Hotlines
  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

  • Fire Hazard Reporting

    1800 280 0000

  • General Enquiries

    1800 286 5555

  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

Search Fire Code by:

Navigate to:

Legend: Explanations & Illustrations Rationale Note Revision history Print

Clause 7.4 - SMOKE CONTROL SYSTEM

7.4.1 Provision

a. An engineered smoke control system as specified in Cl.7.4.5 shall be provided where:

(1) the requirements for compartmentation specified in Cl.3.2.1, Cl.3.2.4a. and Cl.3.2.4b. are relaxed under the conditions in Cl.3.2.6 for Atrium spaces in a building, or

! Note to QPs on Clause 7.4.1a.(1)

The QPs are required to consult SCDF to seek consent before making any plan submission. The consent that is given by SCDF to allow the use of engineered smoke control system in the proposal shall only relate to the relaxation on the compliance with the above requirements under Cl.3.2.1 and Cl.3.2.4a. and b. of the Fire Code.

(2) the total floor area of any compartment in a building or part of a building exceeds 5000m², or

(3) the total aggregate floor area of all basement storeys exceeds 2000m², except in any of the following situations:

E

(a) Where the basement or a portion of the basement is used as a car park, the car park shall comply with the requirements of Cl.7.4.3, provided it is compartmented from the rest of the basement.

E

(b) Where a plant/equipment room with floor area not exceeding 250m² is compartmented from rest of the basement, two doors remotely located from each other for better reach in firefighting operations shall be provided. The provision of a single door opening for this room is permitted provided the most remote part of the room is less than 8m from the door, and the equipment found inside this room, does not obstruct the throw of a water jet from a firefighting hose.

E

(c) Where a plant/equipment room with floor area exceeds 250m² but not 2000m², and for which smoke vents in accordance with Cl.7.4.2 or smoke purging system of at least 9 air changes per hour are provided.

E

(d) Where a service area comprising storerooms or workshops (restricted to staff only) which are compartmented, which are provided with smoke venting in accordance with Cl.7.4.2, or a smoke purging system of at least 9 air changes per hour in lieu of an engineered smoke control system. An automatic fire alarm/ extinguishing system in accordance with Table 6.4A shall be provided where required.

E

b. A smoke vent in accordance with Cl.7.4.2 shall be provided if the total aggregate floor area of all basement storeys does not exceed 2000m². In lieu of smoke vents, a smoke purging system or an engineered smoke control system is permissible for car parks or other occupancies respectively.

E

7.4.2 Smoke vent

E

Smoke vents shall be adequately distributed along the perimeter of the space served, and its outlets shall be easily accessible during firefighting and rescue operations. Smoke vents shall comply with the following requirements:

a. the number and their sizes shall be such that the aggregate effective vent openings shall not be less than 2.5% of the floor area served;

b. the vent outlets, if covered under normal conditions, shall be openable in case of fire;

c. the position of all vent outlets and the areas they serve shall be suitably indicated adjacent to such outlets;

d. where ducts are required to connect the vent to outlets, the ducts shall either be enclosed in structure or be constructed to give at least 1-hr fire resistance rating; and

e. separate ducts and vent outlets shall be provided for each storey.

7.4.3 Smoke purging system

Smoke purging system, where permitted under this Code in buildings, shall conform to all of the following requirements:

a. The smoke purging system shall be independent of any other system serving other parts of the building.

E

b. The purging system’s purge rate shall be at least 9 air changes per hour.

c. The purging system shall be activated automatically by the building fire alarm system. In addition, a remote manual start-stop switch shall be located at the FCC, or at main fire alarm panel on first storey (where there is no FCC in the building). Visual indication of the operation status of the smoke purging system shall also be provided with this remote control.

d. Supply air shall be drawn directly from the external space and its intake shall not be less than 5m from any exhaust discharge openings. Outlets for the supply air shall be adequately distributed over the area served.

e. Where there is natural ventilation for the area served based upon evenly distributed openings equal to not less than 2.5% of the floor area of a given storey, such natural ventilation can be considered a satisfactory substitute for the supply part of the smoke purging system.

