Maintenance Notice: The SCDF website will be undergoing a system upgrade on 15 October 2026, from 7pm to 10pm. Users may experience intermittent downtime during this period. We apologise in advance for any inconvenience caused.
Please be informed that Alexandra Fire Station will not be hosting the weekly Saturday Fire Station Open House on 17 October 2026. Please refer to the list of other Fire Stations that are available for visits.
Government officials will NEVER ask you to transfer money or disclose bank log-in details over a phone call. Call the 24/7 ScamShield Helpline at 1799 if you are unsure if something is a scam. For details, visit the ScamShield website.
Please be informed that Yishun Fire Station will not be hosting the weekly Saturday Fire Station Open House from 28 February 2026 to March 2028. Please refer to the list of other Fire Stations that are available for visits.
SCDF does not endorse or certify products. Legitimate fire safety products are certified by independent accredited Certification Bodies. Claims of 'SCDF-approved' or similar are false. Report them at https://www.scdf.gov.sg/home/feedback.
The application for Registered Inspector (RI) is open from 1 Nov to 30 Nov 2026. Please download the application form at https://www.scdf.gov.sg/fire-safety-services-listing/downloads/forms-and-guides.

1

/

6

Search TRSS
Include in Search
Clear All
3.4.1 Member Dimensions

The minimum member size of SS and NS shall be as stipulated in Chapter 2 - Architectural Design.

3.4.2 Reinforcement Requirements

All diameters of reinforcement specified hereinafter shall refer to minimum fabric mesh or bar diameters. All spacing of reinforcement specified hereinafter shall refer to maximum spacing of reinforcement in both directions.

3.4.2.1 Wall Reinforcements of SS and NS

a. Minimum Reinforcement in SS or NS walls - refer to TABLE 3.4.2.1.

b. Reinforcements at both faces of the internal common wall shall be H10-100 c/c in both faces. The shear links shall be H8-600 c/c in both directions.

c. Shielding wall in front of SS door:

Reinforcements at both faces of the wall shall be minimum H10-200 c/c. The shear link with L-bend at two ends shall be H8 at 600 c/c in both directions.

3.4.2.2 Reinforcements of SS and NS slabs

a. Intermediate SS/NS slabs and slabs/waists of staircase SS/NS:

Top and bottom layer of slab reinforcements shall be H10-100 c/c in both directions. The shear links shall be H8-600 c/c in both directions.

b. Ceiling slab of top-most SS:

i. Reinforcements at both external face and internal face of the slab shall be H13- 100 c/c (both directions).

ii. The shear links shall be H8-600 c/c in both directions.

c. Floor slab of bottom-most SS or NS and floor slab of NS located above a SS:

i. Slab reinforcements at both external face and internal face shall be H13-100 c/c (both directions).

ii. The shear links shall be H8-600 c/c in both directions.

d. Ceiling slab outside the SS tower which is immediately above SS door:

The minimum ceiling slab shall be constructed of 150mm thick reinforced concrete. The reinforcement shall consist of two layers of reinforcement (top and bottom) at H10-100 c/c in both directions. These top and bottom layers of reinforcement bars shall be continuous or anchored to the slab of SS with tension anchorage length.

e. Floor slab outside SS tower:

The reinforcements of every floor slab immediately outside SS tower walls shall be structurally connected to the SS tower.

f. SS slab which is integrated with pile-cap/footing:

For SS slab integrated with the pile-cap or footing of 500mm thick or more, shear links is not required. The maximum spacing of main reinforcement shall be 200mm c/c.