Hydrant obstructed by fencing
Hydrant obstructed by car park lot
Hydrant obstructed by bollards
Hydrants obstructed by plantation and fences
Hydrant obstructed
Hydrant obstructed by railings
Hydrant obstructed by metal railing
Hydrant installed along fire engine access way not protected
Private hydrant without 100mm thick yellow band
Hydrant key unable to turn due to edge obstructing
Hydrant pit cover sealed up
Round hydrant pit cover not acceptable
Incorrect layout of hydrant and pit cover
Landing valve, hose reel and standby hose located too close to each other
Rising main not compartmented
Breeching inlet obstructed by car park lot and rack
Dry rising main inlet door obstructed when opened
Breeching inlet not readily accessible
Improper location of breeching inlet
Breeching inlet obstructed by plantation
Inaccessible breeching inlet
Dry rising main inlet obstructed by column
Minimum nominal bore of drying rising main was less than 100mm
Wet rising main inlet painted yellow colour instead of red
Missing signage for type of breeching inlet eg. dry rising main breeching inlet
Missing signage for sprinkler or rising main in breeching inlet
Glass-fronted inlet box not provided for breeching inlet
Missing signage for breeching inlet
Missing glass-fronted inlet box
Inappropriate signage for dry rising main, hose reel, breeching inlet
Breeching inlet labelling incomplete wording eg. sprinkler rising main breeching inlet
Missing drain valve for rising main
Obstructed landing valve
Rising main landing valve obstructed
Insufficient height for landing valve
Missing handwheel on landing valve
Incorrect color for drying rising main inlet
Stop valve for testing installed at air release valve
Insufficient clearance for air release valve
Air release valve not installed at topmost stack of rising main
Hose reel not located adjacent to exits
Hose reel cabinet door lock used not the type operated manually from inside when tempered glass is removed
Recess door for hose reel unable to open 180'
Hosereel obstructed by car park lot
Hose reel compartment door without handle and instruction notice to open door
Inappropriate signage for hosereel
Hose reel without full operating instruction notice
Dry rising main landing valve height less than the required 760mm from floor level