E

f. Replacement air shall be provided and if it is supplied by a separate mechanical system, such a system shall be connected to a secondary power supply.

g. Exhaust ducts shall be fabricated from heavy gauge steel of at least 1.2mm thickness.

h. The exhaust fan shall be capable of operating effectively at 250ºC for 2 hours and be connected to a secondary power supply.

7.4.4 Ductless jet fan system

a. General

This system can be used in lieu of a smoke purging system for conventional car parks where passenger cars/light weight vehicles are parked alongside each other with common driveways. It is not intended for mechanised car park systems or other forms of car parking systems.

b. Provision of sprinkler system

(1) The basement car park shall be sprinkler-protected in accordance with the SS CP 52.

(2) The arrangement of the sprinkler heads and the jet fans shall be such that, upon the operation of the jet fans, the effect on the spray pattern of the sprinklers is minimised.

c. Zoning of car park

(1) All car park spaces shall be divided into smoke control zones with each zone not larger than 2000m2 (excluding plant rooms and circulation spaces) for the purpose of smoke containment and quicker location of fire. A commissioning test will be carried out using hot smoke to demonstrate that smoke can be contained within each zone and channelled to the extract fans.

(2) Each smoke control zone shall have its own jet fan system (fresh air fans, exhaust air fans and jet fans) to purge smoke from the affected zone. The ducts shall be fabricated from heavy steel gauge steel of 1.2mm thickness. Alternatively, sharing of the fresh air and exhaust air fans is permitted provided the fans, wiring and control panel are protected with at least 1-hr fire resistance rating. The exhaust fan system shall also be designed to run in at least two parts, such that the total exhaust capacity does not fall below 100% of the required rate of extract for the zones affected in the event of failure of any one part. This requirement is also applicable for mechanised supply fan system, if it is used.

d. Jet fan system

(1) The jet fan system shall be activated by the sprinkler system serving the basement car park level and any other areas located within the same level. The activation of the jet fan system shall be confined to the smoke control zone on fire and all its adjacent zones. A firefighter cut-off and activation (override) switch shall be provided at the FCC. As an alternative form of fan activation, the use of smoke detectors to activate the jet fan system is allowed, provided:

(a) the detectors are positioned at the effective mid-range of the jet fan profile;

(b) in-duct smoke detector is located at the start point of the exhaust duct; and

(c) jet fan system shall only operate upon activation of two smoke detectors. This is to minimise false alarms.

(2) The jet fan system shall be provided with a secondary source of power supply through automatic operation of an emergency generator in case of failure of the primary power supply source.

(3) The jet fans shall be distributed at a spacing of 2⁄3 of the tested effective range of each jet fan. The tested effective range of the jet fan shall be taken as the distance up to the point at 0.2m/s of the air-velocity distribution profile.

(4) The minimum headroom for the installation of the jet fan system is 3m.

(5) The interaction of the various components of the jet fan system shall be as follows:

(a) Each group of exhaust fans for each smoke control zone shall be interlocked with its corresponding groups of jet fans for that zone.

(b) If the group of exhaust fans stops/fails in any smoke control zone, the corresponding group of jet fans in that zone shall stop. But if any of the exhaust fans is still in operation in a particular smoke control zone, all the jet fans in that zone shall continue to operate.

(c) The exhaust fan shall continue to run even if any corresponding group of jet fans fails.

(d) The other groups of jet fans shall continue to run even if any one group of jet fans fails.

(e) If the fire alarm signal is isolated, the exhaust fans and jet fans shall continue to run at high speed. If the fans are manually restarted, both the exhaust fans and jet fans shall continue to run at high speed until they are set to low speed at the field control panel.

(6) The jet fan system shall be independent of any systems serving other parts of the building.

(7) The jet fan system design shall be such that the bulk air velocity induced by the jet fans is sufficient to stop the advance of the ceiling jet within 5m from the fire location in the direction opposite to the induced bulk air flow.

