Maintenance Notice: The SCDF website will be undergoing a system upgrade on 15 October 2026, from 7pm to 10pm. Users may experience intermittent downtime during this period. We apologise in advance for any inconvenience caused.
Please be informed that Alexandra Fire Station will not be hosting the weekly Saturday Fire Station Open House on 17 October 2026. Please refer to the list of other Fire Stations that are available for visits.
Government officials will NEVER ask you to transfer money or disclose bank log-in details over a phone call. Call the 24/7 ScamShield Helpline at 1799 if you are unsure if something is a scam. For details, visit the ScamShield website.
Please be informed that Yishun Fire Station will not be hosting the weekly Saturday Fire Station Open House from 28 February 2026 to March 2028. Please refer to the list of other Fire Stations that are available for visits.
SCDF does not endorse or certify products. Legitimate fire safety products are certified by independent accredited Certification Bodies. Claims of 'SCDF-approved' or similar are false. Report them at https://www.scdf.gov.sg/home/feedback.
The application for Registered Inspector (RI) is open from 1 Nov to 30 Nov 2026. Please download the application form at https://www.scdf.gov.sg/fire-safety-services-listing/downloads/forms-and-guides.

1

/

6

Search CPFPRTS
Include in Search
Clear All

3.13.1 Requirements for Class 0

Any reference to a surface being Class 0 shall be construed as a requirement that:

a. the material of which the wall or ceiling is constructed shall be non-combustible throughout, or

b. The surface material (or, if it is bonded throughout to a substrate, the surface material in conjunction with the substrate) shall have a surface of Class 1 when tested to BS 476: Part 7 and if tested in accordance with BS 476: Part 6 shall have an index of performance (I) not exceeding 12 and a sub-index (i1) not exceeding 6.

3.13.2 Requirements for a class other than Class 0 classification

Any reference to a surface being of a class other than Class 0 shall be taken as complying with the relevant test criteria as to surface spread of flame specified in relation to that class in BS 476: Part 7.

3.13.3 Classification

Class 0 shall be regarded as the highest class followed by Class 1 as set hereunder:

a. Class 0 - Surface of no flame spread. Such surfaces shall conform to the requirements of Cl.3.13.1.

b. Class 1 - Surface of very low flame spread. This refers to surfaces on which during the first 1½ mins of test, the spread of flame does not exceed 165mm and the final spread of flame does not exceed 165mm under the relevant test conditions.