Maintenance Notice: The SCDF website will be undergoing a system upgrade on 15 October 2026, from 7pm to 10pm. Users may experience intermittent downtime during this period. We apologise in advance for any inconvenience caused.
Please be informed that Alexandra Fire Station will not be hosting the weekly Saturday Fire Station Open House on 17 October 2026. Please refer to the list of other Fire Stations that are available for visits.
Government officials will NEVER ask you to transfer money or disclose bank log-in details over a phone call. Call the 24/7 ScamShield Helpline at 1799 if you are unsure if something is a scam. For details, visit the ScamShield website.
Please be informed that Yishun Fire Station will not be hosting the weekly Saturday Fire Station Open House from 28 February 2026 to March 2028. Please refer to the list of other Fire Stations that are available for visits.
SCDF does not endorse or certify products. Legitimate fire safety products are certified by independent accredited Certification Bodies. Claims of 'SCDF-approved' or similar are false. Report them at https://www.scdf.gov.sg/home/feedback.
The application for Registered Inspector (RI) is open from 1 Nov to 30 Nov 2026. Please download the application form at https://www.scdf.gov.sg/fire-safety-services-listing/downloads/forms-and-guides.

1

/

6

Search CPFPRTS
Include in Search
Clear All

3.12.1 General provision

Openings for pipes, ducts, conduits or cables which pass through any part of an element of structure (except for a part which does not serve as a fire resisting barrier) or cavity barrier, shall be:

a. kept as few in number as possible;

b. kept as small as practicable; and

c. all gaps shall be filled with fire-stopping materials.

3.12.2 Fire-stopping

Fire-stopping shall be of material having the necessary fire resistance when tested to BS 476: Part 20 or other acceptable standards.

3.12.3 Materials for fire-stopping

Suitable fire-stopping materials include:

a. Proprietary fire-stopping and sealing systems (including those designed for service penetrations) which have been shown under test conditions to maintain the fire resistance of the wall or other element, shall be in accordance with the Code of Practice for Fire Precautions in Buildings, except where herein modified in this Code.

b. Other fire-stopping materials include:

(1) cement mortar;

(2) gypsum based plaster;

(3) cement or gypsum based vermiculite/ perlite mixes;

(4) glass fibre, crushed rock, blast furnace slag or ceramic based products (with or without resin binders); and

(5) intumescent mastics.

The method of fire-stopping and choice of materials shall be appropriate to the situation and its application.