(8) The smoke control sub-panel in each smoke control zone is to be connected to the main smoke control panel, such that any isolation of jet fan system at a particular zone is automatically displayed at the main smoke control panel.

(9) The car park main smoke control panel at the FCC/Guard house and remote local panel for the supply and exhaust fans shall indicate, by means of indicator lights, whether the fans are on low or high speed. The panels are also required to have the individual group of jet fans indication lights interlocked with the main exhaust fans in the respective smoke control zones.

(10) In the event of failure of the primary source of power supply and subsequent operation of the secondary power supply, the mode of operation of the jet fan system during the fire mode shall follow that prior to the failure of the primary power supply. For example, if the operation of jet fan system in a particular smoke control zone is switched off by the firefighter during fire mode condition and the primary source of power fails, the subsequent operation of the secondary power supply shall be such that the jet fan system remains in the previous fire mode condition, i.e. non-operational mode for that smoke control zone, while the other smoke control zones resume operation.

(11) The jet fan system design shall take into consideration the presence of any down-stand beams and other obstructions that are of depths of more than 1/10 of the car park floor to ceiling height so as to account for any resistance to airflow.

(12) On activation of the jet fan system, the movement of smoke towards the extraction point(s) shall not adversely affect the means of escape and cause smoke to be blown into the lobby area or exit staircases.

(13) The operation of the jet fan system should be such that there are no stagnant areas where smoke can accumulate in the event of fire.

(14) The operation of the jet fan system shall not cause the volume of air movement to be greater than that volume extracted by the main exhaust fans.

e. Wiring arrangement of jet fans

(1) All jet fans shall be connected to the local jet fan control panel in groups of not more than three jet fans.

(2) Each group will be connected by fire-rated cabling.

(3) Each group of jet fans will be protected by a separate MCB (main circuit breaker), with power supply compliant with SS CP 5, to prevent the failure of all the jet fans at once due to tripping of the main RCB, e.g. due to overloading.

(4) The jet fans shall also be wired in a zigzag configuration and no two consecutive jet fans in a straight line are to be wired in the same group. In the event of failure of one group of jet fans, the next corresponding group will be able to drive the smoke towards the exhaust location to be extracted (see Diagram 7.4.4e.(4) - 1 & 2). Should one group of jet fans fail, all other groups shall still continue to run.

(5) The location of the local control panel for the operation of the jet fans within each zone shall be in a relatively safe area within the zone and be spaced as least 5m apart from the local control panels of adjacent zones. This is to minimise the risk of a fire affecting all the control panels if they be spaced closely together, and thus rendering the ineffectiveness of the jet fan system.

f. Provision of supply air

(1) Supply air to the car park can be provided via mechanised supply air fans or by permanent openings of at least 2.5% of the floor area. Whichever is used, the maximum inlet air speed should be 2m/s to prevent recirculation of smoke.

(2) The air velocity within escape routes and ramps shall not exceed 5m/s to prevent escapees from being hindered by the air flow.

(3) The replacement air intakes shall face away from any smoke exhaust points and be sited at least 5m apart so as to prevent recirculation of smoke. If the supply and exhaust louvers are located on the same façade of the building, they shall also be sited at least 5m apart.

(4) The replacement air intake shall be located on the opposing end of the smoke exhaust points so that there is no opposing flow between the supply air and the smoke that is drawn towards the exhaust fan.

g. Exhaust fan design

(1) The car park shall be provided with at least 12 air changes per hour during a fire.

(2) The capacity of the exhaust fan and any associated ducting shall be calculated on the basis that the pressure in the car park close to the extract points is equal to the external atmospheric pressure.

