Hotlines
  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

  • Fire Hazard Reporting

    1800 280 0000

  • General Enquiries

    1800 286 5555

  • 995

    Fire Engine/ Ambulance

  • 1777

    Non-Emergency Ambulance

Registered inspector fire safety handbook

CP 52 - Automatic Sprinkler Systems

  • Fire Safety Non-Compliance

    Royal flush sprinkler head with cover plate painted over

  • Fire Safety Non-Compliance

    Sprinkler gong not working when sprinkler activated

  • Fire Safety Non-Compliance

    Sprinkler breeching inlet installed next to bin centre

  • Fire Safety Non-Compliance

    Incorrect sprinkler water effective capacity labelled

  • Fire Safety Non-Compliance

    Faulty indicator for sprinkler pump status

  • Fire Safety Non-Compliance

    Sprinkler water proofing test failed

  • Fire Safety Non-Compliance

    Existing under duct sprinkler being obstructed by new air con supply duct put up during tenancy A/A work

  • Fire Safety Non-Compliance

    Royal flush sprinkler head with cover plate missing & obstructing the deflector

  • Fire Safety Non-Compliance

    Sprinkler head located too closed to exit sign

  • Fire Safety Non-Compliance

    Sprinkler head obstructed by pipe works

  • Fire Safety Non-Compliance

    Sprinkler head obstructed duct work

  • Fire Safety Non-Compliance

    Sprinkler in car park being obstructed by pipes running below

  • Fire Safety Non-Compliance

    Sprinkler head obstructed by electrical services

  • Fire Safety Non-Compliance

    Sprinkler control valve not adjacent to FCC, fire fighting lobby or protected area where it is readily accessible from the common area

  • Fire Safety Non-Compliance

    Insufficient sprinkler coverage for concealed space in ceiling

  • Fire Safety Non-Compliance

    Sprinkler protection not provided at top/bottom of lift shaft

  • Fire Safety Non-Compliance

    Under duct sprinkler not under or below duct and obstructed

  • Fire Safety Non-Compliance

    Under duct sprinkler not provided for rectangular duct width more than 800mm and circular duct more than 1000mm

  • Fire Safety Non-Compliance

    Incorrect sprinkler rating installed in kitchen

  • Fire Safety Non-Compliance

    Sprinkler control valve obstructed by plantation

  • Fire Safety Non-Compliance

    Sprinkler control valve obstructed by car park lot

  • Fire Safety Non-Compliance

    Sprinkler control valve not protected

  • Fire Safety Non-Compliance

    Sprinkler control valve installed next to switch room and bin centre

  • Fire Safety Non-Compliance

    Sprinkler pump not provided with certification body's label

  • Fire Safety Non-Compliance

    Sprinkler design chart not provided