Definition of Minor A&A |
|
| |
Lodgement Of Minor Addition / Alteration Works (Minor A&A) |
|
| |
Minor Addition / Alteration to fire safety works refers to the
erection or delection of internal partitions (including alteration
to fire protection system). The erection of internal partitions
should only involve materials of lightweight non-combustible construction
and must not affect the fire compartmentation and means of escape
provisions, or pose additional fire hazard to the building. |
|
| |
|
|
| |
Minor additions / alterations to fire safety works are only applicable
to
• Shop, office or an approved ancillary office in industrial
premises
• Temporary Fire Permit (TFP) or a Fire Safety Certificate
(FSC) should have already been obtained.
|
|
| |
|
|
| |
The plans can be lodged by the following types of QPs:
• Registered architect; or
• Professional Engineer (Civil); or
• Professional Engineer (Structure); or
• Professional Engineer (Mechanical); or
• Professional Engineer (Electrical). |
|
| |
|
|
| |
|
|
| |
Criteria for Minor A&A |
|
| |
Works that do not affect the fire resistance of element of struction
and the fire compartment;
Works that do not affect means of escape;
Works that do not affect the wet / dry riser / landing / hosereel;
Works that do not involve change of usage;
Works that do not involve increase of floor area;
Works that do not involve raise floor system;
Works that do not involve conservation project;
Any other works which would not contravene the Act and the Regulations.
|
|
| |
|
|
| |
|
|
| |
Submission Procedures |
|
| |
a) Manual Submission |
|
| |
Within 21 days upon completion of the minor addition / alteration
works, the Qualified Person shall lodge the plan with the :
|
|
| |
|
|
| |
Fire Safety & Shelter Department
HQ Singapore Civil Defence Force
91 Ubi Avenue 4
Singapore 408827.
Click on the link to download the application form FSSD-MAA.
|
|
| |
|
|
| |
b) Electronic
Submission |
|
| |
Alternatively, the QP may also make on-line submissions through
the CORENET e-Submission.
The lodgement fee for each submission is $75.
|
|
| |
|
|
| |
|
|
| |
Compliance to the following guidelines |
|
| |
The plan shall comprise with the following:
• Site plan / location plan;
• Whole floor plan in detail - indicating clearly the exits
/ exit staircases available and the type of fire protection system
for the building;
• Detailed layout plan of the addition / alteration indicating:
o The usage of all rooms / areas / compartments;
o The contents of store(s);
o The existing fire doors with rating;
o The layout of sprinklers / detectors.
• Sectional plan of the proposed works;
• Details of partitions, including the type of construction
/ materials used;
• The QP shall endorse on the right hand side of the plan
as follows:
|
|
| |
|
|
| |
"I __________(Qualified Person's name) in accordance with
Regulation 4(5) of the Fire Safety (Building Fire Safety) Regulations
hereby certify that the Minor Addition/Alteration works have been
satisfactorily completed on _______ (date); and
"I certify that the addition / alteration works do not affect
the existing fire protection system in accordance with Regulation
4(5) of the Fire Safety (Building Fire Safety) Regulations";
or
"I certify that the addition / alteration works as shown in
these drawings affected the existing *sprinkler / automatic fire
alarm systems and I have supervised the works on site to ensure
that the said system(s) have been modified in accordance with Regulation
4(5) of the Fire Safety (Building Fire Safety) Regulations".
|
|
| |
|
|
| |
• All proposed works shall be coloured red on plan whereas
deletion shall be indicated in yellow dotted lines;
• The plans are to be signed by the applicant/tenant and the
Building Owner / Management Corporation.
• Space of 150 mm x 100 mm on top right hand corner shall
be kept blank for all plans for FSSD endorsement.
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|