(3) Each smoke control zone of the car park shall have its own exhaust fan system. The exhaust fan system in each zone should be designed to run in at least two parts, such that the total exhaust capacity does not fall below 50% of the required rate of extract in the event of failure of any one part, and that a fault or failure of the exhaust fan system in one zone will not affect the operation of the exhaust fan system in the other zones. The above requirement is also applicable for mechanised supply fan systems, where used. (Note: If there is sharing of the exhaust air fans, see Cl.7.4.4c.(2))

(4) The smoke discharge points shall be located such that the smoke extracted from the smoke exhaust fans does not affect any occupied area or means of escape at the level where smoke is discharged.

h. Fire resistance of jet fan system

The jet fan system, such as the mechanised air supply fans, smoke exhaust fans, jet fans, duct works and wiring shall be capable of operating effectively at 250°C for 2 hours. The fans, ducts and wiring shall be tested in accordance with BS 7346: Pt 2, BS 476: Pt 24 and SS 299 respectively.

7.4.5 Engineered smoke control system

a. Acceptable design guidance

E

The engineered smoke control system shall be in the form of a smoke ventilation system by natural or mechanical extraction designed in accordance with BR 186, BR 258, BR 368 and other acceptable standards:

b. Sprinkler system

R Rationale - Clause 7.4.5b

The main reason that sprinkler system must be provided is to control the fire size. The sprinkler head spacing in respect of both hazard and classification determines the size of a fire, in area and perimeter. The activation of sprinkler heads would, besides controlling the fire size, help to reduce the build-up of heat and toxic gases, which can lead to flashover and smoke explosions. Based on research, if the fire is not sprinkler controlled, the fire size would be unlimited and therefore, fire size could not be established.

A building provided with an engineered smoke control system shall be sprinkler-protected.

c. Fire size

(1) Non-industrial buildings

The capacity of the engineered smoke control system shall be calculated based on the incidence of a likely maximum fire size for a sprinkler controlled fire as recommended in the following table:

TABLE 7.4.5c.(1) : FIRE SIZE FOR NON- INDUSTRIAL BUILDINGS
Occupancy (Sprinkler-protected)Fire Size
Heat Output (MW)Perimeter of Fire (m)
Shops512
Offices114
Hotel Guest Room0.56
Hotel Piublic Areas2.512
Assembly Occupancy with Fixed Seating2.512

(2) Industrial buildings

The requirements for design fire size are applicable to sprinkler- protected industrial premises (factory and warehouse) without in-rack sprinklers and limited to the design of smoke control system based on Cl.7.4.

(a) Fire growth

The fire growth can be evaluated by the following generic fire growth curve (also referred to as ‘t2 fire’), that represents the general types of combustible material present within an enclosure:

 

Qmax = ∝ (t-ti)2 ------------------------------------- equation (1)
where:
Qmax = heat release rate (kW);
∝ = fire growth parameter (kJ/s3);
t = time (s);
ti = time of ignition (s) (taken here as zero)

The fire growth parameter varies with the fire load density and the fire load configuration factor. However, for purpose of design, fire growth parameter can be generally defined as follows:

TABLE 7.4.5c.(2)(A) : FIRE GROWTH PARAMETER FOR INDUSTRIAL BUILDINGS
Fire growth rateFire growth parameter (kJ/s3)Time for Qg = 1MW (s)
Slow0.0029600
Medium0.012300
Fast0.047150
Ultra fast0.18875

Note:

The fire growth rate that is applicable through available literature or standard such as the SFPE Handbook shall be adopted. In the instance where the fire growth rate lies in between the range as stated above, the more conservative fire growth rate is to be used.

(b) Design fire – sprinkler-protected

(i) The heat output of the design fire is assumed to increase according to equation (1) until sprinkler operation is deemed to occur at time t8. Following sprinkler operation, the heat output of the fire is considered to remain constant.

(ii) The capacity of the smoke control system shall be based on the fire size that is controlled by activation of 2nd ring of sprinklers.

(iii) The operation of the sprinkler system at ts and the corresponding fire size can be determined by hand calculations based on fire engineering principles or the use of fire engineering tools such as FPETool from National Institute of Standards and Technology (NIST). Whichever approach is used, the following design factors governing its calculation are as follows:

• Rate of fire growth
The type of fuel load and its configuration in the premises shall govern the rate of fire growth which can be represented using equation (1) and Table 7.4.5c.(2)(a).

