multi-storey car park
The above requirement exempts the provision of smoke-stop lobby to exit staircases in cross-ventilated car park buildings. In Figure 2.2.13c.(2) - 4, the space before the exit staircases can satisfactorily achieve a smoke free environment. The doors to exit staircases shall be minimum ½-hr fire rated.
Figure 2.2.13c.(2) - 6 : Situation where no exemption is granted -
internal staircase serving building exceeding 24m habitable height
Figure 2.2.13c.(2) - 7 : Situation where no exemption is granted -
when adjacent to a fire lift
No exemption of the smoke-stop lobby will be granted for the exit staircase adjacent to a fire lift. The firefighters would require the lobby space as a ‘staging’ point in their fire fighting operations, prior to entering into the affected areas, in fire emergencies.
(Note: Cl 2.2.13c.(2) is not applicable to buildings under PG VII)
Smoke-stop lobby is exempted for the arrangements shown in Figures 2.2.13(c)(2) – 1 & 2 in buildings of PG II, IV, V, VI & VIII up to 60m high. The reasons for this relaxation being:
Any internal exit staircase without provision for natural ventilation and in habitable height not exceeding 60m will be provided with dedicated pressurization system. The door opening into the staircase is required to have minimum 1-hr fire resistance rating.
Partially enclosed staircase is required to be cross-ventilated having uninterrupted external openings of minimum 50% of the plan area of the staircase.
Section
Figure 2.2.13c.(2) - 8 : Fixed unobstructed ventilation openings
Section
Figure 2.2.13c.(2) - 9
Likewise a cross-ventilated car parking storey in Figure 2.2.13c.(2) - 9 is exempted from the provision of smoke-stop lobby to exit staircase. However, the upper storeys above the car parking floors are not exempted from provision of Cl 2.2.13c.(2).
(a) Where the building exceeds four storeys and belongs to PG III or VII.
(b) Where the internal exit staircase, which is provided with pressurisation, exceeds the habitable height of 24m.
(c) Where the exit staircase is adjacent to a fire lift as required in Chapter 6.
2.2.14 Smoke-free approach to exit staircase in basement
Effective Date: 1 March 2024
R
Rationale - Clause 2.2.14
Access to exits must be free of smoke and be available to building occupants at all times. Therefore, a reliable means of escape for occupants and access for firefighters shall be provided via smoke-free access route and staircases. For this reason, providing mechanical air pressuring systems to smoke-stop lobbies and exit staircases is needed to prevent smoke infiltration.
Amendment History
2.2.14 |
25 Aug 2023 |
1 March 2024 |
Revised/Clarification |
2.2.14 Smoke-free approach to exit staircase in basement
a. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies, one of which shall be designated as a fire lift lobby. The exit staircase connecting to the fire lift lobby shall be pressurised to comply with the requirements in Chapter 7.
b. In a building comprising two, three, or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a smoke-free lobby. Where only one smoke-free lobby is provided, it shall be required to serve as a fire lift lobby.
c. Smoke-free lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7. |
25 Aug 2023 |
Download
|
a. In a building comprising single basement storey, the entry to exit staircases need not be through smoke-free lobbies.
E
Explanations & Illustrations
Clause 2.2.14a. : Smoke-free approach to exit staircase in basement
Figure 2.2.14a.
Smoke-stop lobby is required for all staircases, one of which shall be designated as a fire lift lobby. Owing to the depth of the basement, and to prevent heat and smoke from getting into the staircase, the provision of smoke-stop lobby is required. This is similar to the requirement of smoke-stop lobby to building exceeding 4 storeys above ground. Also refer to Cl.6.6.4b. for the provision of two fire lifts if basement depth exceeds 9m.
Amendment History
2.2.14 |
25 Aug 2023 |
1 March 2024 |
Revised/Clarification |
2.2.14 Smoke-free approach to exit staircase in basement
a. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies, one of which shall be designated as a fire lift lobby. The exit staircase connecting to the fire lift lobby shall be pressurised to comply with the requirements in Chapter 7.
b. In a building comprising two, three, or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a smoke-free lobby. Where only one smoke-free lobby is provided, it shall be required to serve as a fire lift lobby.
c. Smoke-free lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7. |
25 Aug 2023 |
Download
|
b. In a building comprising two, three or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a fire lift lobby even though the exit staircase is not required to be served by a fire lift. However, where the depth of the basement exceeds 9m below the average grade level and fire lifts are required in accordance with Cl.6.6.4b.(3), the entries to the exit staircases with provision of fire lifts at every basement storey level shall be through fire lift lobbies.
E
Explanations & Illustrations
Clause 2.2.14b. : Smoke-free approach to exit staircase in basement
Figure 2.2.14b. - 1 : Plan of basement storey (<9m depth)
Smoke-stop lobby is required for at least one of the staircases. One of which shall be designated as a fire lift lobby.
