Lounge not compartmented with fire door and wall from hotel corridor
Fire Safety Requirements Clause 3.2.5
Occupied space not compartmented from car park
FCC not fully compartmented
Store room (exceeding 10m2) not compartmented
FCC not compartmented
Electrical socket installed on fire-rated partition
Fire Safety Requirements Clause 3.3.7
Non-compliance of Fire Code for external wall cladding (invalid or no COC)
Fire Safety Requirements Clause 3.5.4
Lift located within an exit staircase
Fire Safety Requirements Clause 3.7.1
Compartment wall not full height
Under alarm activation mode, fire shutter unable to close due to decorative board obstructing it
Fire Safety Requirements Clause 3.7.9
Under alarm activation mode, fire shutter unable to close completely
Electrical services sharing same shaft as fire fighting equipment
Fire Safety Requirements Clause 3.8
Electrical services inside protected staircase
Fire Safety Requirements Clause 3.8.1
Electrical services serving other areas passing through staircase
Fire Safety Requirements Clause 3.8.7
Electrical socket installed in fire fighting lobby
Electrical socket installed in staircase
Damaged fire-rated enclosure for M&E servicecs
Fire Safety Requirements Clause 3.8.9
Incomplete fire-rated enclosure for service pipes
M&E services labelling not provided on fire-rated enclosure
Fire-rated door without door closer installed
Fire Safety Requirements Clause 3.9.2
Electrical services passing through protected staircase
Wall between units and covered car park area not compartmented
Fire Safety Requirements Clause 3.12.1
Services penetrating through compartment walls and floors not fire-stopped
Combustible materials used for decorating fire fighting lobby
Fire Safety Requirements Clause 3.15
Glass door installed in protected staircase
Fire Safety Requirements Clause 3.15.13