• Sprinkler response time index (RTI)
The RTI is the thermal sensitivity of the sprinkler and shall be based on the manufacturer’s specification.
Example:
Standard response sprinkler – 105m0.5s0.5;
Fast response sprinkler - 50m 0.5s0.5;
ESFR - 26m0.5s0.5

• Temperature rating of sprinkler
The operating temperature of the sprinklers shall be based on SS CP 52 (e.g. 141°C or 68°C).

• Ambient temperature
Room temperature for air-conditioned spaces and non-air conditioned spaces can be taken as 25°C and 30°C respectively.

• Ceiling height
The ceiling height shall be based on the height, measured from the finished floor level to the soffit of the ceiling/roof.

• Spacing of sprinkler above fire
Sprinkler spacing shall be based on SS CP 52 (e.g. 3m by 3m or 4m x 3m).

Note: The application of FPETool from NIST or any other software in determining the activation time of the sprinkler system and the corresponding fire size has its limitations. Some of the software programs are based on Alpert’s correlations where a number of fundamental assumptions are made such as flat smooth ceilings, unconfined smoke flow, axisymmetric plumes (not near walls or corners), location of detector close to the ceiling, etc.. Such assumptions shall thus be taken into consideration when using this tool.

(iv) The capacity of the smoke control system shall also take into consideration the possibility of forklift or general goods vehicle on fire along the internal ramps/driveways. For design purposes, the design fire size shall be taken as follows:

TABLE 7.4.5c.(2)(b)(iv) : VEHICLE DESIGN FIRE SIZE
Type of vehicleDesign fire size
Forklift or car4MW
General goods vehicle10MW

(c) Determination of perimeter of fire

(i) Fire perimeter for forklift/car and goods vehicle

The fire perimeter is used to determine the mass flow rate of smoke. For forklift or general goods vehicle, the perimeter of fire shall be taken as follows:

TABLE 7.4.5C.(2)(C)(I) : FIRE PERIMETER SIZE Type of vehicle Perimeter of fire Forklift or car 5m x 2m General goods vehicle 9m x 2.5m

TABLE 7.4.5c.(2)(C)(I) : FIRE PERIMETER SIZE
Type of vehiclePerimeter of fire
Forklift or car5m x 2m
General goods vehicle9m x 2.5m

(ii) Fire perimeter other than for forklift/car and general goods vehicle

Other than for forklift/car and general goods vehicle, the following equation is used to calculate the fire perimeter for a square fire of equal sides:

P = 4(Qc/Qr)0.5 -------------------------------- equation (2)
where:
P = fire perimeter (m);
Qc = convective heat output = 0.7Qmax (kW);
Qr = heat release rate per unit area (kW/m2), see Table 7.4.5c.(2)(c)(ii)

Where elongated storage configurations such as racking or shelving are used, the fire perimeter is determined using the following equation:

P = 2[Qc/(Qr x d)] --------------------------- equation (3)
where:
Qc = convective heat output = 0.7Qmax (kW);
Qr = heat release rate per unit area (kW/m2), see Table 7.4.5c.(2)(c)(ii)
d = depth of rack (m)

For purpose of calculating the fire perimeter, the values for Qr given in Table 7.4.5c.(2)(c)(ii) are used.

TABLE 7.4.5c.(2)(C)(II) : HEAT RELEASE RATE
Building UseHeat release rate per unit area, Qr (kW/m2)
Industrial260
Storage500

d. Capacity

E

The capacity of an engineered smoke control system shall be capable of handling the demand for smoke exhaust in a worst case scenario.

e. Clear layer

E

The design smoke layer base shall be above the heads of people escaping beneath it. The minimum height shall be 2.5m.

f. Smoke reservoir

(1) Smoke reservoirs to prevent the lateral spread of smoke, and to collect smoke for removal, shall be of non-combustible construction capable of withstanding smoke temperatures.

E

(2) For cases where smoke is removed from the room of origin, the smoke reservoir size for a smoke ventilation system shall not exceed:

E

(a) 2000m² for a natural smoke ventilation system; and

(b) 2600m² for a mechanical smoke ventilation system.