Figure 2.2.14b. - 2 : Plan of basement storey (=>9m depth)
At least one staircase requires smoke-stop lobby, which shall also be served as fire lift lobby. Also refer to Cl.6.6.4a. & b. which requires two fire lifts and exit staircases to be provided.
Amendment History
2.2.14 |
25 Aug 2023 |
1 March 2024 |
Revised/Clarification |
2.2.14 Smoke-free approach to exit staircase in basement
a. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies, one of which shall be designated as a fire lift lobby. The exit staircase connecting to the fire lift lobby shall be pressurised to comply with the requirements in Chapter 7.
b. In a building comprising two, three, or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a smoke-free lobby. Where only one smoke-free lobby is provided, it shall be required to serve as a fire lift lobby.
c. Smoke-free lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7. |
25 Aug 2023 |
Download
|
c. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies or designated fire lift lobbies in accordance with Cl.6.6.4b.(3).
E
Explanations & Illustrations
Clause 2.2.14a. : Smoke-free approach to exit staircase in basement
Figure 2.2.14a.
Smoke-stop lobby is required for all staircases, one of which shall be designated as a fire lift lobby. Owing to the depth of the basement, and to prevent heat and smoke from getting into the staircase, the provision of smoke-stop lobby is required. This is similar to the requirement of smoke-stop lobby to building exceeding 4 storeys above ground. Also refer to Cl.6.6.4b. for the provision of two fire lifts if basement depth exceeds 9m.
Amendment History
2.2.14 |
25 Aug 2023 |
1 March 2024 |
Revised/Clarification |
2.2.14 Smoke-free approach to exit staircase in basement
a. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies, one of which shall be designated as a fire lift lobby. The exit staircase connecting to the fire lift lobby shall be pressurised to comply with the requirements in Chapter 7.
b. In a building comprising two, three, or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a smoke-free lobby. Where only one smoke-free lobby is provided, it shall be required to serve as a fire lift lobby.
c. Smoke-free lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7. |
25 Aug 2023 |
Download
|
d. Smoke-free and fire lift lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7.
Amendment History
2.2.14 |
25 Aug 2023 |
1 March 2024 |
Revised/Clarification |
2.2.14 Smoke-free approach to exit staircase in basement
a. In a building comprising more than four basement storeys, the entry to exit staircases serving the basement storeys at every basement storey level shall be through smoke-free lobbies, one of which shall be designated as a fire lift lobby. The exit staircase connecting to the fire lift lobby shall be pressurised to comply with the requirements in Chapter 7.
b. In a building comprising two, three, or four basement storeys, entry at every basement storey level to at least one of the exit staircases serving the basement storeys shall be through a smoke-free lobby. Where only one smoke-free lobby is provided, it shall be required to serve as a fire lift lobby.
c. Smoke-free lobbies in basement occupancies shall be required to comply with the relevant provisions under Cl.2.2.13b. and shall be mechanically ventilated to comply with the requirements in Chapter 7. |
25 Aug 2023 |
Download
|
2.2.15 Area of refuge and exit reduction
E
Explanations & Illustrations
Clause 2.2.15 : Area of refuge & exit reduction
( No illustration )
An area of refuge is intended to provide only temporary point of safety to permit delayed egress travel from any level. Therefore, an area of refuge cannot be a room or space whose only access to the building spaces is through the space where the fire is located has been provided. Rather, the area of refuge must provide access to a public way via an exit such as an enclosed exit stair.
See Cl.1.4.9 and Cl.2.2.6e. for illustration.
When a floor area has access to area(s) of refuge in compliance with all of the following requirements in this Clause, the occupant load for which vertical exits are to be accounted for the floor area can be reduced to half when one area of refuge is provided and to one third when two or more areas of refuge are provided.
a. An area of refuge shall be adequate in size to hold the occupant load it receives from the floor area it serves as provision for required exit, in addition to its own occupant load calculated on the basis of 0.3m2 per person except for healthcare
occupancies when the occupant load shall comply with the provisions under Cl.9.3.2b.(4).
b. An area of refuge shall be provided with at least one staircase for use by the occupants to gain access to other exit staircases or the ground level directly to an external space.
c. An area of refuge shall be entered through an external corridor and the room or space or area of refuge shall be separated from the corridor by a wall with at least 1-hr fire resistance rating.
d. External corridors when used as entry into an area of refuge shall conform to the requirements for external exit passageway for minimum width, changes in floor level, roof protection, enclosure on the open side and provision of opening of wall between the room or space and the exit passageway.
e. Exit doors between the room or space or area of refuge and the external corridor shall have fire resistance of at least ½-hr and be fitted with an automatic self-closing device to comply with the requirements of Cl.3.9.2.
f. Every fire compartment in which exit reduction is permitted in connection with area of refuge shall have in addition to exit through the area(s) of refuge at least one exit staircase complying with Cl.2.3.3.