Please be informed that Ang Mo Kio Fire Station will not be hosting the weekly Saturday Fire Station Open House on 19 September 2026. Please refer to the list of other Fire Stations that are available for visits.
Please be informed that Yishun Fire Station will not be hosting the weekly Saturday Fire Station Open House from 28 February 2026 to March 2028. Please refer to the list of other Fire Stations that are available for visits.
Government officials will NEVER ask you to transfer money or disclose bank log-in details over a phone call. Call the 24/7 ScamShield Helpline at 1799 if you are unsure if something is a scam. For details, visit the ScamShield website.
SCDF does not endorse or certify products. Legitimate fire safety products are certified by independent accredited Certification Bodies. Claims of 'SCDF-approved' or similar are false. Report them at https://www.scdf.gov.sg/home/feedback
Please be informed that Central Fire Station will not be hosting the weekly Saturday Fire Station Open House on 10 October 2026. Please refer to the list of other Fire Stations that are available for visits.
Please be informed that Marina Bay Fire Station will not be hosting the weekly Saturday Fire Station Open House until further notice. Please refer to the list of other Fire Stations that are available for visits.

1

/

6

Search CPFPRTS
Include in Search
Clear All
8.5.1 Location and plan details

Two paper sets of plans shall be kept next to the main alarm panel in a dedicated plan box marked “STATION LAYOUT PLANS FOR FIREFIGHTERS” to help firefighters to navigate in the station. The plans shall:

a. minimally be of A3 size;

b. be without gridlines;

c. have spaces clearly annotated;

d. indicate the fire lift, firefighting staircase, exit staircase, fire lift lobbies, smoke-free lobbies, fire pump room, landing valves, Two-way Emergency Voice Communication handsets, and firefighters’ intercoms in red; and

e. be updated and in good condition at all times.

8.5.2 Plan Box

A locked glass-fronted plan box constructed of non-combustible material shall be provided and firmly mounted on wall. The key shall be kept in a glass-fronted box alongside the plan box or as part of the plan box. Signage complying with SS 508 shall be provided to read “IN CASE OF EMERGENCY, BREAK GLASS FOR KEYS”. A spare key shall be kept in the PSC.