(3) For cases where smoke is removed from a circulation space or atrium space, the smoke reservoir size for a smoke ventilation system shall not exceed:

E

(a) 1000m² for a natural smoke ventilation system; and

(b) 1300m² for a mechanical smoke ventilation system.

(4) Reservoir length

E

The maximum length of the smoke reservoir shall not exceed 60m.

(5) Stagnant regions

E

Adequate arrangement(s) shall be made in each smoke reservoir for the removal of smoke in a way that will prevent the formation of stagnant regions.

(6) Perforated ceiling

E

For cases where the smoke reservoir is above the false ceiling, the ceiling shall be of perforated type with at least 25% opening.

g. Discharge of smoke

For cases where smoke is removed from a circulation space or atrium space, the rooms discharging smoke into the circulation space/atrium spaces shall either:

(1) have a floor area of not exceeding 1000m² (for natural ventilation system) or 1300m² (for mechanical ventilation system), or

E

(2) be subdivided such that smoke is vented to the circulation space or atrium only from part of the room with floor area not exceeding 1000m² (for natural ventilation system) or 1300m² (for mechanical ventilation system), that is adjacent to the circulation space or atrium. However, the remainder of the room needs to be provided with an independent smoke ventilation system(s).

E

h. Limitations

E

Owing to practical limitations, a smoke ventilation system shall have:

(1) a maximum mass flow not exceeding 175kg/s; and

(2) a minimum smoke layer temperature of 18°C above ambient temperature.

i. Replacement air

E

(1) Replacement air shall by natural means be drawn directly from the external space.

(2) The design replacement air discharge velocity shall not exceed 5m/s to prevent the escapees being hindered by the air flow.

(3) Replacement air intake shall be sited at least 5m away from any exhaust air discharge.

(4) Replacement air shall be discharged at a low level, at least 1.5m beneath the designed smoke layer, to prevent fogging up of the lower clear zone.

(5) Where the inlet cannot be sited at least 1.5m below the smoke layer, a smoke curtain or a barrier shall be used to prevent replacement air disrupting the smoke layer.

(6) Where replacement air is taken through inlet air ventilators or door- ways, devices shall be incorporated to automatically open such inlet ventilators and doors to admit replacement air upon activation of the smoke ventilation system.

(7) Where the automatic roller shutters are used at replacement air inlets in the design and installation of an engineered smoke control system, it shall be of perforated type having the required effective free area for the effective operation of the engineered smoke control system.

j. Emergency power supply

E

The engineered smoke ventilation system shall be provided with secondary source of power supply.

k. Mode of activation

(1) Automatic activation

(a) The engineered smoke ventilation system shall be activated by smoke detectors located in the smoke control zone. Use of smoke detectors for activation shall be carefully designed, so that accidental or premature activation of smoke detectors in a non- fire zone (due to smoke spills or spread from other areas) are avoided.

E

(b) Provision of activating smoke detectors shall comply with SS CP 10.

E

(2) Manual activation

R Rationale - Clause 7.4.5k.(2)

The provision of remote manual activation and control switches located at Fire Command Centre or Fire Alarm Panel would permit better controlling of the smoke ventilation system.

In the event of the smoke detectors malfunctioning, the atrium smoke extract system can be activated by a manual switch, which performs the function of the smoke detectors in actuating the associated devices for the isolation and extraction of the smoke from the affected areas.

A remote manual activation and control switches, as well as visual indication of the operation status of the smoke ventilation system, shall also be provided at the FCC. Where there is no FCC, it shall be indicated at the main fire alarm panel.

l. Interlocking with other ACMV systems

E

Except for ventilation systems in Cl.5.2.1g. and Cl.5.2.1h., all other air-conditioning and mechanical ventilation systems within the areas served shall be shut down automatically upon activation of the smoke ventilation system.

m. Standby fans/ multiple fans

(1) Either a standby fan or multiple fans with excess capacity shall be provided for each mechanical smoke ventilation system, such that in the event the duty fan or the largest capacity fan fails, the required smoke extraction rate will still be met. The standby fan shall be automatically activated in the event the duty fan fails.

E

(2) Fans shall be capable of operating at 250°C for 2 hours.

(3) Protected circuits

R Rationale - Clause 7.4.5m.(3)

Since the smoke control system is installed to remove smoke and heat from the building to aid evacuation of occupants and firefighting operations, the system’s circuits shall be protected to ensure operational reliability and sustained operation during fire emergency.

The fans and associated smoke control equipment shall be wired in protected circuits designed to ensure continued operation in the event of fire.

(4) Electrical supply

R Rationale - Clause 7.4.5m.(4)

The main purpose is to ensure that the electrical supply to the fans could be maintained continuously for at least 1 hour.

The electrical supply to the fans shall, in each case, be connected to a sub-main circuit exclusive thereto after the main isolator of the building. The cables shall be of at least 1-hr fire resistance rating in accordance with SS 299.

n. Smoke ventilation ducts

(1) Smoke ventilation ducts (both exhaust and replacement air ducts) shall be of at least 1-hr fire resistance rating. The rating shall apply to fire exposure from both the interior and exterior of the duct or structure and the duct shall also comply with Cl.7.1.2h..

(2) Where a duct passes through another fire compartment with higher fire rating, the duct shall be constructed to have fire-rating as that of the compartment. Where a duct is installed in a single fire compartment and does not pass through another compartment, smoke control ducts (both exhaust and replacement air ducts) within that compartment need not comply with the 1-hr fire resistance rating requirement subject to the following conditions:

(a) the smoke ventilation ducts (both exhaust and replacement air ducts) are constructed of at least 1.2mm thick galvanised steel sheet;

(b) sprinklers, designed to SS CP 52, shall be provided above and below the entire length of the ducts (regardless of the duct dimensions) to protect the duct surfaces from the effect of water spray through the activated sprinklers; and

(c) the construction and support of the duct shall conform to the appropriate requirements of the duct construction standards contained in ASHRAE Handbook, IHVE Guild books or SMACNA Manuals.

o. Fire damper

(1) Fire dampers shall not be fitted in the smoke ventilation system, except where used in an engineered smoke control system. In such a situation, a combination of fire and smoke dampers shall be constructed in accordance with SS 333, and its electric actuator shall be tested in accordance with the requirements of UL 555S for at least 2 hours at 250ºC.

(2) The damper shall be in closed position during fail-safe mode.

(3) The combination fire and smoke damper, and any duct extension between it and the protected vent shaft, shall be of the same rating as the element of structure.

(4) Sprinkler protection shall be provided to the electric actuator.

(5) The electrical power supply cables to the electric actuator shall be fire resistant.

p. The time taken for a smoke ventilation system within a smoke zone to be fully operational shall not exceed 60 secs from the time of activation.

q. Fail-safe system

E

For natural smoke ventilation system, the natural ventilators shall be-

(1) in the “open” position in the event of power/system failure; and

(2) positioned such that they will not be adversely affected by positive wind pressure.

r. Natural ventilation shall not be used together with mechanical ventilation.

E

s. Smoke curtain

R Rationale - Clause 7.4.5s

The intent of the smoke curtain is to contain the smoke and to prevent spillage of smoke to other areas.

All smoke curtains, where required, unless permanently fixed in-position, shall be brought into position automatically to provide adequate smoke-tightness and effective depth.

t. Obstruction to means of escape

E

A smoke curtain, or other smoke barrier, located at any access route forming part of or leading to a means of escape, shall not in its operational position obstruct said escape route.

u. Smoke or chanelling screens

E

Where glass walls or panels are being used as smoke screens to form a smoke reservoir or as channelling screens, they shall be able to withstand the design highest temperature.

v. All smoke control equipment (including smoke curtains) shall be supplied and installed in accordance with BS EN 12101-1, BS EN 12101-3 and BS 7346 Pt 7 or equivalent.

E